Plan Review Details - Permit 12100425
Plan Review Stops For Permit 12100425
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-11-07 Cont ID  
Sent By shill Date 2012-11-07 Time 12:47 Rev Time 0.00
Received By shill Date 2012-11-07 Time 12:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-10-17 Cont ID  
Sent By jwitmer Date 2012-10-17 Time 14:38 Rev Time 0.00
Received By jwitmer Date 2012-10-17 Time 14:38 Sent To  
Notes
2012-10-17 14:50:44BUILDING PLAN REVIEW
 PERMIT: 12100425
 ADD: 477 S ROSEMARY # 217/ 219
 CONT: CHANDLER CONSTRUCTION COMPANY
 TEL: (561)791-6934
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 OCT. 17/ 2012
 ACTION: DENIED
  
 1) BEFORE PLANS CAN BE ISSUED, CITY PLACE STAMP OR
 REVIEW NEEDS TO BE ON ALL SHEETS.
  
 PLANS APPEAR TO BE CODE COMPLIANT, WILL BE STAMPED
 AFTER CITY PLACE APPROVAL GIVEN.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-11-02 Cont ID  
Sent By rlecky Date 2012-11-02 Time 17:37 Rev Time 0.00
Received By rlecky Date 2012-11-02 Time 15:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-10-19 Cont ID  
Sent By wjolin Date 2012-10-19 Time 11:24 Rev Time 0.00
Received By wjolin Date 2012-10-19 Time 11:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-02 Cont ID  
Sent By rlecky Date 2012-11-02 Time 17:39 Rev Time 0.00
Received By rlecky Date 2012-10-12 Time 10:15 Sent To  
Notes
2012-10-15 10:15:55B-08

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-10-31 Cont ID  
Sent By hmoser Date 2012-10-31 Time 13:41 Rev Time 0.00
Received By hmoser Date 2012-10-31 Time 13:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-10-22 Cont ID  
Sent By lwagner Date 2012-10-22 Time 13:54 Rev Time 0.00
Received By lwagner Date 2012-10-22 Time 12:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-11-07 Cont ID  
Sent By jroach Date 2012-11-07 Time 11:51 Rev Time 0.00
Received By jroach Date 2012-11-07 Time 11:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-10-26 Cont ID  
Sent By eschneid Date 2012-10-26 Time 14:11 Rev Time 0.50
Received By eschneid Date 2012-10-26 Time 11:44 Sent To  
Notes
2012-10-26 14:11:30FAILED
  
 PLEASE RESPOND IN WRITING.
  
 1) THE PLANS SHOW THE INSTALLATION OF NEW 36 INCH TALL
 ROOFTOP CONDENSING UNITS ON AN 18 INCH RACK, FOR A
 TOTAL HEIGHT OF 54 INCHES. THE CITYPLACE DRI REQUIRES
 THAT ALL ROOFTOP MECHANICAL EQUIPMENT, INCLUDING BUT
 NOT LIMITED TO SUCH ITEMS AS PUBLIC AND PRIVATE UTILITY
 SERVICE CONNECTIONS; HEATING, VENTILATING, AND AIR
 CONDITIONING SYSTEMS; COMMUNICATIONS DEVICES; AND
 RELATED EQUIPMENT, SHALL BE SCREENED FROM PUBLIC VIEW.
 PLEASE PROVIDE DETAILS ON HOW THE NEW ROOFTOP
 CONDENSING UNITS WILL BE SCREENED. THE HEIGHT OF THE
 EQUIPMENT AND THE HEIGHT OF THE SCREENING SHALL BE
 PROVIDED AND SHOWN ON ELEVATION DRAWINGS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  