Plan Review Details - Permit 12110167
Plan Review Stops For Permit 12110167
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-11-16 Cont ID  
Sent By lmartine Date 2012-11-16 Time 09:56 Rev Time 0.00
Received By lmartine Date 2012-11-16 Time 09:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-13 Cont ID  
Sent By rmcdouga Date 2012-11-13 Time 15:32 Rev Time 0.00
Received By rmcdouga Date 2012-11-13 Time 14:41 Sent To  
Notes
2012-11-13 14:57:252010 FBC
  
 REVISION IS DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED NOA NO.
 08-0221.04 HAS BEEN SUPERSEDED BY NOA NO.08-0922.04.
 PLEASE SUBMIT THE CURRENT PRODUCT APPROVAL. DCA RULE
 9N-3
  
 2) THE ENGINEERING SPECIFIES AN ALLOWABLE UPLIFT
 PRESSURE OF -457.5 PSF FOR THE APPROVED ASSEMBLY THAT
 WILL BE INSTALLED. THE ASSEMBLY WITH THIS MAXIMUM
 DESIGN PRESSURE IS FOR NON-INSULATED CONCRETE DECKS.
 HOWEVER, THE APPROVED ASSEMBLY THAT WAS SUBMITTED (PAGE
 8 OF 27) IS FOR AND INSULATED CONCRETE DECK WITH A
 MAXIMUM DESIGN PRESSURE OF -140 PSF. PLEASE CORRECT.
 CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-16 Cont ID  
Sent By lmartine Date 2012-11-16 Time 09:56 Rev Time 0.00
Received By lmartine Date 2012-11-14 Time 15:23 Sent To  
Notes
2012-11-15 15:23:48GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-13 Cont ID  
Sent By rmcdouga Date 2012-11-13 Time 15:32 Rev Time 0.00
Received By rmcdouga Date 2012-11-13 Time 12:00 Sent To  
Notes
2012-11-13 12:25:27TO RM