Plan Review Details - Permit 12110332
Plan Review Stops For Permit 12110332
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-01-24 Cont ID  
Sent By jwitmer Date 2013-01-24 Time 09:45 Rev Time 0.00
Received By jwitmer Date 2013-01-24 Time 09:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-01-11 Cont ID  
Sent By jwitmer Date 2013-01-11 Time 09:17 Rev Time 0.00
Received By jwitmer Date 2013-01-11 Time 09:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-04 Cont ID  
Sent By jwitmer Date 2012-12-04 Time 11:47 Rev Time 0.00
Received By jwitmer Date 2012-12-04 Time 11:41 Sent To  
Notes
2012-12-04 11:57:18BUILDING PLAN REVIEW
 PERMIT: 12110332
 ADD: 250 S AUSTRALIAN AVE # 200
 CONT: CHANDLIER CONSTRUCTION
 TEL: (561)313-0297
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE A DEMOLITION PLAN OF THE EXISTING
 SPACE, THE LAST ISSUED PERMIT FOR THIS SPACE WAS A
 DEMOLITION PERMIT 08110276 WHICH STILL HAD A CORRIDOR
 THAT LEAD FROM THE ELEVATOR LOBBY AREA TO THE WEST SET
 OF STAIRS. THE ADJACENT TENANT SPACE SHADED IN GREY
 DOES NOT HAVE ACCESS TO A STAIRWELL WITHOUT GOING
 THROUGH THE ELEVATOR LOBBY.
  
 2010 EXIST BLDG CODE SECTION 703.2.2 SUPPLEMENTAL SHAFT
 AND FLOOR OPENING ENCLOSURE REQUIREMENTS.
 WHERE THE WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF
 THAT FLOOR AREA, THE ENCLOSURE REQUIREMENTS OF SECTION
 703.2 SHALL APPLY TO VERTICAL OPENINGS OTHER THAN
 STAIRWAYS THROUGHOUT THE FLOOR. THIS WILL ENCLUDE THE
 NEED FOR ENCLOSURE OF ELEVATOR LOBBIES OR ONE OF THE
 SIX EXCEPTIONS, PLEASE SEE THE MEMORANDUM ON:
  
 ELEVATOR LOBBIES IN EXISTING HIGH RISE CONSTRUCTION
  
 DATE: JANUARY 3, 2011
  
 IT HAS RECENTLY BEEN BROUGHT TO OUR ATTENTION THAT MANY
 EXISTING HIGH RISE STRUCTURES IN OUR COMMUNITY WERE
 INITIALLY CONSTRUCTED OR HAVE BEEN SUBSEQUENTLY
 MODIFIED SO AS TO BE WITHOUT ?ELEVATOR LOBBIES?.
 ELEVATOR LOBBIES ARE FIRE RATED ENCLOSURES, ENCLOSING
 THE ELEVATOR SHAFT ITSELF WITH EACH FLOOR ABOVE THE
 FIRST FLOOR. THE LACK OF AN ELEVATOR LOBBY CAN, UNDER
 CERTAIN CONDITIONS, CONSTITUTE A SERIOUS CONCERN BY
 CREATING INCREASED POTENTIAL FOR SPREAD OF SMOKE OR
 FIRE THOUGH AN EXISTING HIGH RISE STRUCTURE DURING A
 FIRE EVENT.
 RESEARCH BY CITY STAFF INDICATES THE REQUIREMENT FOR
 RATING OF ELEVATOR SHAFT ENCLOSURES WAS CLEARLY
 IDENTIFIED IN THE 1929 CITY OF WEST PALM BEACH BUILDING
 CODE IN SECTIONS 1807 AND 1907 RESPECTIVELY, FOR TYPE I
 AND TYPE II STRUCTURES OVER THREE (3) STORIES, AS TWO
 (2) HOURS MINIMUM, AND ONE (1) HOUR FOR TYPE III
 STRUCTURES (SEE ATTACHED EXHIBIT 1). BY 1965 THE
 SOUTHERN STANDARD BUILDING CODE IN EFFECT IN THE CITY
 REQUIRED ELEVATOR ENCLOSURES WHICH ENCLOSED NOT MORE
 THAN THREE (3) ELEVATORS TO BE ENCLOSED IN TWO (2) HOUR
 RATED ENCLOSURES IN A SINGLE SECTION WHICH WAS SECTION
 701.3 (SEE EXHIBIT 2). INTERESTINGLY, THE TERM
 ?ELEVATOR LOBBY? ITSELF DOES NOT APPEAR IN THE BUILDING
 CODE ITSELF UNTIL SOMETIME BETWEEN THE 1973 AND 1978
 EDITIONS. HOWEVER, AS PREVIOUSLY STATED, THE
 REQUIREMENT FOR FIRE RATING ELEVATOR SHAFT ENCLOSURES
 AND ALL OPENINGS THERETO DATES AS FAR BACK AS 1929. THE
 1965 CODE ALSO REQUIRED THAT, ?THE PATH OF TRAVEL FROM
 ONE FLIGHT OF STAIRS TO THE NEXT SHALL NOT PASS
 DIRECTLY IN FRONT OF ELEVATOR DOORS.? THIS CRITERIA IS
 CONSISTENT WITH CURRENT CODE REQUIREMENT WHICH PROVIDES
 THAT ONLY ONE OF THE TWO REQUIRED STAIRS MAY OPEN INTO
 THE ELEVATOR LOBBY AND THAT EACH TENANCY IN A MULTIPLE
 TENANT CONDITION SHALL HAVE ACCESS TO BOTH STAIRS, AT
 LEAST ONE OF WHICH MAY BE ACCESSED WITHOUT PASSING
 THROUGH THE ELEVATOR LOBBY.
 TO SUMMARIZE CITY STAFF?S RESEARCH, THE REQUIREMENT FOR
 FIRE RATING OF AN ELEVATOR SHAFT ENCLOSURE HAS BEEN
 IDENTIFIED TO EXIST IN EVERY BUILDING CODE ADOPTED IN
 THIS CITY FROM THE 1930?S TO THE PRESENT DAY WITH ONLY
 ONE NOTABLE EXCEPTION. ON OCTOBER 1, 2005 WITH THE
 ENACTMENT OF THE 2004 FLORIDA BUILDING CODE, THE
 REQUIREMENT WAS AMENDED TO ALLOW THE ELIMINATION OF THE
 FIRE RATED ENCLOSURE IF THE CORRIDOR INTO WHICH THE
 ELEVATOR OPENED WAS NOT REQUIRED ITSELF TO BE RATED
 (SEE EXHIBIT 3). THIS REQUIREMENT WAS AMENDED AGAIN ON
 DECEMBER 8, 2006 WITH THE FIRST ?BLUE PAGE? AMENDMENTS
 TO THE 2004 FLORIDA BUILDING CODE (SEE EXHIBIT 4) WHICH
 RE-INSTITUTED THE REQUIREMENT FOR A FIRE RATED ELEVATOR
 LOBBY WITH THE SPECIFIC LIMITED EXCEPTIONS THAT EXIST
 TODAY (SEE EXHIBIT 5). THIS MEANS THAT BUILDINGS WHICH
 DO NOT MEET THE CURRENT (OR 1929) CODE MAY BE DEEMED
 ?LEGALLY-EXISTING NON-CONFORMING? IF A PERMIT WHICH
 DEMONSTRATES THE ELIMINATION OF SUCH A LOBBY CAN BE
 EVIDENCED WHICH WAS ISSUED ONLY DURING THE
 ABOVE-REFERENCED NARROW ?WINDOW? OF TIME BETWEEN
 OCTOBER 1, 2005 AND DECEMBER 8, 2006. HOWEVER, EVEN
 LEGALLY-EXISTING NON-CONFORMITIES MUST ALSO BE
 ADDRESSED AS RENOVATIONS OCCUR IN ACCORDANCE THE TERMS
 THAT FOLLOW.
 TO BETTER PREPARE BUILDING OWNERS, MANGERS, OPERATORS,
 AND DESIGN PROFESSIONALS TO ANTICIPATE AND ADDRESS
 THESE SPECIFIC CODE REQUIREMENTS, THE CONSTRUCTION
 SERVICES DEPARTMENT AND FIRE PREVENTION DEPARTMENT
 PROPOSE TO ADDRESS THE ABSENCE OF AN ELEVATOR LOBBY
 (WHEN REQUIRED) AS FOLLOWS:
  
 1. IF A TENANT IMPROVEMENT IS SUBMITTED WHICH PROPOSES
 TO RECONFIGURE THE ENTIRE EXISTING BUILDING FLOOR, AN
 ELEVATOR LOBBY, OR COMPLIANCE WITH ONE OF THE SIX (6)
 EXCEPTIONS ALLOWED UNDER THE PRESENT CODE WILL BE
 REQUIRED. THIS IS REGARDLESS OF WHETHER OR NOT THE
 ABSENCE OF AN ELEVATOR LOBBY CAN BE DEMONSTRATED WITH A
 VALID PERMIT ISSUED BETWEEN OCTOBER 1, 2005 AND
 DECEMBER 8, 2006.
 2. IF A TENANT IMPROVEMENT IS SUBMITTED WHICH PROPOSES
 TO RECONFIGURE A PORTION OF THE EXISTING BUILDING FLOOR
 AREA, WITH NO WORK BEING PROPOSED IN THE AREA OF THE
 ELEVATOR LOBBY, AND NO ELEVATOR LOBBY IS FOUND TO EXIST
 ON THE FLOOR, AND A VALID PERMIT CAN BE EVIDENCED WHICH
 WAS ISSUED BETWEEN OCTOBER 1, 2005 AND DECEMBER 8,
 2006, THE TENANT IMPROVEMENT PERMIT MAY BE APPROVED AND
 THE BUILDING SHALL REMAIN AS LAWFULLY CONFIGURED UNTIL
 THE MAJORITY OF THE EXISTING FLOOR PLAN, OR THE
 ELEVATOR LOBBY AREA ITSELF UNDERGOES RENOVATION.
 3. IF A TENANT IMPROVEMENT IS SUBMITTED WHICH PROPOSES
 TO RECONFIGURE A PORTION OF THE EXISTING BUILDING FLOOR
 AREA, WITH NO WORK BEING PROPOSED IN THE AREA OF THE
 ELEVATOR LOBBY, AND NO ELEVATOR LOBBY IS FOUND TO EXIST
 ON THE FLOOR, AND NO VALID PERMIT CAN BE EVIDENCED
 WHICH WAS ISSUED BETWEEN OCTOBER 1, 2005 AND DECEMBER
 8, 2006, THE TENANT IMPROVEMENT PERMIT MAY BE APPROVED.
 THE BUILDING OWNER WILL BE NOTIFIED OF AN UNSAFE
 CONDITION ON THE EXISTING STRUCTURE BY THE CITY FIRE
 MARSHAL?S OFFICE AND ASKED TO UNDERTAKE APPROPRIATE
 ACTIONS TO CORRECT THE SITUATION.
 4. IF ANY RECONFIGURATION IS PROPOSED WHICH AFFECTS THE
 ELEVATOR LOBBY AREA ITSELF, AN ELEVATOR LOBBY, OR
 COMPLIANCE WITH ONE OF THE SIX (6) EXCEPTIONS LISTED IN
 THE CODE SHALL BE REQUIRED.
  
 IT SHOULD BE NOTED THAT CITY STAFF REMAINS COMMITTED TO
 ASSISTING BUILDING OWNERS, MANAGERS, AND DESIGN
 PROFESSIONALS IN SUCCEEDING IN CREATING AND MAINTAINING
 SAFE PLACES TO LIVE AND WORK IN OUR COMMUNITY. WE ARE
 READY AND WILLING TO PROVIDE TECHNICAL ASSISTANCE IN
 UNDERSTANDING THE OFTEN COMPLEX CRITERIA THAT AFFECT
 EXISTING AND NEW HIGH RISE BUILDINGS. IT MUST BE STATED
 THAT THE SIMPLE INSTALLATION OF A HOIST-WAY
 PRESSURIZATION SYSTEM MAY BE ONE POTENTIAL METHOD TO
 ELIMINATE THE NEED FOR AN ELEVATOR LOBBY THROUGHOUT AN
 ENTIRE BUILDING. ANOTHER ALTERNATIVE IS TO INSTALL FIRE
 SHUTTERS AT THE ELEVATOR DOOR OPENINGS. THESE
 METHODOLOGIES MAY OFFER THE ADDED POTENTIAL TO INCREASE
 THE LEASABLE FLOOR AREA WITHIN THESE BUILDINGS.
  
 PLEASE FEEL FREE TO CONTACT US DIRECTLY IF WE CAN
 ASSIST YOU FURTHER IN UNDERSTANDING THESE CRITERIA AND
 HELP YOU TO ENSURE THE SAFETY OF YOUR RESIDENTS,
 TENANTS, AND PROPERTY.
  
 DOUG WISE ? 805-6650 ? [email protected]
 MIKE CARSILLO ? 804-4709 ? [email protected]
  
 2) PLEASE PROVIDE HOW THE CARD READERS ON DOORS 203 &
 231 WILL WORK TO ALLOW ENTRY TO THE WEST STAIRWELL DOOR
 IN CASE OF ELEVATOR LOBBY AREA FULL OF SMOKE AND
 THIS IS THE ONLY EMERGENCY ACCESS? FBC-B 1008.1.4.4.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-01-14 Cont ID  
Sent By rlecky Date 2013-01-14 Time 12:25 Rev Time 0.00
Received By rlecky Date 2013-01-14 Time 12:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-30 Cont ID  
Sent By rlecky Date 2012-11-30 Time 16:28 Rev Time 0.00
Received By rlecky Date 2012-11-27 Time 15:51 Sent To  
Notes
2012-11-30 16:29:2112110332
 250 S AUSTRALIAN AVENUE # 200
 COMMERCIAL INTERIOR ( DIGITAL)
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENT.
  
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GFCIS. NEC 422.52
  
 VENDING MACHINES SHALL BE PROTECTED WITH GFCIS. NEC
 422.51
  
 INDICATE ON THE PLAN THE LOCATION OF THE PANEL BOARDS,
 TRANSFORMER AND FEEDERS. VERIFY SAFETY CLEARANCES HAVE
 BEEN OBSERVED. NEC 215.5, 110.26
  
 NOTE:
 SEPARATE PERMIT ARE REQUIRED FOR VOICE, DATA AND FIRE
 ALARM.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-01-30 Cont ID  
Sent By wjolin Date 2013-01-30 Time 12:31 Rev Time 0.00
Received By wjolin Date 2013-01-28 Time 14:23 Sent To  
Notes
2013-01-30 12:18:42250 SOUTH AUSTRALIAN AVENUE - SUITE #200
 PERMIT #12110332
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1.0: DOOR #203 WILL BE EQUIPPED WITH A
 DELAYED-EGRESS LOCKING SYSTEM, THEREFORE, THE FOLLOWING
 APPLIES:
  
 DOOR ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE
 PERMITTED TO BE ELECTRICALLY LOCKED IF EQUIPPED WITH
 APPROVED, LISTED HARDWARE THAT INCORPORATES A BUILT-IN
 SWITCH, PROVIDED THAT THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5) LOSS OF POWER TO THE HARDWARE AUTOMATICALLY UNLOCKS
 THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
  
 AN IRREVERSIBLE PROCESS SHALL RELEASE THE LOCK WITHIN
 15 SECONDS, UPON APPLICATION OF A FORCE TO THE RELEASE
 DEVICE REQUIRED IN 7.2.1.5.9 UNDER THE FOLLOWING
 CONDITIONS:
 (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF
 (67 N).
 (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY
 APPLIED FOR MORE THAN 3 SECONDS.
 (C) THE INITIATION OF THE RELEASE PROCESS SHALL
 ACTIVATE AN AUDIBLE SIGNAL IN THE VICINITY OF THE DOOR
 OPENING.
 (D) ONCE THE LOCK HAS BEEN RELEASED BY THE APPLICATION
 OF FORCE TO THE RELEASING DEVICE, RELOCKING SHALL BE BY
 MANUAL MEANS ONLY.
 (5) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1-INCH HIGH AND NOT LESS THAN 1/8-INCH IN STROKE
 WIDTH ON A CONTRASTING BACKGROUND THAT READS AS FOLLOWS
 SHALL BE LOCATED ON THE DOOR LEAF ADJACENT TO THE
 RELEASE DEVICE:
 PUSH UNTIL ALARM SOUNDS - DOOR CAN BE OPENED IN 15
 SECONDS
  
 SHEET E2.1: PROVIDE AN EXIT SIGN ON THE EAST SIDE OF
 DOOR #203.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-01-17 Cont ID  
Sent By wjolin Date 2013-01-17 Time 11:30 Rev Time 0.00
Received By wjolin Date 2013-01-17 Time 10:32 Sent To  
Notes
2013-01-17 11:30:12250 SOUTH AUSTRALIAN AVENUE - SUITE #200
 PERMIT #12110332
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1-0: SEVERAL EXIT ACCESS DOORS ARE EQUIPPED WITH
 KEYPADS THAT WILL PROHIBIT OCCUPANTS FROM THE
 HEARING/MEDIATION AREAS FROM FREE ACCESS TO A SECONDARY
 EXIT (WEST STAIR). HAVING DOORS THAT SIMPLY UNLOCK WITH
 FIRE ALARM ACTIVATION DOES SATISFY THE REQUIREMENTS FOR
 ACCESS-CONTROLLED EGRESS.
  
 SHEET A1-0: DOOR #203 SERVES MORE THAN 50 PERSONS FROM
 THE HEARING/MEDIATION SIDE BUT DOES NOT SWING IN THE
 DIRECTION OF TRAVEL FOR THESE OCCUPANTS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-11-30 Cont ID  
Sent By wjolin Date 2012-11-30 Time 10:40 Rev Time 0.00
Received By wjolin Date 2012-11-29 Time 14:30 Sent To  
Notes
2012-11-30 10:07:39250 SOUTH AUSTRALIAN AVENUE - SUITE #200
 PERMIT #12110332
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 LIFE SAFETY PLAN: NO EXIT SIGNAGE PROVIDED ON PLANS.
  
 SHEET A1-0: THE ADJACENT TENANT SPACE APPEARS TO ONLY
 HAVE ACCESS TO ONE EXIT (EAST STAIR).
  
 SHEET A1-0: SEVERAL EXIT ACCESS DOORS ARE EQUIPPED WITH
 KEYPADS THAT WILL PROHIBIT OCCUPANTS FROM FREE ACCESS
 TO A SECONDARY EXIT (WEST STAIR). DOORS REQUIRE FREE
 EGRESS OR MUST COMPLY WITH THE FOLLOWING:
  
 SECTION 7.2.1.6.2 OF NFPA 101 FLORIDA EDITION 2009
 ALLOWS ACCESS CONTROLLED EGRESS DOORS PROVIDED THAT ALL
 SEVEN OF THE FOLLOWING CRITERIA ARE MET:
 1.A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
 SECTION 7.2.1.5.5 OF NFPA 101 FLORIDA EDITION 2009
 ALLOWS ELECTRICALLY CONTROLLED EGRESS DOOR ASSEMBLIES
 IF EQUIPPED WITH APPROVED LISTED HARDWARE THAT
 INCORPORATES A BUILT-IN SWITCH AND THE FOLLOWING FIVE
 CRITERIA ARE MET:
 1. THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 2. THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION THAT
 IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 3. THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 4. OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 5. LOSS OF POWER TO THE HARDWARE AUTOMATICALLY UNLOCKS
 THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 NOTE: THESE REQUIREMENTS ARE DIFFERENT THAN THE
 REQUIREMENTS OF FOR MAGNETIC LOCKS WHEREBY AN OCCUPANT
 SENSOR AND PUSH TO EXIT BUTTON ARE NEEDED IN ON THE
 EGRESS SIDE.
  
 SHEET E2-1: NO EXIT SIGNAGE PROVIDED ON PLANS.
  
 SHEET FA0-1: PLANS INDICATE THE USE OF THE HORN-STROBE
 DEVICES; VERIFY EXISTING FIRE ALARM SYSTEM IS NOT
 EQUIPPED WITH SPEAKER-STROBE NOTIFICATION APPLIANCES.
  
 SHEET FA2-1: PROVIDE FIRE ALARM NOTIFICATION DEVICE IN
 BATHROOMS #218 & #219.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-01-30 Cont ID  
Sent By rregueir Date 2013-01-30 Time 13:56 Rev Time 0.00
Received By rregueir Date 2013-01-23 Time 11:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-18 Cont ID  
Sent By rregueir Date 2013-01-17 Time 14:43 Rev Time 0.00
Received By rregueir Date 2013-01-10 Time 13:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-12-06 Time   Rev Time 0.00
Received By rregueir Date 2012-11-13 Time 13:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-12-06 Cont ID  
Sent By rregueir Date 2012-12-06 Time 14:53 Rev Time 0.00
Received By rregueir Date 2012-12-06 Time 14:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-12-05 Cont ID  
Sent By lwagner Date 2012-12-05 Time 12:35 Rev Time 0.00
Received By lwagner Date 2012-12-05 Time 12:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-01-30 Cont ID  
Sent By rregueir Date 2013-01-30 Time 13:56 Rev Time 0.00
Received By rregueir Date 2013-01-30 Time 13:56 Sent To  
Notes
***NONE***