Plan Review Details - Permit 12100654
Plan Review Stops For Permit 12100654
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-11-13 Cont ID  
Sent By jwitmer Date 2012-11-13 Time 11:58 Rev Time 0.00
Received By jwitmer Date 2012-11-13 Time 11:14 Sent To  
Notes
2012-11-13 11:17:50BUILDING PLAN REVIEW
 PERMIT: 12100654
 ADD: 400 W RAILROAD AVE. 4TH FLOOR
 CONT: TBD
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 NOV. 13/ 2012
 ACTION: DENIED
  
 1) PLANS FAIL TO PROVIDE LOCATION OF SUITE, THEY
 INDICATE THE 4TH FLOOR, THERE ARE OTHER PROJECTS ALSO
 LOCATED ON THE FOURTH FLOOR, BE SUITE SPECIFIC. 2010
 WPB ADMINISTRATIVE CODE 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE LOCATION...
  
 2) PLEASE PROVIDE ADDITIONAL INFORMATION (CLARITY) AS
 TO THE FRONT ENTRY DOOR, THE DEMOLISION PLAN DOES NOT
 APPEAR TO HAVE ANY WORK TO BE COMPLETED ON THE ENTRY
 DOOR, THE LIFE SAFETY PLAN IT APPEARS TTHE ENTRY DOOR
 IS BEING MOVED AND REHUNG AS TO THE SWING OF THE DOOR
 WHEREAS ON SHEET A100 IT APPEARS TO BE IN THE SAME
 LOCATION AND THESWING OF THE DOOR APPEARS TO REMAIN THE
 SAME. 107.2.1.
  
 3) SHEET A100 THE RECEPT ROOM DOOR # 2 IS MISSING THE
 REQUIRED 18" ON THE LATCH SIDE OF THE DOOR. 2010
 FLORIDA ACCESSIBILITY CODE FIGURE 404.2.4.1 (A).
  
 4) A100 GALLEY # 105 INDICATES A KITCHEN SINK, THERE IS
 NO CUT SECTION THROUGH THIS AREA PROVIDING COMPLIANCE
 WITH 2010 ACCESSIBILTY CODE 606.3 HEIGHT REQUIREMENT OF
 34" TO THE RIM OR COUNTER FROM FINISH FLOOR.
  
 5) A100 IN BOTH THE WATING ROOM (101) AND OFFICE (103)
 BOTH INDICATE GLAZING IN THE WALL WITHIN 24" OF THE
 DOOR PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B
 2406.4(6) HAZARDOUS LOCATION.
  
 6) A100 PLANS DO NOT PROVIDE ANY EMERGENCY LIGHTING IN
 ACCORDANCE WITH 2010 FBC-B 1006.2 NOR ANY EXIT SIGNAGE
 OR DIRECTIONALS1006.3.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-06 Cont ID  
Sent By rlecky Date 2012-11-06 Time 11:46 Rev Time 0.00
Received By rlecky Date 2012-11-06 Time 11:24 Sent To  
Notes
2012-11-06 11:46:10PLEASE PROVIDE AND ELECTRICAL PLAN. SHOW WIRING METHOD.
 NEC 215.5
  
 VERIFY THE LIGHTING MEETS THE REQUIREMENTS OF THE
 FLORIDA ENERGY CODE. FBC ENERGY CONSERVATION CODE 505.3
  
 NOTE:
 SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA AND
 FIRE ALARM SYSTEMS
  
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-11-17 Cont ID  
Sent By wjolin Date 2012-11-17 Time 14:40 Rev Time 0.00
Received By wjolin Date 2012-11-17 Time 14:30 Sent To  
Notes
2012-11-17 14:40:40444 WEST RAILROAD AVENUE - SUITE #?
 PERMIT #12100654
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS DO NOT INDICATE A SUITE NUMBER.
  
 THE COMMON PATH OF TRAVEL FROM GALLEY #105 TO STAIR A-2
 EXCEEDS 100 FEET.
  
 PLANS DO NOT SHOW ANY AUTOMATIC SPRINKLER OR FIRE ALARM
 DESIGN.
  
 PROVIDE PORTABLE FIRE EXTINGUISHER(S).
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rregueir Date 2012-10-23 Time 14:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-02-13 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2013-02-13 10:22:40PROJECT NOT MOVING FORWARD PER CUSTOMER REQUEST.

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-11-05 Cont ID  
Sent By lwagner Date 2012-11-05 Time 12:47 Rev Time 0.00
Received By lwagner Date 2012-11-05 Time 10:50 Sent To  
Notes
2012-11-05 12:46:57FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. AN ISOMETRIC DIAGRAM IS REQUIRED FOR THE PLUMBING.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.3 PLUMBING: 13. PLUMBING RISER
  
 ***NOTE***
 THE SINK RIM IS REQUIRED TO BE 34" AFF MAX.
 FBC 2010 ACCESSIBILITY CODE 2010 606.3 HEIGHT:
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-12-21 Cont ID  
Sent By aaponte Date 2012-12-21 Time 09:52 Rev Time 0.00
Received By aaponte Date 2012-12-21 Time 09:52 Sent To  
Notes
***NONE***