Plan Review Details - Permit 12110439
Plan Review Stops For Permit 12110439
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-12-28 Cont ID  
Sent By tgordon Date 2012-12-28 Time 11:16 Rev Time 0.00
Received By tgordon Date 2012-12-28 Time 11:16 Sent To  
Notes
2012-12-28 11:30:51*** PROVISO ***
 1) HAVE A PRODUCT APPROVAL FOR THE A/C CONDENSER STAND
 REVIEWED AND ON JOB-SITE BEFORE FINAL INSPECTION.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 1, 2010, (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (G)
 EXTERIOR COOLER, FREEZERS & "PER-ENGINEERED A/C
 STANDS". ALSO SEE 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 2) ALSO COMPLY WITH 2010 FBC/ENERGY 503.2.4.4 SHUTOFF
 DAMPER CONTROLS. BOTH OUTDOOR AIR SUPPLY AND EXHAUST
 DUCTS SHALL BE EQUIPPED WITH DAMPERS THAT WILL
 AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED
 ARE NOT IN USE.
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732