Plan Review Details - Permit 12100355
Plan Review Stops For Permit 12100355
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2013-01-08 Cont ID  
Sent By jwitmer Date 2013-01-08 Time 15:29 Rev Time 0.00
Received By jwitmer Date 2013-01-08 Time 15:29 Sent To  
Notes
2013-01-08 15:32:44I SPOKE WITH THE ARCHITECT OF RECORD MARK MCCREE HE
 WOULD LIKE TO DELETE THE REPLACEMENT OF JALOUSIE
 WINDOWS FROM THE SCOPE OF WORK, E-MAIL SENT FOR
 DOCUMENTATION.
 SEE ATTACHMENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2013-01-08 Cont ID  
Sent By jwitmer Date 2013-01-08 Time 15:29 Rev Time 0.00
Received By jwitmer Date 2013-01-08 Time 09:54 Sent To  
Notes
2013-01-08 09:56:40BUILDING PLAN REVIEW
 PERMIT: 12100355
 ADD: 825 SOUTHERN BLVD SUITE # 5
 CONT: MTC REMODELING
 TEL: (561)655-5956
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 JAN. 08/2013
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 4TH REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 4TH REQUEST. 2010 FBC-B 1609.1.1 DETERMINATION OF
 WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE
 TABLE 1609.2(2) .
  
 4) COMPLIED.
  
 PLEASE TAKE NOTE!!!!!!!!!!!!!!!!!
  
 *****CHAPTER 553.80(2)(B) FLORIDA STATUTES *****STATES
 THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR
 TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED
 THREE
 OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A CODE
 VIOLATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-12-19 Cont ID  
Sent By jwitmer Date 2012-12-19 Time 10:38 Rev Time 0.00
Received By jwitmer Date 2012-12-19 Time 10:38 Sent To  
Notes
2012-12-19 10:43:55BUILDING PLAN REVIEW
 PERMIT: 12100355
 ADD: 825 SOUTHERN BLVD SUITE # 5
 CONT: MTC REMODELING
 TEL: (561)655-5956
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DEC. 19/2012
 ACTION: DENIED
  
 1) SEMI -COMPLIED, SEE COMMENT # 2, NOT REVIEWED BY THE
 DESIGNER OF RECORD. SHEET 1 INDICATES THE FRONT JJALOSE
 WINDOWS ABOVE THE STOREFRONT ARE TO BE REPLACED,
 PRODUCT APPROVALS WERE SUBMITTED FOR WINDOW
 REPLACEMENT.
 2010 FBC-B 1609.1.2 PROTECTION OF WINDOWS. PRODUCT
 APPROVALS SUBMITTED FOR NON-IMPACT GLASS. REQUIRES
 PRODUCT APPROVAL FOR STORM SHUTTERS.
 IS THE STOREFRONT SYSTEM BELOW TTHE EXISTING JALOSIE
 WINDOWS ALSO BEING REPLACED?
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
 (31)(E) STORM SHUTTERS
  
 2) 3RD REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3)3RD REQUEST. 2010 FBC-B 1609.1.1 DETERMINATION OF
 WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 3) 2ND REQUEST , SEMI-COMPLIED. NEW 8X11 SHEET
 INDICATING THE REMOVAAL OF DOOR FROM THE HALLWAY WIDTH
 INDICATED AS 3'-6" IS NOT SIGNED NOR SEALED, NOR IS THE
 REVISION THAT IS CLOUDED INDICATING THE REVISION DATE.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 FROM 2ND REVIEW. NEW COMMENT- THE HALLWAY THAT LEADS
 FROM TTHE FRONT OF THE PHARMACY TO THE BREAKROOM, IN
 THIS REVISION THE SWING OF THE DOOR HAS CHANGED WHICH
 WILL REQUIRE 18" CLEAR ON THE LATCH SIDE OF THE DOOR,
 PLEASE SEE 2010 ACCESSIBILITY CODE FIGURE 404.2.4.1(A).
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-12-04 Cont ID  
Sent By jwitmer Date 2012-12-04 Time 11:23 Rev Time 0.00
Received By jwitmer Date 2012-12-04 Time 11:23 Sent To  
Notes
2012-12-04 11:31:28BUILDING PLAN REVIEW
 PERMIT: 12100355
 ADD: 825 SOUTHERN BLVD SUITE # 5
 CONT: MTC REMODELING
 TEL: (561)655-5956
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DEC. 04/2012
 ACTION: DENIED
  
 1) SHEET 1 INDICATES THE FRONT JJALOSE WINDOWS ABOVE
 THE STOREFRONT ARE TO BE REPLACED, PRODUCT APPROVALS
 WERE SUBMITTED FOR WINDOW REPLACEMENT.
 2010 FBC-B 1609.1.2 PROTECTION OF WINDOWS. PRODUCT
 APPROVALS SUBMITTED FOR NON-IMPACT GLASS. REQUIRES
 PRODUCT APPROVAL FOR STORM SHUTTERS.
 IS THE STOREFRONT SYSTEM BELOW TTHE EXISTING JALOSIE
 WINDOWS ALSO BEING REPLACED?
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
 (31)(E) STORM SHUTTERS
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 3) NEW COMMENT- THE HALLWAY THAT LEADS FROM TTHE FRONT
 OF THE PHARMACY TO THE BREAKROOM, IN THIS REVISION THE
 SWING OF THE DOOR HAS CHANGED WHICH WILL REQUIRE 18"
 CLEAR ON THE LATCH SIDE OF THE DOOR, PLEASE SEE 2010
 ACCESSIBILITY CODE FIGURE 404.2.4.1(A).
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-10-18 Cont ID  
Sent By jwitmer Date 2012-10-18 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2012-10-17 Time 16:56 Sent To  
Notes
2012-10-18 07:05:26BUILDING PLAN REVIEW
 PERMIT: 12100355
 ADD: 825 SOUTHERN BLVD SUITE # 5
 CONT: MTC REMODELING
 TEL: (561)655-5956
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 OCT. 18/2012
 ACTION: DENIED
  
 1) SHEET 1 INDICATES THE FRONT JJALOSE WINDOWS ABOVE
 THE STOREFRONT ARE TO BE REPLACED, NO PRODUCT APPROVALS
 WERE SUBMITTED FOR WINDOW REPLACEMENT.
 2010 FBC-B 1609.1.2 PROTECTION OF WINDOWS.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-01-09 Cont ID  
Sent By rlecky Date 2013-01-09 Time 10:45 Rev Time 0.00
Received By rlecky Date 2013-01-09 Time 10:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-11-26 Cont ID  
Sent By rlecky Date 2012-11-26 Time 15:38 Rev Time 0.00
Received By rlecky Date 2012-11-26 Time 15:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-11-05 Cont ID  
Sent By rlecky Date 2012-11-05 Time 09:36 Rev Time 0.00
Received By rlecky Date 2012-11-05 Time 09:13 Sent To  
Notes
2012-11-05 09:37:1512100355
 823 SOUTHERN BLVD.
 COMMERCIAL RENOVATION
  
 NONMETALLIC-SHEATHED CABLE (ROMEX) IS NOT AN ACCEPTABLE
 WIRING METHOD FOR THIS OCCUPANCY. NEC 334.12
 ALL RECEPTACLES LOCATED WITH IN SIX FEET OF A SINK MUST
 BE GFCI PROTECTED. NEC 210.8
 INCLUDE A RISER PLAN SHOWING THE NEW AND EXISTING
 ELECTRIC SERVICE COMPONENTS WITH MAIN DISCONNECT,
 SERVICE GROUNDING, AND LOCATION. NEC 110.26, 215.5
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-11-29 Cont ID  
Sent By wjolin Date 2012-11-29 Time 11:19 Rev Time 0.00
Received By wjolin Date 2012-11-29 Time 11:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-10-19 Cont ID  
Sent By wjolin Date 2012-10-19 Time 11:31 Rev Time 0.00
Received By wjolin Date 2012-10-19 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-01-09 Cont ID  
Sent By rlecky Date 2013-01-09 Time 13:13 Rev Time 0.00
Received By rlecky Date 2013-01-02 Time 09:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-12-19 Cont ID  
Sent By tgordon Date 2012-12-19 Time 11:01 Rev Time 0.00
Received By tgordon Date 2012-12-11 Time 16:48 Sent To  
Notes
2012-12-11 16:50:46CONTRACTOR SUBMITTED RESPONSES TO BUILDING REVIEW
 BEFORE ALL THE REVIEWS HAD BEEN COMPLETED. PUT WITH
 ORIGINAL PACKAGE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-18 Cont ID  
Sent By jwitmer Date 2012-12-18 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2012-11-20 Time 15:52 Sent To  
Notes
2012-11-20 15:53:49INCOMING SENT TO B-04. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-11-05 Cont ID  
Sent By rlecky Date 2012-11-05 Time 09:36 Rev Time 0.00
Received By rlecky Date 2012-10-15 Time 08:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2013-01-07 Cont ID  
Sent By tgordon Date 2013-01-07 Time 13:52 Rev Time 0.00
Received By tgordon Date 2013-01-07 Time 13:52 Sent To  
Notes
2013-01-07 13:53:22OUTDOOR AIR 187 CFM'S. PER COOLING LOAD CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2012-12-19 Cont ID  
Sent By tgordon Date 2012-12-19 Time 11:00 Rev Time 0.00
Received By tgordon Date 2012-12-19 Time 11:00 Sent To  
Notes
2012-12-19 11:01:46SEE NOTES FROM LAST REVIEW 12/17/12 PLEASE CORRECT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-12-17 Cont ID  
Sent By tgordon Date 2012-12-17 Time 15:59 Rev Time 0.00
Received By tgordon Date 2012-12-17 Time 15:59 Sent To  
Notes
2012-12-17 16:19:35*** MECHANICAL PLAN CORRECTIONS NEEDED ***
  
 1) WALL MOUNTED CONDENSER STAND NEEDS TO BE ON THE
 PLANS & SITE SPECIFIC, OR SUBMIT AN UP TO DATE PRODUCT
 APPROVAL FOR THE STAND. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9B-72 JAN. 1, 2006. (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (G) EXTERIOR COOLER, FREEZERS &
 PER-ENGINEERED A/C STANDS.AND 2010 FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 2) AS NOTED IN LAST REVIEW 11/1/12 NOTE #3. PROVIDE
 OUTDOOR AIR CAL'S. PER 2010 FBC/M 403.3.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-11-01 Cont ID  
Sent By hmoser Date 2012-11-01 Time 09:02 Rev Time 0.00
Received By hmoser Date 2012-11-01 Time 07:50 Sent To  
Notes
2012-11-01 09:02:50PLANS DENIED
 1) PROVIDE A DETAIL FROM THE ENGINEER ON THE
 WALL STAND FOR THE CONDENSER. PER SECTION
 301.12 WIND RESISTANCE 2010 FBC (M)
 2) REFER TO SECTION 307.2.1 CONDENSATE DISPOSAL.
 2010 FBC (M)
 3) PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3
 MINIMUM VENTILATION RATES 2010 FBC (M)
 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS
 ( FOR FRESH AIR) 2010 FLORIDA ENERGY CODE.
 5) REFER TO SECTION 503.2.1 CALCULATION OF HEATING &
 COOLING LOADS. 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-01-09 Cont ID  
Sent By lwagner Date 2013-01-09 Time 13:01 Rev Time 0.00
Received By lwagner Date 2013-01-09 Time 13:01 Sent To  
Notes
2013-01-09 13:01:30RE-STAMPED

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-12-04 Cont ID  
Sent By lwagner Date 2012-12-04 Time 15:03 Rev Time 0.00
Received By lwagner Date 2012-12-04 Time 14:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-10-18 Cont ID  
Sent By lwagner Date 2012-10-18 Time 13:39 Rev Time 0.00
Received By lwagner Date 2012-10-18 Time 13:15 Sent To  
Notes
2012-10-18 13:42:59FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 PLEASE SHOW SINKS CONNECTING DOWNSTREAM OF RESTROOM WET
 VENT.
  
 909.1 HORIZONTAL WET VENT PERMITTED.
 ONLY THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 HORIZONTAL WET VENT.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 2 Status P Date 2012-11-29 Cont ID  
Sent By mdekle Date 2012-11-29 Time   Rev Time 0.00
Received By mdekle Date 2012-11-29 Time 15:12 Sent To  
Notes
2012-11-29 14:29:3011/29/12

Review Stop Z ZONING
Rev No 1 Status P Date 2012-10-24 Cont ID  
Sent By mdekle Date 2012-10-24 Time   Rev Time  
Received By mdekle Date 2012-10-24 Time   Sent To  
Notes
***NONE***