Plan Review Details - Permit 12100383
Plan Review Stops For Permit 12100383
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-16 Cont ID  
Sent By rmcdouga Date 2012-10-16 Time 09:42 Rev Time 0.00
Received By rmcdouga Date 2012-10-16 Time 09:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-10-12 Cont ID  
Sent By rmcdouga Date 2012-10-12 Time 08:22 Rev Time 0.00
Received By rmcdouga Date 2012-10-12 Time 08:22 Sent To  
Notes
2012-10-12 08:23:36DENIED BY BUILDING
  
 YOUR ATTACHED LETTER IS NOT ACCEPTABLE. THE LETTER IS
 GIVING THE FASTENER SPACING AT 9" ON CENTER WHICH IS
 GIVEN IN THE PRODUCT APPROVAL FOR A DESIGN PRESSURE OF
 -52.5 PSF. THIS WILL WORK FOR THE INTERIOR ROOF ZONE
 BUT NOT FOR THE PERIMETER AND CORNER AREAS OF THE ROOF.
 THE CORNER AND PERIMETER AREAS REQUIRE ENHANCED
 FASTENING BECAUSE THE NEGATIVE PRESSURES IN THESE AREAS
 ARE IN EXCESS OF THE -52.5 PSF THAT THE 9" O.C. SPACING
 AT THE 4" LAP AND THE 2 STAGGERED ROWS IN THE CENTER OF
 THE BASE SHEET IS GOOD FOR. IN ORDER TO GET HIGHER
 PRESSURES THE NUMBER OF FASTENERS IN THE BASE SHEET
 NEEDS TO BE INCREASED.
  
 TYPICALLY THE LETTER WOULD SPECIFY THAT THE NOA
 SPECIFIES A DESIGN PRESSURE OF -52.5 PSF WHEN THE BASE
 SHEET IS FASTENED AT 9" O.C. IN THE 4" LAP AND 9" O.C.
 IN TWO STAGGERED ROWS IN THE CENTER OF THE SHEET WITH
 11 GA. ANNULAR RING SHANK NAILS AND 1-5/8" DIAMETER TIN
 CAPS. THE ENHANCED FASTENING OF THE FOUR FEET WIDE
 PERIMETER AND CORNER AREAS AT THE ROOF EDGES WILL BE
 ACCOMPLISHED BY INCREASING THE FASTENER DENSITY TO 4"
 O.C. IN THE 4" LAP AN 4" O.C. IN TWO STAGGERED ROWS IN
 THE CENTER OF THE BASE SHEET.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-10-11 Cont ID  
Sent By fmittner Date 2012-10-11 Time 14:36 Rev Time 0.00
Received By fmittner Date 2012-10-11 Time 14:36 Sent To  
Notes
2012-10-11 14:37:31APPROVED FOR FLAT ROOF OVER SUNROOM/FRONT ROOMA REA.
 ROOF OVER DOOR TO REMAIN TILE.