Plan Review Details - Permit 12120170
Plan Review Stops For Permit 12120170
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-12-17 Cont ID  
Sent By rbrown Date 2012-12-17 Time 10:24 Rev Time 0.00
Received By rbrown Date 2012-12-17 Time 10:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-10 Cont ID  
Sent By rmcdouga Date 2012-12-10 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2012-12-10 Time 16:51 Sent To  
Notes
2012-12-11 06:37:212010 FBC
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE FLAT
 ROOF IS FOR A CEMENTITIOUS WOOD FIBER DECK. THIS IS NOT
 THE WOOD DECK THAT IS USUALLY FOUND ON SINGLE FAMILY
 RESIDENCES. PLEASE MAKE SURE THAT THIS IS A
 CEMENTITIOUS WOOD FIBER DECK. DCA RULE 9N-3
  
 2) SPECIFY THE APPROVED ASSEMBLY, FASTENING OPTION AND
 MAXIMUM DESIGN PRESSURE FOR THE SYSTEM LISTED IN THE
 PRODUCT APPROVAL THAT WILL BE INSTALLED. FBC R905.9.3
  
 3) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 ENHANCED FASTENING CALCULATIONS AS REQUIRED BY
 LIMITATION NUMBER 7 ON PAGE OF THE NOA FOR THE CORNER
 AND PERIMETER ROOF AREAS. FBC R301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]