Plan Review Details - Permit 12110304
Plan Review Stops For Permit 12110304
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-11-13 Cont ID  
Sent By rlecky Date 2012-11-13 Time 14:56 Rev Time 0.00
Received By rlecky Date 2012-11-13 Time 14:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-13 Cont ID  
Sent By rlecky Date 2012-11-13 Time 08:35 Rev Time 0.00
Received By rlecky Date 2012-11-13 Time 08:30 Sent To  
Notes
2012-11-13 08:34:51PLEASE PROVIDE MORE INFORMATION.
  
 SHOW LOCATION OF SERVICE, INCLUDE AN ELECTRICAL RISER
 PLAN WITH THE METER, GROUNDING , CONDUIT AND WIRE
 SIZES. INCLUDE LOCATION AND SIZE OF MAIN DISCONNECT.
 NEC 215.5
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
 561-805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-13 Cont ID  
Sent By rlecky Date 2012-11-13 Time 14:56 Rev Time 0.00
Received By rlecky Date 2012-11-13 Time 14:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-13 Cont ID  
Sent By rlecky Date 2012-11-13 Time 08:35 Rev Time 0.00
Received By rlecky Date 2012-11-09 Time 15:21 Sent To  
Notes
2012-11-09 15:22:16INCOMING SENT TO <$5K ELECTRIC BOX. JW