Plan Review Details - Permit 12110467
Plan Review Stops For Permit 12110467
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-21 Cont ID  
Sent By tgordon Date 2012-12-21 Time 14:02 Rev Time 0.00
Received By tgordon Date 2012-12-21 Time 10:44 Sent To  
Notes
2012-12-21 10:44:42SENT TO TOM GORDON'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-04 Cont ID  
Sent By lmartine Date 2012-12-04 Time 15:08 Rev Time 0.00
Received By lmartine Date 2012-11-15 Time 17:21 Sent To  
Notes
2012-11-16 17:26:47IN MECHANICAL BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-12-21 Cont ID  
Sent By tgordon Date 2012-12-21 Time 13:42 Rev Time 0.00
Received By tgordon Date 2012-12-21 Time 12:17 Sent To  
Notes
2012-12-21 13:48:40*** PROVISO ***
 1) PROVIDE OUTDOOR AIR, PER 2010 FBC/M 403.3.
 2) COMPLY WITH 2010 FBC/ENERGY 503.2.4.4 SHUTOFF DAMPER
 CONTROLS.
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-12-04 Cont ID  
Sent By lmartine Date 2012-12-04 Time 14:51 Rev Time 0.00
Received By lmartine Date 2012-12-04 Time 14:51 Sent To  
Notes
2012-12-04 14:59:03*** CORRECTIONS NEEDED TO MECHANICAL PLANS ***
  
 1) PLEASE SUBMIT COOLING LOAD CAL'S., PER 2010
 FBC/ENERGY 503.2.1.
  
 2) PLEASE SUBMIT ENERGY CAL'S., PER 2010 FBC/ENERGY
 501.2.
  
 MECHANICAL PLAN REVIEW BY: TOM GORDON (HY-BYRD INC.)
 FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710