Plan Review Details - Permit 12100967
Plan Review Stops For Permit 12100967
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-12-20 Cont ID  
Sent By shill Date 2012-12-20 Time 08:52 Rev Time 0.00
Received By shill Date 2012-12-20 Time 08:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-12-03 Cont ID  
Sent By shill Date 2012-12-03 Time 17:07 Rev Time 0.00
Received By shill Date 2012-12-03 Time 17:07 Sent To  
Notes
2012-12-03 17:16:17****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SHUTTER MOUNTING CONNECTION TYPE IS TO CORRELATE
 WITH THE ANCHOR SCHEDULES IN THE PRODUCT APPROVAL, SEE
 SHEET 5. THE NAMING CONVENTION USED BY THE NOA
 SUBMITTED IS A THROUGH E. (THEREFORE, THE SHUTTER
 MOUNTING CONNECTION TYPE SHOULD BE A, B, C, D, OR E.)
  
 2. SCOPE IS STILL NOT CLEAR. APPLICATION AND PLAN STATE
 THAT DOORS WILL BE INSTALLED, BUT NO PRODUCT APPROVAL
 FOR DOORS SUBMITTED. PLAN SHOWS A STAIR, APPLICATION
 DOES NOT REFER TO A STAIR.
  
 3. THE APPLICATION IS FOR DOORS AND WINDOWS, PLAN SHOWS
 OTHER WORK. PLEASE CLARIFY SCOPE. FBC 106.
  
 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. FBC
 106.
  
 5. INFORMATIONAL; NO PLUMBING REVIEW REQUIRED FOR WATER
 HEATER CHANGE OUT. PLUMBING CONTRACTOR CAN APPLY AS A
 STAND ALONE PERMIT. THIS WILL NOT BE A SUB PERMIT AS
 THERE IS NO PLUMBING REVIEW FOR THIS PERMIT.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-13 Cont ID  
Sent By shill Date 2012-11-13 Time 13:23 Rev Time 0.00
Received By shill Date 2012-11-13 Time 13:22 Sent To  
Notes
2012-11-13 13:25:07****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. DESIGN INTENT IS NOT CLEAR. THE PLAN STATES THAT
 SHUTTERS WILL BE INSTALLED, SHUTTER PRODUCT APPROVAL
 SUBMITTED, BUT THE WINDOW PRODUCT APPROVAL SUBMITTED IS
 FOR AN IMPACT GLASS PRODUCT.
  
 IF SHUTTERS ARE PROPOSED, ADDRESS THE FOLLOWING
 COMMENTS. IF SHUTTERS ARE NOT PROPOSED, PLEASE REVISE
 PLAN.
  
 COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609,
 FBC*106.
  
 3. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2012-11-13 Cont ID  
Sent By rlecky Date 2012-11-13 Time 08:42 Rev Time 0.00
Received By rlecky Date 2012-11-13 Time 08:41 Sent To B
Notes
2012-11-13 08:43:38MISC 1

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-12-20 Cont ID  
Sent By shill Date 2012-12-20 Time 08:52 Rev Time 0.00
Received By shill Date 2012-12-06 Time 10:43 Sent To  
Notes
2012-12-06 10:44:13INCOMING SENT TO SAMANTHA'S DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-03 Cont ID  
Sent By shill Date 2012-12-03 Time 17:30 Rev Time 0.00
Received By shill Date 2012-11-19 Time 07:47 Sent To  
Notes
2012-11-19 07:47:27TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-13 Cont ID  
Sent By shill Date 2012-11-13 Time 13:25 Rev Time 0.00
Received By shill Date 2012-11-01 Time 16:31 Sent To  
Notes
2012-11-01 16:31:52TO ZONING
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-11-09 Cont ID  
Sent By mdekle Date 2012-11-09 Time   Rev Time  
Received By mdekle Date 2012-11-02 Time   Sent To E
Notes
***NONE***