Plan Review Details - Permit 12120229
Plan Review Stops For Permit 12120229
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-12-14 Cont ID  
Sent By jgomez Date 2012-12-14 Time 14:32 Rev Time 0.00
Received By jgomez Date 2012-12-14 Time 14:32 Sent To  
Notes
2012-12-14 14:33:18RAS 117 CALCS SUBMITTED. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-14 Cont ID  
Sent By jgomez Date 2012-12-14 Time 08:37 Rev Time 0.00
Received By jgomez Date 2012-12-14 Time 08:16 Sent To  
Notes
2012-12-14 08:50:01RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 09-0224.01 SUBMITTED. NEED THE NAIL ENHANCING
 CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. 1609.4.3 OF 2010 FBC.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATIONS WAS UPDATED AS REQUIRED BY SEC. 109.3
 OF CITY AMENDMENTS TO FBC. OWE THE PERMIT FEE BALANCE
 OF S$35.68. PAY THIS AT TIME OF PERMIT PICK UP.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-14 Cont ID  
Sent By jgomez Date 2012-12-14 Time 08:37 Rev Time 0.00
Received By jgomez Date 2012-12-07 Time 14:38 Sent To  
Notes
2012-12-13 14:38:52JG