Plan Review Details - Permit 12090651
Plan Review Stops For Permit 12090651
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-27 Cont ID  
Sent By hmoser Date 2012-09-27 Time 10:21 Rev Time 0.00
Received By hmoser Date 2012-09-26 Time 09:24 Sent To  
Notes
2012-09-26 09:25:16TO HM DESK
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-09-27 Cont ID  
Sent By hmoser Date 2012-09-27 Time 10:20 Rev Time 0.00
Received By hmoser Date 2012-09-27 Time 10:10 Sent To  
Notes
2012-09-27 10:20:36PASS PROVISO
 1) PROVIDE A LETTER FROM A ENGINEER FOR CURB
 TO ROOF TIEDOWN AND RTU TO CURB TIEDOWN.
 PER SECTION 310.12 WIND RESISTANCE 2010 FBC (M)
 2) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS.
 2010 FBC (M)
 3) REFER TO SECTION 606.2.1 SUPERVISION 2010 FBC (M)
 4) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]