Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-11-30 Cont ID  
Sent By rlecky Date 2012-11-30 Time 10:49 Rev Time 0.00
Received By rlecky Date 2012-11-30 Time 10:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-26 Cont ID  
Sent By rlecky Date 2012-11-26 Time 09:18 Rev Time 0.00
Received By rlecky Date 2012-11-26 Time 08:57 Sent To  
Notes
2012-11-20 15:57:42PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
 VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED
 WORKING SPACE HAS BEEN PROVIDED AT THE ELECTRICAL
 SERVICE. NEC 110.26, 240.24
 PROVIDE A LOAD CALCULATION FOR THE MAIN SERVICE FEED.
 NEC 220.40
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-30 Cont ID  
Sent By rlecky Date 2012-11-30 Time 10:49 Rev Time 0.00
Received By rlecky Date 2012-11-30 Time 10:49 Sent To  
Notes
2012-11-30 10:49:39CONTRACTOR SUBMITTED REVISIONS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-26 Cont ID  
Sent By rlecky Date 2012-11-26 Time 09:22 Rev Time 0.00
Received By rlecky Date 2012-11-20 Time 15:57 Sent To  
Notes
***NONE***