Plan Review Details - Permit 12090727
Plan Review Stops For Permit 12090727
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-10-18 Cont ID  
Sent By rmcdouga Date 2012-10-18 Time 13:39 Rev Time 0.00
Received By rmcdouga Date 2012-10-18 Time 13:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2012-10-18 Cont ID  
Sent By rmcdouga Date 2012-10-18 Time 13:37 Rev Time 0.00
Received By rmcdouga Date 2012-10-18 Time 13:37 Sent To  
Notes
2012-10-18 13:39:32PREVIOUSLY APPROVED AND FINALED UNDER PERMIT #07011353.

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-10-18 Cont ID  
Sent By rmcdouga Date 2012-10-18 Time 13:40 Rev Time 0.00
Received By rmcdouga Date 2012-10-18 Time 13:40 Sent To  
Notes
2012-10-18 14:24:002010 FBC
  
 PLUMBING PROVISO
  
 DUE TO CHANGES TO THE SWIMMING POOL CODES SINCE THE
 POOL WAS ORIGINALLY PERMITTED UNDER THE 2004 FBC, THE
 FOLLOWING REQUIREMENTS MUST BE MEET.
  
 1) ANSI/APSP-7 2006 SECTION 4.4 (2010 FBCR4101.6.3)
 LIMITS THE WATER VELOCITY IN THE MAIN DRAIN BRANCH
 SUCTION TO 6 FT/SEC WHEN ONE OF THE PAIR IS BLOCKED.
 THE BRANCH PIPING FOR THIS POOL IS TWO INCHES.
 THEREFORE, THE MAXIMUM FLOW RATE FOR THE PUMP CAN NOT
 EXCEED 60 GPM.
  
 2) THE 2010 FBC ENERGY CONSERVATION SECTION 403.9.4
 REQUIRES POOL PUMPS AND POOL PUMP MOTORS WITH A TOTAL
 HORSE POWER (HP) OF GREATER THAN OR EQUAL TO 1 HP TO
 HAVE THE CAPABILITY OF OPERATING AT TWO OR MORE SPEEDS.
 THE LOW SPEED SHALL HAVE A ROTATION RATE OF NO MORE
 THAN 1/2 OF THE MOTOR'S MAXIMUM ROTATION RATE. THE PUMP
 MOTOR SHALL NOT BE SPLIT-PHASE, SHADED POLE OR
 CAPACITOR START-INDUCTION RUN TYPES.

Review Stop Z ZONING
Rev No 1 Status N Date 2012-10-18 Cont ID  
Sent By rmcdouga Date 2012-10-18 Time 13:35 Rev Time 0.00
Received By rmcdouga Date 2012-10-18 Time 13:35 Sent To  
Notes
2012-10-18 13:36:45PREVIOUSLY APPROVED UNDER PERMIT #07011351


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved