Plan Review Stops For Permit 12120168 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2012-12-12 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2012-12-12 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2012-12-12 |
Time |
09:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2012-12-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2012-12-11 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2012-12-11 |
Time |
08:42 |
Sent To |
|
|
Notes |
2012-12-11 09:07:06 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | DIRECT-DECK ADHERED BORAL UNDERLAYMENT SPECIFIES THE | | MAXIMUM DESIGN PRESSURE AS -45 PSF. THE PROPOSED SYSTEM | | IS A FOAM ON TILE SYSTEM WITH THE BONDED UNDERLAYMENT | | FORMING PART OF THE LOAD-PATH AND THE DESIGN UPLIFT | | PRESSURE IS TOO LOW. THIS HOUSE IS LOCATED IN EXPOSURE | | CATEGORY D WITH A WIND SPEED OF 170 MPH VULT / 132 MPH | | VASD. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-12-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2012-12-11 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2012-12-06 |
Time |
12:09 |
Sent To |
|
|
Notes |
2012-12-07 12:09:54 | ON LUIS'S DESK |
|
|
|