Plan Review Details - Permit 12100408
Plan Review Stops For Permit 12100408
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-10-17 Time   Rev Time 0.00
Received By jwitmer Date 2012-10-12 Time 12:41 Sent To  
Notes
2012-10-15 10:06:19GAVE TO RON
2012-10-12 12:42:26INCOMING SENT TO MECHANICAL BOX <$5K. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-10-17 Cont ID  
Sent By rregueir Date 2012-10-17 Time 14:00 Rev Time 0.00
Received By rregueir Date 2012-10-17 Time 13:56 Sent To  
Notes
2012-10-17 14:00:42PROVISO:
  
 1) NEED ORIGINAL SIGNED AND SEALED LETTER FROM
 ARCHITECT REGRADING TRANSFER OF DESIGN RESPONSIBILITY
 TO AE SOSA AIR CONDITIONING
  
 2) IF THE ARCHITECT IS TRANSFERRING DESIGN
 RESPONSIBILITY, THE PLAN SUBMITTED SHALL NOT HAVE THE
 ARCHITECT'S TITLE BLOCK OR ANY INFORMATION ON THE PLAN
 IDENTIFYING LICHI AS THE DESIGNER.
  
 3) PROVIDE THE A/C CONTRACTOR'S LICENSE NUMBER AND
 ORIGINAL SIGNATURE ON THE REVISED PLAN AS THE DESIGNER
 OF RECORD.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]