Plan Review Details - Permit 12100549
Plan Review Stops For Permit 12100549
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-10-23 Cont ID  
Sent By rlecky Date 2012-10-23 Time 11:09 Rev Time 0.00
Received By rlecky Date 2012-10-23 Time 11:09 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-10-19 Cont ID  
Sent By wjolin Date 2012-10-19 Time 12:05 Rev Time 0.00
Received By wjolin Date 2012-10-19 Time 11:31 Sent To E
Notes
2012-10-19 11:56:062275 PALM BEACH LAKES BOULEVARD
 PERMIT #12100549
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A REMOTE ANNUNCIATOR OR VOICE CONTROL PANEL AT
 THE MAIN ENTRANCE.
  
 FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBER/LETTER OR
 COMBINATION TO EACH FIRE ALARM DEVICE ON THE SYSTEM.
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY.
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 INDICATE THE METHOD (PHONE LINES, ETC) FIRE ALARM
 SIGNAL TRANSMISSION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-24 Cont ID  
Sent By hmoser Date 2012-10-24 Time 12:59 Rev Time 0.00
Received By hmoser Date 2012-10-17 Time 14:33 Sent To  
Notes
2012-10-17 14:34:12TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-10-24 Cont ID  
Sent By hmoser Date 2012-10-24 Time 12:59 Rev Time 0.00
Received By hmoser Date 2012-10-24 Time 12:51 Sent To  
Notes
***NONE***