Plan Review Details - Permit 12100295
Plan Review Stops For Permit 12100295
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-11-19 Cont ID  
Sent By jwitmer Date 2012-11-19 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2012-11-19 Time 11:30 Sent To  
Notes
2012-11-19 15:02:25BUILDING PLAN REVIEW
 PERMIT: 12100295
 ADD: 477 S ROSEMARY SUITE # 169
 CONT: CRAFT CONSTRUCTION
 TEL: (561)275-8770
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 OCT 19/2012
 ACTION: PROVISO
  
  
  
 BUILDING PROVISO:
 3A) BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 3B) BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
 2010 FBC 1609.1.2 PROTECTION OF OPENINGS. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-11-07 Cont ID  
Sent By jwitmer Date 2012-11-07 Time 11:21 Rev Time 0.00
Received By jwitmer Date 2012-11-07 Time 11:21 Sent To  
Notes
2012-11-07 11:23:58BUILDING PLAN REVIEW
 PERMIT: 12100295
 ADD: 477 S ROSEMARY SUITE # 169
 CONT: CRAFT CONSTRUCTION
 TEL: (561)275-8770
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 OCT 19/2012
 ACTION: DENIED
  
 1) NEED LETTER FROM CITY PLACE INDICATING AN APPROVED
 REVIEW OF ELEMENTS WITHIN THE TENANT BUILD OUT.
  
 2)2ND REQUEST THIS BUILDING MEETS THE DEFINITION OF A
 THRESHOLD BUILDING AND WILL NEED TO PROVIDE (3) THREE
 COPIES OF ALL DOCUMENTS, 1 FIELD SET, 1 BUILDING
 DEPARTMENT OFFICE SET & 1 SET FOR THRESHOLD INSPECTOR.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) NOTE: A SOFT-HOLD (REVIEWS WII CONTINUE, THE PERMIT
 WILL NOT BE ISSUED UNTIL THE FOLLOWING ITEMS ARE
 SUBMITTED TO KEN CONRAD) WILL BE PUT ON THIS PROJECT
 UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY THE
 CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 2D)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONCRETE RESTORATION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2D()2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 NOTE: 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 NOTE: PLEASE CALL THE CITY OF WEST PALM BEACH'S
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 3A)2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3B) 2ND REQUEST. 2010 FBC 1609.1.2 PROTECTION OF
 OPENINGS. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 4) 2ND REQUEST. ARCHITECTURAL AND STRUCTURAL SHEETS ARE
 LACKING 2010 FBC-B 1609.1.1 DETERMINATION OF WIND
 DESIGN- CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 5) 2ND REQUEST. COMMENTS THAT DEAL WITH COMMENTS ON
 A100 DETAIL 03 AND 4S1 DETAILS 4,5 & 9 "STYROFOAM OR
 OTHER NON COMPRESSIBLE VOID FILLER CAPABLE OF
 SUPPORTING 150 PSF."
  
 5A ) 2ND REQUEST. 2010 WEST PALM BEACH ADMINISTRATIVE
 CODE 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 SUCH INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL
 CODES SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR
 SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION ...
  
 5B) 2ND REQUEST. THE SPECIFIED PRODUCT STYROFOAM WILL
 NEED TO MEET THE REQUIREMENTS OF THE 2010 FBC SECTION
 603.1. COMBUSTIBLE MATERIALS IN TYPE II CONSTRUCTION,
 (3)
 FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26,
  
 5C) 2ND REQUEST. THE SPECIFIED PRODUCT STYROFOAM WILL
 NEED TO MEET THE REQUIREMENTS OF THE 2010 FBC SECTION
 603.1. COMBUSTIBLE MATERIALS IN TYPE II CONSTRUCTION,
 (12)
 STAGES & PLATFORM CONSTRUCTION IN ACCORDANCE WITH 410.3
 & 4, RESPECTIVELY.
 2010 FBC-B 410.4 PLATFORM CONSTRUCTION.
 PERMANENT PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS
 AS REQUIRED FOR THE TYPE OF CONSTRUCTION OF THE
 BUILDING IN WHICH THE PERMANENT PLATFORM IS LOCATED.
 PERMANENT PLATFORMS ARE PERMITTED TO BE CONSTRUCTED OF
 FIRE-RETARDANT-TREATED WOOD FOR TYPES I, II AND IV
 CONSTRUCTION WHERE THE PLATFORMS ARE NOT MORE THAN 30
 INCHES (762 MM) ABOVE THE MAIN FLOOR, AND NOT MORE THAN
 ONE-THIRD OF THE ROOM FLOOR AREA AND NOT MORE THAN
 3,000 SQUARE FEET (279 M2) IN AREA. WHERE THE SPACE
 BENEATH THE PERMANENT PLATFORM IS USED FOR STORAGE OR
 ANY PURPOSE OTHER THAN EQUIPMENT, WIRING OR PLUMBING,
 THE FLOOR ASSEMBLY SHALL NOT BE LESS THAN 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE SPACE
 BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR
 EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE
 PERMANENT PLATFORM NEED NOT BE PROTECTED.
  
 5D) 2ND REQUEST. A802 DETAIL 02 DOES NOT PROVIDE THE
 TYPE OF MATERIALS THE RAISED BOWLING ALLEY FLOOR FOR
 TYPE I OR TYPE II AS FAR AS COMBUSTIBLE STILL STAND.
 603.1.1 AND SECTION 410.4 FOR PLATFORM CONSTRUCTION.
  
 6)COMPLIED. SHEET A102 INDICATES THE USE OF STAIRS IN
 MANY AREAS, PLEASE REVIEW 2010 FBC-B 1028.11.3 TREAD
 AND CONTRASTING MARKING STRIPE.
  
 7) 2ND REQUEST. PLANS ( A503 DETAIL 07) APPEAR TO HAVE
 A LIFT BUT NO PRODUCT INFORMATION HAS BEEN PROVIDED FOR
 THE LIFT, PLEASE SUBMIT THE MANUFACTURERS
 SPECIFICATIONS FOR LIFT. 2010 FBC-B 3001.6(F) LIFT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-10-29 Cont ID  
Sent By jwitmer Date 2012-10-29 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2012-10-19 Time 07:04 Sent To  
Notes
2012-10-19 09:51:22BUILDING PLAN REVIEW
 PERMIT: 12100295
 ADD: 477 S ROSEMARY SUITE # 169
 CONT: CRAFT CONSTRUCTION
 TEL: (561)275-8770
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 OCT 19/2012
 ACTION: DENIED
  
 1) NEED LETTER FROM CITY PLACE INDICATING AN APPROVED
 REVIEW OF ELEMENTS WITHIN THE TENANT BUILD OUT.
  
 2) THIS BUILDING MEETS THE DEFINITION OF A THRESHOLD
 BUILDING AND WILL NEED TO PROVIDE (3) THREE COPIES OF
 ALL DOCUMENTS, 1 FIELD SET, 1 BUILDING DEPARTMENT
 OFFICE SET & 1 SET FOR THRESHOLD INSPECTOR.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) NOTE: A SOFT-HOLD (REVIEWS WII CONTINUE, THE PERMIT
 WILL NOT BE ISSUED UNTIL THE FOLLOWING ITEMS ARE
 SUBMITTED TO KEN CONRAD) WILL BE PUT ON THIS PROJECT
 UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY THE
 CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 2D)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONCRETE RESTORATION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2D()2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 NOTE: 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 NOTE: PLEASE CALL THE CITY OF WEST PALM BEACH'S
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 3A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3B) 2010 FBC 1609.1.2 PROTECTION OF OPENINGS. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 4) ARCHITECTURAL AND STRUCTURAL SHEETS ARE LACKING 2010
 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6
 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 5) COMMENTS THAT DEAL WITH COMMENTS ON A100 DETAIL 03
 AND 4S1 DETAILS 4,5 & 9 "STYROFOAM OR OTHER NON
 COMPRESSIBLE VOID FILLER CAPABLE OF SUPPORTING 150
 PSF."
  
 5A ) 2010 WEST PALM BEACH ADMINISTRATIVE CODE 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH INFORMATION
 SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL"
 OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION ...
  
 5B) THE SPECIFIED PRODUCT STYROFOAM WILL NEED TO MEET
 THE REQUIREMENTS OF THE 2010 FBC SECTION 603.1.
 COMBUSTIBLE MATERIALS IN TYPE II CONSTRUCTION, (3)
 FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26,
  
 5C) THE SPECIFIED PRODUCT STYROFOAM WILL NEED TO MEET
 THE REQUIREMENTS OF THE 2010 FBC SECTION 603.1.
 COMBUSTIBLE MATERIALS IN TYPE II CONSTRUCTION, (12)
 STAGES & PLATFORM CONSTRUCTION IN ACCORDANCE WITH 410.3
 & 4, RESPECTIVELY.
 2010 FBC-B 410.4 PLATFORM CONSTRUCTION.
 PERMANENT PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS
 AS REQUIRED FOR THE TYPE OF CONSTRUCTION OF THE
 BUILDING IN WHICH THE PERMANENT PLATFORM IS LOCATED.
 PERMANENT PLATFORMS ARE PERMITTED TO BE CONSTRUCTED OF
 FIRE-RETARDANT-TREATED WOOD FOR TYPES I, II AND IV
 CONSTRUCTION WHERE THE PLATFORMS ARE NOT MORE THAN 30
 INCHES (762 MM) ABOVE THE MAIN FLOOR, AND NOT MORE THAN
 ONE-THIRD OF THE ROOM FLOOR AREA AND NOT MORE THAN
 3,000 SQUARE FEET (279 M2) IN AREA. WHERE THE SPACE
 BENEATH THE PERMANENT PLATFORM IS USED FOR STORAGE OR
 ANY PURPOSE OTHER THAN EQUIPMENT, WIRING OR PLUMBING,
 THE FLOOR ASSEMBLY SHALL NOT BE LESS THAN 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE SPACE
 BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR
 EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE
 PERMANENT PLATFORM NEED NOT BE PROTECTED.
  
 5D) A802 DETAIL 02 DOES NOT PROVIDE THE TYPE OF
 MATERIALS THE RAISED BOWLING ALLEY FLOOR FOR TYPE I OR
 TYPE II AS FAR AS COMBUSTIBLE STILL STAND. 603.1.1 AND
 SECTION 410.4 FOR PLATFORM CONSTRUCTION.
  
 6) SHEET A102 INDICATES THE USE OF STAIRS IN MANY
 AREAS, PLEASE REVIEW 2010 FBC-B 1028.11.3 TREAD AND
 CONTRASTING MARKING STRIPE.
  
 7) PLANS ( A503 DETAIL 07) APPEAR TO HAVE A LIFT BUT NO
 PRODUCT INFORMATION HAS BEEN PROVIDED FOR THE LIFT,
 PLEASE SUBMIT THE MANUFACTURERS SPECIFICATIONS FOR
 LIFT. 2010 FBC-B 3001.6(F) LIFT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-11-07 Cont ID  
Sent By rlecky Date 2012-11-07 Time 09:50 Rev Time 0.00
Received By rlecky Date 2012-11-07 Time 09:50 Sent To  
Notes
2012-11-07 09:51:0812100295
 477 S. ROSEMARY AVENUE # 169
 NEW BOWLING ALLEY / RECREATION COMPLEX
  
 THE FOLLOWING PROVISO WAS PLACED ON THE ELECTRICAL
 PLAN.
  
 PROVISO:
  
 SAFE WORKING CLEARANCES AND DEDICATED WORKING SPACE IS
 REQUIRED AT ALL ELECTRICAL PANEL BOARDS. NEC 110.26,
 240.24
  
 THE BOWLING MACHINES AND THE AV EQUIPMENT MUST BE
 LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY
 (NRTL). NEC 110.3, 600.3
  
 SAFETY LABELING IS REQUIRED FOR ELECTRICAL DISCONNECTS
 AND FOR FLASH PROTECTION. NEC 110.22, 110.16
  
 SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA AND
 FIRE ALARM SYSTEMS.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-10-30 Cont ID  
Sent By rlecky Date 2012-10-30 Time 15:30 Rev Time 0.00
Received By rlecky Date 2012-10-25 Time 09:19 Sent To  
Notes
2012-10-30 15:32:2312100295
 477 S. ROSEMARY AVENUE # 169
 RECREATION COMPLEX
  
 PLEASE ADDRESS THE FOLLOWING ELECTRICAL PLAN REVIEW
 COMMENTS.
  
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
  
 SHEET E1:
 NOTE G23: MULTIWIRE BRANCH CIRCUITS REQUIRE A MEANS
 THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED
 CONDUCTORS. NEC 210.4
  
 SHEET E3:
 PROVIDE A STRUCTURAL SUPPORT DETAIL FOR LIGHT FIXTURES
 AND LIGHTING ARRAYS WEIGHING MORE THAN 50 POUNDS. NEC
 410.36, 314.27
  
 SHEET E6:
 PROVIDE A DETAIL FOR THE CORD STRAIN RELIEF REQUIRED
 FOR THE PINSITTER CORD. NEC 400.10
 INDICATE AND LABEL ON THE PLAN THE METHOD SELECTED TO
 PROVIDE THE REQUIRED SAFE WORKING CLEARANCES AND
 DEDICATED WORKING SPACE AT THE ELECTRICAL PANEL BOARDS.
 NEC 110.26, 240.24
 VERIFY THE BOWLING MACHINES AND THE AV EQUIPMENT ARE
 LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY
 (NRTL). NEC 110.3, 600.3
  
 SHEET E 11:
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 DISCONNECTS AND FOR FLASH PROTECTION. NEC 110.22,
 110.16
  
 NOTE:
 SEPARATE PERMITS ARE REQUIRED FOR VOICE AND DATA AND
 FIRE ALARM SYSTEMS
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-11-14 Cont ID  
Sent By ddaniels Date 2012-11-14 Time 09:30 Rev Time 0.00
Received By ddaniels Date 2012-11-14 Time 09:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-10-25 Cont ID  
Sent By wjolin Date 2012-10-25 Time 12:51 Rev Time 0.00
Received By wjolin Date 2012-10-18 Time 11:30 Sent To  
Notes
2012-10-18 12:03:47477 SOUTH ROSEMARY AVENUE - SUITE #169
 PERMIT #12100295
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: THE PERMIT INFORMTION INDICATES THIS PROJECT
 IS FOR SUITE #169; HOWEVER, THE PLANS ALL INDICATE
 SUITE #100. PLEASE CLARIFY.
  
 GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 GENERAL: ALL ASSEMBLY AREAS SHALL BE PROVIDED WITH
 PERMANENT SIGNAGE INDICATING "NO SMOKING BY ORDER OF
 THE FIRE MARSHAL."
  
 GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 GENERAL: CURTAINS, DRAPES AND OTHER LOOSELY HANGING
 FINISHINGS/DECORATIONS SHALL MEET THE FLAME PROPAGATION
 CRITERIA OF NFPA 701 (MATERIAL WILL SELF EXTINGUISH
 ONCE DIRECT FIRE FLAME HAS BEEN REMOVED). THE INTERIOR
 FINISH MATERIALS FOR WALLS AND CEILINGS SHALL MEET THE
 SMOKE DEVELOPMENT (0-450) AND FLAME SPREAD (76-200)
 REQUIREMENTS FOR CLASS C INTERIOR FINISHES PER NFPA
 101.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: PROVIDE A CONTRASTING MARKING STRIPE ON EACH
 LEADING EDGE OF THE STAIRS SO AS TO MAKE IT READILY
 APPARENT THAT AN ELEVATION CHANGE EXITS ON THE SHORT
 RUN OF STAIRS.
  
 LIFE SAFETY SHEET 001: TO HELP SIMPLIFY THE OVERALL
 SCHEME, PLEASE INCLUDE THE FOLLOWING INFORMATION ON THE
 LIFE SAFETY PLAN: EXIT SIGN LOCATIONS (WITH INDICATING
 CHEVRONS), FIRE EXTINGUISHER LOCATIONS, TRAVEL
 DISTANCES, COMMON PATH OF TRAVEL, ETC.
  
 ELECTRICAL: INDICATE THE LOCATION OF THE FACP AND THE
 VOICE EVACUATION PANEL.
  
 ELECTRICAL: FIRE ALARM VOICE EVACUATION SYSTEM SHALL
 OVERRIDE THE DJ/MUSIC SYSTEM TO ENSURE FIRE ALARM
 MESSAGE IS INTELLIGIBLE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2012-11-28 Time   Rev Time 0.00
Received By rregueir Date 2012-11-19 Time 13:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-19 Cont ID  
Sent By lmartine Date 2012-11-14 Time 13:22 Rev Time 0.00
Received By lmartine Date 2012-11-06 Time 15:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-10-30 Time   Rev Time 0.00
Received By rregueir Date 2012-10-11 Time 13:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-11-13 Cont ID  
Sent By rregueir Date 2012-11-13 Time 16:12 Rev Time 0.00
Received By rregueir Date 2012-11-13 Time 16:08 Sent To  
Notes
2012-11-13 16:10:07PROVISO:
  
 PAGE M2: REVISE AIR BALANCE SCHEDULE TO REFLECT THE AIR
 BEING EXHAUSTED BY THE FCU'S TO SHOW THAT THE BUILDING
 IS BEING MAINTAINED AT A POSITIVE PRESSURE PER FBC-EB
 503.2.10.6.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-10-29 Cont ID  
Sent By rregueir Date 2012-10-29 Time 10:38 Rev Time 0.00
Received By rregueir Date 2012-10-25 Time 13:05 Sent To  
Notes
2012-10-25 15:02:00REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M1: GENERAL NOTE #17 CALLS FOR SMOKE DETECTORS TO
 BE INSTALLED IN THE RETURN AIR DUCT. SMOKE DETECTORS
 ARE REQUIRED TO BE IN THE SUPPLY PER FBC-M 606.2.1.
  
 2. PG M1: PLEASE CLARIFY THE AIR BALANCE SCHEDULE. IT
 IS NOT CLEAR HOW THE REQUIRED RATE OF OUTSIDE AIR WILL
 BE INTRODUCTED THROUGH THE FCU WHEN THE RETURN AIR IS
 100% EQUAL TO THE SUPPLY AIR. EXAMPLE: FCU-1 HAS 5854
 CFM SUPPLY AND 5854 CFM OF RETURN. HOW CAN AN
 ADDITIONAL 2280 CFM OF OUTSIDE AIR BE INCLUDED IN THIS
 SYSTEM? SEE FBC-M 403.1.
  
 3. PG M2: MECHANICAL OUTDOOR AIR INTAKE OPENINGS SHALL
 BE LOCATED A MINIMUM OF 10 FEET HORIZONTALLY FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT SOURCE, SUCH AS
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS PER
 FBC-M 401.4.1.
  
 4. PG M2: WORK NOTE #1: CONDENSATE IS PROHIBITED FROM
 BEING DISCHARGED INTO SANITARY SEWER SYSTEM PER CITY
 ORDINANCE. DISCHARGE INTO EXISTING BUILDING CNDENSATE
 SYSTEM OR PROPOSE ANOTHER APPROPRIATE LOCATION.
  
 5. PG M2: APPLIANCES SHALL NOT BE INSTALLED IN A
 LOCATION WHERE SUBJECT TO MECHANICAL DAMAGE UNLESS
 PROTECTED BY APPROVED BARRIERS. SHOW HOW CU 1 AND CU 2
 WILL BE PROTECTED PER FBC-M 303.4.
  
 6. PG M2: IT APPEARS THAT AREA SERVICE 128 IS BEING
 DESIGNED WITH A PLENUM CEILING. IT SHOULD BE NOTED THAT
 MATERIALS WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR
 SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND
 A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84 OR UL 723 PER FBC-M
 602.2.1. IT'S POSSIBLE THAT COMBUSTIBLES SUCH AS PVC
 MAY BE PENETRATING THE FLOOR SLAB ABOVE THIS SPACE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-10-29 Cont ID  
Sent By lwagner Date 2012-10-29 Time 13:22 Rev Time 0.00
Received By lwagner Date 2012-10-29 Time 13:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2012-11-28 Cont ID  
Sent By rregueir Date 2012-11-28 Time 11:23 Rev Time 0.00
Received By rregueir Date 2012-11-28 Time 11:23 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2012-11-21 Cont ID  
Sent By jwitmer Date 2012-11-21 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2012-11-21 Time 15:13 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2012-11-19 Cont ID  
Sent By jwitmer Date 2012-11-19 Time 14:58 Rev Time 0.00
Received By jwitmer Date 2012-11-19 Time 14:58 Sent To  
Notes
2012-11-19 14:59:29BUILDING PLAN REVIEW
 PERMIT: 12100295
 ADD: 477 S ROSEMARY SUITE # 169
 CONT: CRAFT CONSTRUCTION
 TEL: (561)275-8770
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 NOV. 19/2012
 ACTION: DENIED
  
 1) NEED LETTER FROM CITY PLACE INDICATING AN APPROVED
 REVIEW OF ELEMENTS WITHIN THE TENANT BUILD OUT.
  
 2)2ND REQUEST THIS BUILDING MEETS THE DEFINITION OF A
 THRESHOLD BUILDING AND WILL NEED TO PROVIDE (3) THREE
 COPIES OF ALL DOCUMENTS, 1 FIELD SET, 1 BUILDING
 DEPARTMENT OFFICE SET & 1 SET FOR THRESHOLD INSPECTOR.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) NOTE: A SOFT-HOLD (REVIEWS WII CONTINUE, THE PERMIT
 WILL NOT BE ISSUED UNTIL THE FOLLOWING ITEMS ARE
 SUBMITTED TO KEN CONRAD) WILL BE PUT ON THIS PROJECT
 UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY THE
 CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 2D)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONCRETE RESTORATION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 2D()2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 NOTE: 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 NOTE: PLEASE CALL THE CITY OF WEST PALM BEACH'S
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2012-11-19 Cont ID  
Sent By eschneid Date 2012-11-19 Time 17:26 Rev Time 0.50
Received By eschneid Date 2012-11-19 Time 17:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2012-11-14 Cont ID  
Sent By eschneid Date 2012-11-13 Time 16:04 Rev Time 1.50
Received By eschneid Date 2012-11-13 Time 16:04 Sent To  
Notes
2012-11-14 15:02:06FAILED
  
 PLEASE PROVIDE RESPONSES IN WRITING.
  
 1) REPEAT COMMENT - THE CITYPLACE DESIGN GUIDELINES
 INCLUDE A SECTION ON THE ARCHITECTURAL CHARACTER FOR
 CITYPLACE. THIS INCLUDES THAT THE MATERIALS WILL BE
 DERIVED FROM THE MEDITERRANEAN VOCABULARY. PRIMARY
 BUILDING MATERIALS WILL BE LIGHT COLORED STUCCO, STONE
 OR PRECAST. WOOD, TILE AND STONE WILL BE USED IN WINDOW
 AND OTHER FACADE DETAILS. THE INTERIOR ARCADE ELEVATION
 SHOWS THE MAJORITY OF THE FACADE TREATED WITH "MFG.
 GENERAL SHALE BRICK STYLE, ENGLISH PUB" BRICKS. STAFF
 HAS LOOKED AT THE BRICK STYLE ON THE MANUFACTURER'S
 SITE, AND THEY DO NOT COMPLY WITH THE MEDITERRANEAN
 CHARACTER REQUIREMENT. PLEASE NOTE THAT A COMMENT ABOUT
 BRICKS NOT MEETING THE MEDITERRANEAN CHARACTER WAS MADE
 IN AN E-MAIL TO GINA MOORE ON MARCH 23, 2012.
  
 2) REPEAT COMMENT - THE CITYPLACE DESIGN GUIDELINES
 ENCOURAGE VARIATION IN THE ROSEMARY RETAIL CORRIDOR
 STREET FACADE. AS SUCH, PLEASE CONSIDER VARYING THE
 MATERIALS AT VARIOUS POINTS ALONG THE 300+ FOOT LONG
 FACADE. CITYPLACE HAS PROVIDED AN E-MAIL WITH A
 CONCEPTUAL ELEVATION TO STAFF WHICH SHOWS STUCCO ON
 PIERS ALONG THE FACADE. THE ZONING STAFF IS AMENIABLE
 TO THE CONCEPT OF STUCCO PIERS TO VARY THE FACADE, BUT
 HAS NOT SEEN THE FINAL VERSION OF WHAT CITYPLACE WILL
 APPROVE.
  
 3) THE NEW POSTER CASES PROPOSED ON THE ROSEMARY AVENUE
 FRONTAGE ARE NOT PERMITTED, AS THEY ARE NOT DESIGNATED
 LOCATIONS IN THE CITYPLACE MASTER SIGN PLAN.
  
 4) PLEASE REMEMBER THAT THE RS THAT ARE USED AS DOOR
 HANDLES SHALL COUNT TOWARD THE SIGNAGE SQUARE FOOTAGE
 ON THE BUILDING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-10-30 Cont ID  
Sent By escheide Date 2012-10-30 Time 20:24 Rev Time 4.00
Received By eschneid Date 2012-10-30 Time 20:24 Sent To  
Notes
2012-10-30 20:28:25FAILED
  
 PLEASE PROVIDE RESPONSES IN WRITING.
  
 1) THE INDOOR RECREATION USE IS NOT PERMITTED WITHIN
 THE CITYPLACE DRI. ZONING STAFF MAY NOT APPROVE THIS
 PERMIT UNTIL THE CITYPLACE DRI IS AMENDED TO ALLOW THE
 USE.
  
 2) THE CITYPLACE DESIGN GUIDELINES INCLUDE A SECTION ON
 THE ARCHITECTURAL CHARACTER FOR CITYPLACE. THIS
 INCLUDES THAT THE MATERIALS WILL BE DERIVED FROM THE
 MEDITERRANEAN VOCABULARY. PRIMARY BUILDING MATERIALS
 WILL BE LIGHT COLORED STUCCO, STONE OR PRECAST. WOOD,
 TILE AND STONE WILL BE USED IN WINDOW AND OTHER FACADE
 DETAILS. THE INTERIOR ARCADE ELEVATION SHOWS THE
 MAJORITY OF THE FACADE TREATED WITH "MFG. GENERAL SHALE
 BRICK STYLE, ENGLISH PUB" BRICKS. STAFF HAS LOOKED AT
 THE BRICK STYLE ON THE MANUFACTURER'S SITE, AND THEY DO
 NOT COMPLY WITH THE MEDITERRANEAN CHARACTER
 REQUIREMENT. PLEASE NOTE THAT A COMMENT ABOUT BRICKS
 NOT MEETING THE MEDITERRANEAN CHARACTER WAS MADE IN AN
 E-MAIL TO GINA MOORE ON MARCH 23, 2012.
  
 3) THE CITYPLACE DESIGN GUIDELINES ENCOURAGE VARIATION
 IN THE ROSEMARY RETAIL CORRIDOR STREET FACADE. AS SUCH,
 PLEASE CONSIDER VARYING THE MATERIALS AT VARIOUS POINTS
 ALONG THE 300+ FOOT LONG FACADE.
  
 4) THE CITYPLACE MASTER SIGN PLAN DOES NOT PERMIT
 AWNINGS TO BE INTERNALLY ILLUMINATED. PLEASE EXPLAIN
 THE PURPOSE OF THE LIGHTING MOUNTED RECESSED INTO THE
 CANOPY. IS THIS TO PROVIDE DOWN LIGHTING OR TO
 ILLUMINATE THE CANOPY?
  
 5) THE RS THAT ARE USED AS DOOR HANDLES SHALL COUNT
 TOWARD THE SIGNAGE SQUARE FOOTAGE ON THE BUILDING.
  
 6) PLEASE PROVIDE TWO MORE WINDOWS ON FERN STREET.
  
 7) MANY OF THE PAGES SHOW WHAT APPEARS TO BE A TABLE
 LAYER OVERLAP IN THE SOUTHEAST PORTION (OUTDOOR PATIO)
 OF THE FACILITY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.