Plan Review Details - Permit 12090691
Plan Review Stops For Permit 12090691
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-01 Cont ID  
Sent By rmcdouga Date 2012-10-01 Time 13:29 Rev Time 0.00
Received By rmcdouga Date 2012-10-01 Time 13:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-27 Cont ID  
Sent By rmcdouga Date 2012-09-27 Time 08:21 Rev Time 0.00
Received By rmcdouga Date 2012-09-27 Time 08:21 Sent To  
Notes
2012-09-27 08:21:162010 FBC
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVALS ARE MISSING REQUIRED SHEETS 2
 THROUGH 6 AND 51. PLEASE SUBMIT TWO SETS OF THE MISSING
 SHEETS. DCA RULE 9N-3
  
 2) THE EXPOSURE CATEGORY ON THE ARCHITECTS CALCULATION
 LETTER IS INCORRECTLY SPECIFIED AS B. THIS STRUCTURE IS
 LOCATED IN EXPOSURE D PER FBC 1609.4.3
  
 3) THE APPLICATION LISTS THE SQUARE FOOTAGE AS 14,598
 AND THE VALUE OF THE WORK AS $ 12,000.00. BASED ON
 MARSHALL AND SWIFT ESTIMATING GUIDE THE AVERAGE COST
 PER SQUARE FOOT FOR THIS TYPE OF ROOF IS MUCH HIGHER
 FOR 14,598 SQFT OF ROOFING. PLEASE CLARIFY. CITY
 AMENDMENTS 109.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-01 Cont ID  
Sent By rmcdouga Date 2012-10-01 Time 13:29 Rev Time 0.00
Received By rmcdouga Date 2012-09-28 Time 16:17 Sent To  
Notes
2012-09-28 16:17:58TO RM