Plan Review Stops For Permit 12090651 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-09-27 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2012-09-27 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2012-09-26 |
Time |
09:24 |
Sent To |
|
|
Notes |
2012-09-26 09:25:16 | TO HM DESK | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2012-09-27 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2012-09-27 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2012-09-27 |
Time |
10:10 |
Sent To |
|
|
Notes |
2012-09-27 10:20:36 | PASS PROVISO | | 1) PROVIDE A LETTER FROM A ENGINEER FOR CURB | | TO ROOF TIEDOWN AND RTU TO CURB TIEDOWN. | | PER SECTION 310.12 WIND RESISTANCE 2010 FBC (M) | | 2) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS. | | 2010 FBC (M) | | 3) REFER TO SECTION 606.2.1 SUPERVISION 2010 FBC (M) | | 4) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS | | 2010 FLORIDA ENERGY CODE | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|
|
|