Plan Review Details - Permit 12120056
Plan Review Stops For Permit 12120056
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-02-07 Cont ID  
Sent By jwitmer Date 2013-02-07 Time 11:36 Rev Time 0.00
Received By jwitmer Date 2013-02-07 Time 11:36 Sent To  
Notes
2013-02-07 11:36:56BUILDING PLAN REVIEW
 PERMIT: 12120056
 ADD: 4011 BROADWAY
 CONT: ALFONSO CRUZ
 TEL: (561)585-2429
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 FEB. 07/2013
 ACTION: DENIED
  
 1) THE PLANS INDICATE CREATING A PASSAGEWAY BETWEEN
 TENANT SPACES. A PERMIT WAS PULLED IN 1990, PERMIT #
 90A01897 FOR A TAKE OUT RESTARAUNT. IS THIS THE
 EXISTING KITCHEN. PLEASE PROVIDE A COMPLETE PLAN OF THE
 WHOLE OF THE TENANT SPACE WITH THE EXISTING KITCHEN.
 PLEASE ALSO PROVIDE SEATING, TABLES AND CHAIRS FOR THE
 NEW DINING AREA, PROVIDE THE ACTUAL OCCUPANT LOAD USING
 15 SQUARE FEET PER OCCUPANT.
  
 MISSING INFORMATION FOR THE MINIMUM CRITERIA FOR
 COMMERCIAL PLAN REVIEW:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE
 PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS
 LAYOUT; ALL FENESTRATION PENETRATIONS;
 FLASHING; AND ROUGH OPENING DIMENSIONS; AND ALL
 EXTERIOR ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 2. OCCUPANCY GROUP 303.1
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES TABLE 1004.1.1 USE
 15 SQ FT / 900/ 15= 60 OCCUPANTS A3 OCCUPANCY.
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: 60
 OCCUPANTS X.2
 OCCUPANCY LOAD60
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 8 STRUCTURAL REQUIREMENTS, CUTTING THROUGH A BLOCK
 WALL, LINTEL REQUIRED
 10 . ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 ACCESSIBLE ROUTE
 TOILET FACILITIES SEE PLUMBING COMMENTS AS TO TWO
 RESTROOMS REQUIRED.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-11 Cont ID  
Sent By jwitmer Date 2012-12-11 Time 15:50 Rev Time 0.00
Received By jwitmer Date 2012-12-11 Time 15:50 Sent To  
Notes
2012-12-11 15:52:50BUILDING PLAN REVIEW
 PERMIT: 12120056
 ADD: 4011 BROADWAY
 CONT: ALFONSO CRUZ
 TEL: (561)585-2429
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DEC. 11/ 2012
 ACTION: DENIED
  
 1) THE PLANS INDICATE CREATING A PASSAGEWAY BETWEEN
 TENANT SPACES. A PERMIT WAS PULLED IN 1990, PERMIT #
 90A01897 FOR A TAKE OUT RESTARAUNT. IS THIS THE
 EXISTING KITCHEN. PLEASE PROVIDE A COMPLETE PLAN OF THE
 WHOLE OF THE TENANT SPACE WITH THE EXISTING KITCHEN.
 PLEASE ALSO PROVIDE SEATING, TABLES AND CHAIRS FOR THE
 NEW DINING AREA, PROVIDE THE ACTUAL OCCUPANT LOAD USING
 15 SQUARE FEET PER OCCUPANT.
  
 MISSING INFORMATION FOR THE MINIMUM CRITERIA FOR
 COMMERCIAL PLAN REVIEW:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE
 PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS
 LAYOUT; ALL FENESTRATION PENETRATIONS;
 FLASHING; AND ROUGH OPENING DIMENSIONS; AND ALL
 EXTERIOR ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 8 STRUCTURAL REQUIREMENTS, CUTTING THROUGH A BLOCK
 WALL, LINTEL REQUIRED
 10 . ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 ACCESSIBLE ROUTE
 TOILET FACILITIES SEE PLUMBING COMMENTS AS TO TWO
 RESTROOMS REQUIRED.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-02-15 Cont ID  
Sent By rlecky Date 2013-02-15 Time 14:10 Rev Time 0.00
Received By rlecky Date 2013-02-15 Time 14:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-12-26 Cont ID  
Sent By rlecky Date 2012-12-26 Time 13:57 Rev Time 0.00
Received By rlecky Date 2012-12-21 Time 15:42 Sent To  
Notes
2012-12-26 13:58:23 
 12120056
 4011 BROADWAY
 INTERIOR RENOVATION TO BATHROOM
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENT.
  
 PROVIDE AN ELECTRICAL RISER PLAN SHOWING THE EXISTING
 SERVICE SIZE. SHOW CONDUIT AND FEEDERS TO THE RELOCATED
 PANEL BOARD. INDICATE SIZE OF PANEL BOARD AND LOCATION
 OF MAIN DISCONNECT. NEC 215.5
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-02-02 Cont ID  
Sent By wjolin Date 2013-02-02 Time 20:16 Rev Time 0.00
Received By wjolin Date 2013-02-02 Time 19:50 Sent To  
Notes
2013-02-02 20:15:434011 BROADWAY
 PERMIT #12120056
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE TWO COMBINED DINING AREAS OF 375 SQ.FT. AND 525
 SQ.FT. RESULT IN AN OCCUPANT LOAD OF 60 PERSONS. THIS
 INCREASE IN OCCUPANT LOAD WILL CHANGE THE OCCUPANCY
 CLASSIFICATION FROM MERCANTILE TO ASSEMBLY.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 ASSEMBLY OCCUPANCIES REQUIRE EMERGENCY LIGHTING.
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1-1/2 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 NO EXIT DOOR INFORMATION PROVIDED. DOORS SHALL BE
 ARRANGED TO BE OPENED READILY FROM THE EGRESS SIDE
 WHENEVER THE BUILDING IS OCCUPIED. LOCKS, IF PROVIDED,
 SHALL NOT REQUIRE THE USE OF A KEY, TOOL, OR SPECIAL
 KNOWLEDGE OR EFFORT FOR OPERATION FROM THE EGRESS
 SIDE.THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS
 SHALL OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9
 OF NFPA 101 FLORIDA EDITION 2007.
  
 EVACUATION DIAGRAMS SHALL BE POSTED IN ASSEMBLY
 OCCUPANCIES.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-12-08 Cont ID  
Sent By wjolin Date 2012-12-08 Time 19:28 Rev Time 0.00
Received By wjolin Date 2012-12-08 Time 19:15 Sent To  
Notes
2012-12-08 19:28:044011 BROADWAY
 PERMIT #12120056
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL OF THE CITY'S RECORDS INDICATE THE ADDRESS OF THIS
 BUSINESS AS 4013 BROADWAY. CORRECT PERMIT APPLICATION
 AND DRAWINGS.
  
 THE PLANS INDICATE THERE WILL BE NEW FRAMED OPENING
 INTO THE ADJACENT TENANT SPACE. WHAT PURPOSE DOES THIS
 OPENING SERVE? INDICATE THE OCCUPANCY TYPE AND OCCUPANT
 LOAD OF THE ADJACENT TENANT.
  
 THE PLANS INDICATE THIS SPACE IS AN EXISTING
 RESTAURANT; HOWEVER, NO KITCHEN AREA CAN BE LOCATED ON
 THE PLANS.
  
 PROVIDE A FURNITURE/SEATING LAYOUT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-15 Cont ID  
Sent By rlecky Date 2013-02-15 Time 14:10 Rev Time 0.00
Received By rlecky Date 2013-01-30 Time 09:23 Sent To  
Notes
2013-01-31 09:23:39SENT TO B5 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-26 Cont ID  
Sent By rlecky Date 2012-12-26 Time 13:58 Rev Time 0.00
Received By rlecky Date 2012-12-06 Time 09:08 Sent To  
Notes
2012-12-06 09:09:10INCOMING SENT TO B03 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-02-11 Cont ID  
Sent By hmoser Date 2013-02-11 Time 14:49 Rev Time 0.00
Received By hmoser Date 2013-02-11 Time 14:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-12-12 Cont ID  
Sent By lmartine Date 2012-12-12 Time 13:44 Rev Time 0.00
Received By lmartine Date 2012-12-12 Time 13:44 Sent To  
Notes
2012-12-12 13:49:54*** CORRECTIONS REQUIRED ***
  
 1) PROVIDE FOR EXHAUST AIR IN BATHROOM, PER 2010 FBC/M
 403.3 & TABLE 403.3.
  
 *** MECHANICAL PLAN REVIEW BY: TOM GORDON (HY-BYRD
 INC.)
 *** FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2013-02-05 Cont ID  
Sent By lwagner Date 2013-02-05 Time 11:16 Rev Time 0.00
Received By lwagner Date 2013-02-05 Time 10:26 Sent To  
Notes
2013-02-05 11:15:18FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #2
 DENIED:
  
 403.2 SEPARATE FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX.
 EXCEPTIONS:
 2. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR FOOD
 SERVICE ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS.
  
 IF THE RESTROOM IN THE EXISTING KITCHEN IS TO BE
 COUNTED, THE ROUTE SHALL NOT BE THROUGH THE KITCHEN,
 STORAGE, ETC.
 403.3.1 ACCESS.
 THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY
 SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES
 SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR
 OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO
 THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE
 BUILDING IS OCCUPIED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-12-10 Cont ID  
Sent By lwagner Date 2012-12-10 Time 15:40 Rev Time 0.00
Received By lwagner Date 2012-12-10 Time 14:38 Sent To  
Notes
2012-12-10 15:23:18FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
  
 MORE INFORMATION WILL BE REQUIRED FOR A REVIEW. IS THIS
 A NEW RESTAURANT OR ADDITIONAL SPACE FOR AN EXISTING
 RESTAURANT? PLEASE INCLUDE THE OCCUPANCY TYPE, THE
 AMOUNT OF SEATS, AND OCCUPANCY LOAD.
 403.2 SEPARATE FACILITIES.
 WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE
 FACILITIES SHALL BE PROVIDED FOR EACH SEX.
  
 EXCEPTIONS:
 2. SEPARATE FACILITIES SHALL NOT BE REQUIRED FOR FOOD
 SERVICE ESTABLISHMENTS WHICH SEAT 10 PERSONS OR LESS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2012-12-07 Cont ID  
Sent By ajones Date 2012-12-07 Time 15:56 Rev Time 0.00
Received By ajones Date 2012-12-07 Time 15:56 Sent To  
Notes
***NONE***