Plan Review Details - Permit 12110149
Plan Review Stops For Permit 12110149
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-12-17 Cont ID  
Sent By jwitmer Date 2012-12-14 Time 13:00 Rev Time 0.00
Received By jwitmer Date 2012-12-14 Time 14:19 Sent To  
Notes
2012-12-14 14:20:30BUILDING PLAN REVIEW
 PERMIT: 12110149
 ADD: 515 PALM ST
 CONTRATOR: TO BE DETERMINED
 CONTACT: PATRICE LAFFERTY
 TEL: (561)603-4329
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DEC. 14/ 2012
 CHANGE OF OCCUPANCY:
 ACTION: DENIED
  
 NOTE: THE EXISTING USE FOR THIS STRUCTURE WAS A MIXED
 USE BUILDING, MERCANTILE/ STORAGE, THE NEW PROPOSED USE
 A CHURCH IS A A-3 OCCUPANCY, NEW PLANS NEED TO BE DRAWN
 TO REFLECT THE CODE REQUIREMENTS FOR THE NEW OCCUPANCY,
 THESE REQUIREMENTS ARE LISTED BELOW;
  
 1) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 WILL NEED TO BE PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE
 PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS
 LAYOUT; ALL FENESTRATION PENETRATIONS;
 FLASHING; AND ROUGH OPENING DIMENSIONS; AND ALL
 EXTERIOR ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 1. SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
  
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
  
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
  
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 EARLY WARNING
  
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
  
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
  
 DESIGN LOADS WIND REQUIREMENTS
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 BUILDING ENVELOPE
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 STRUCTURAL CALCULATIONS (IF REQUIRED)
  
  
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
  
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
  
 3) 901.3 CHANGE OF OCCUPANCY CLASSIFICATION.
  
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-12-04 Cont ID  
Sent By jwitmer Date 2012-12-04 Time 10:39 Rev Time 0.00
Received By jwitmer Date 2012-12-04 Time 10:39 Sent To  
Notes
2012-12-04 10:52:11BUILDING PLAN REVIEW
 PERMIT: 12110149
 ADD: 515 PALM ST
 CONTRATOR: TO BE DETERMINED
 CONTACT: PATRICE LAFFERTY
 TEL: (561)603-4329
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 CHANGE OF OCCUPANCY:
 ACTION: DENIED
  
 1) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 WILL NEED TO BE PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE
 PLAN; FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS
 LAYOUT; ALL FENESTRATION PENETRATIONS;
 FLASHING; AND ROUGH OPENING DIMENSIONS; AND ALL
 EXTERIOR ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
  
 1. SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
  
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
  
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE
 RESISTANCE
  
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
  
 6. LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 EARLY WARNING
  
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
  
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
  
 DESIGN LOADS WIND REQUIREMENTS
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 BUILDING ENVELOPE
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 STRUCTURAL CALCULATIONS (IF REQUIRED)
  
  
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
  
 11. INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES (FLAME SPREAD/SMOKE DEVELOPMENT)
 LIGHT AND VENTILATION
 SANITATION
  
 3) 901.3 CHANGE OF OCCUPANCY CLASSIFICATION.
  
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-12-17 Cont ID  
Sent By rlecky Date 2012-12-17 Time 12:07 Rev Time 0.00
Received By rlecky Date 2012-12-17 Time 11:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-26 Cont ID  
Sent By rlecky Date 2012-11-26 Time 14:30 Rev Time 0.00
Received By rlecky Date 2012-11-26 Time 14:16 Sent To  
Notes
2012-11-26 14:31:2212110149
 515 PALM STREET
 CHANGE OF USE
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENT.
  
 PROVIDE AN ELECTRICAL PLAN SHOWING LOCATION OF ALL
 LIGHTING, RECEPTACLES AND THE PANELBOARD. INDICATE THE
 WIRING METHOD USED (IE. ARMORED CABLE, METAL CLAD
 CABLE, OR CONDUIT). NEC 215.5
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINK MUST
 BE GFCI PROTECTED. NEC 210.8
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-12-14 Cont ID  
Sent By wjolin Date 2012-12-14 Time 11:05 Rev Time 0.00
Received By wjolin Date 2012-12-14 Time 09:56 Sent To  
Notes
2012-12-14 11:04:56515 PALM STREET
 PERMIT #12110149
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS SHALL INDICATE THAT A PROPOSED CHANGE IN
 OCCUPANCY FROM A BUSINESS/STORAGE USE TO AN ASSEMBLY
 USE IS BEING PROPOSED. PLANS SHALL INDICATE THE MAXIMUM
 OCCUPANT LOAD CALCULATED FOR EACH SPACE TO BE UTILIZED
 BY THE CHURCH. PROVIDE A PROPOSED SEATING AND FURNITURE
 LAYOUT.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE
 PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO
 RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE
 PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE.
  
 IF THE CALCULATED OCCUPANT LOAD EXCEEDS 300 PERSONS,
 THE ASSEMBLY OCCUPANCY SHALL BE PROTECTED BY A FIRE
 ALARM SYSTEM EQUIPPED WITH AUTOMATIC VOICE
 ANNOUNCEMENTS.
  
 EMERGENCY LIGHTS AND EXIT SIGNAGE REQUIRED IN ALL
 ASSEMBLY SPACES. IT IS UNCLEAR FROM THE PLAN IF
 EXISTING STORAGE #104 WILL BE CONVERTED TO ASSEMBLY
 USE.
  
 CURTAINS, DRAPES AND OTHER LOOSELY HANGING
 FINISHINGS/DECORATIONS SHALL MEET THE FLAME PROPAGATION
 CRITERIA OF NFPA 701 (MATERIAL WILL SELF EXTINGUISH
 ONCE DIRECT FIRE FLAME HAS BEEN REMOVED).
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE HANDRAILS FOR EXISTING EXTERIOR STAIR.
  
 EXISTING FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN
 APPROVED SUPERVISING STATION IN ACCORDANCE WITH NFPA
 72.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-11-26 Cont ID  
Sent By wjolin Date 2012-11-26 Time 09:14 Rev Time 0.00
Received By wjolin Date 2012-11-26 Time 09:05 Sent To  
Notes
2012-11-26 09:14:20515 PALM STREET
 PERMIT #12110149
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT DOORS, EXIT
 SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON
 PATH OF TRAVEL, FURNITURE LAYOUT, SEATING ARRANGEMENTS,
 ETC.
  
 PROVIDE A SCALABLE FLOOR PLAN.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED. WHERE SMOKING IS
 PERMITTED, SAFE RECEPTACLES FOR SMOKING MATERIALS SHALL
 BE PROVIDED.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 AT THIS TIME, A THOROUGH AND COMPLETE PLAN REVIEW
 CANNOT BE PROVIDED DUE TO INCOMPLETE INFORMATION
 SUBMITTED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-02-22 Cont ID  
Sent By lmartine Date 2012-12-19 Time 12:57 Rev Time 0.00
Received By lmartine Date 2012-12-07 Time 16:39 Sent To  
Notes
2012-12-13 16:40:26B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-12-04 Cont ID  
Sent By lwagner Date 2012-12-04 Time 12:32 Rev Time 0.00
Received By lwagner Date 2012-11-05 Time 16:22 Sent To  
Notes
2012-11-20 16:25:17B--11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-02-14 Cont ID  
Sent By jwitmer Date 2013-02-14 Time 11:26 Rev Time 0.00
Received By jwitmer Date 2013-02-14 Time 11:26 Sent To  
Notes
2013-02-25 11:27:38BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-12-04 Cont ID  
Sent By jwitmer Date 2012-12-04 Time 10:52 Rev Time 0.00
Received By jwitmer Date 2012-12-04 Time 10:52 Sent To  
Notes
2012-12-04 10:52:34BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2012-12-17 Cont ID  
Sent By lwagner Date 2012-12-17 Time 09:13 Rev Time 0.00
Received By lwagner Date 2012-12-14 Time 12:56 Sent To  
Notes
2012-12-17 09:13:25FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #2
 DENIED:
  
 THERE IS NOT ENOUGH INFORMATION INCLUDED FOR A PLUMBING
 REVIEW.
 AN OCCUPANCY TYPE (CHURCH ?), AND OCCUPANT LOAD WILL BE
 REQUIRED TO DETERMINT THE REQUIRED PLUMBING FIXTURES.
 FBC PLUMBING 403.1 REQUIRED PLUMBING FIXTURES FOR
 CHURCH:
 WATER CLOSETS FOR MEN = 1 PER 150
 WATER CLOSETS FOR WOMEN = 1 PER 150
 LAVATORIES = 1 PER 200
 DRINKING FOUNTAINS = 1 PER 1000 * (HI/LO TYPE REQUIRED
 PER FBC ACCESSIBILITY 211.2).
 SERVICE SINK = 1
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-12-04 Cont ID  
Sent By lwagner Date 2012-12-04 Time 12:32 Rev Time 0.00
Received By lwagner Date 2012-12-04 Time 12:06 Sent To  
Notes
2012-12-04 12:20:03FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 THERE IS NOT ENOUGH INFORMATION INCLUDED FOR A PLUMBING
 REVIEW.
 AN OCCUPANCY TYPE (CHURCH ?), AND OCCUPANT LOAD WILL BE
 REQUIRED TO DETERMINT THE REQUIRED PLUMBING FIXTURES.
 FBC PLUMBING 403.1 REQUIRED PLUMBING FIXTURES FOR
 CHURCH:
 WATER CLOSETS FOR MEN = 1 PER 150
 WATER CLOSETS FOR WOMEN = 1 PER 150
 LAVATORIES = 1 PER 200
 DRINKING FOUNTAINS = 1 PER 1000 * (HI/LO TYPE REQUIRED
 PER FBC ACCESSIBILITY 211.2).
 SERVICE SINK = 1
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 2 Status F Date 2012-12-19 Cont ID  
Sent By ajones Date 2012-12-19 Time 15:20 Rev Time 0.00
Received By ajones Date 2012-12-19 Time 15:20 Sent To  
Notes
2012-12-19 15:21:45REPEAT COMMENT
 SINCE THE CURRENT SURFACE AREA WAS USED FOR STORAGE,
 THE APPLICANT NEEDS TO INDICATE WHERE THEY WILL PLACE
 THE PARKING SPACES FOR THE CHURCH.
  
 ANGELLA VANN, PLANNNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2012-12-04 Cont ID  
Sent By avann Date 2012-12-04 Time 08:33 Rev Time 0.00
Received By ajones Date 2012-12-04 Time 08:33 Sent To  
Notes
2012-12-04 08:36:11SINCE THE CURRENT SURFACE AREA WAS USED FOR STORAGE,
 THE APPLICANT NEEDS TO INDICATE WHERE THEY WILL PLACE
 THE PARKING SPACES FOR THE CHURCH.
  
 ANGELLA VANN, PLANNNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]
2012-11-29 14:26:0911/29/12