Plan Review Details - Permit 12090544
Plan Review Stops For Permit 12090544
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-12 Cont ID  
Sent By rmcdouga Date 2012-10-12 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2012-10-08 Time 10:21 Sent To  
Notes
2012-10-10 10:21:51SENT TO MCDOUGAL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-03 Cont ID  
Sent By rmcdouga Date 2012-10-03 Time 10:17 Rev Time 0.00
Received By rmcdouga Date 2012-09-21 Time 11:14 Sent To  
Notes
2012-09-24 11:15:24IN MECHANICAL BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-10-12 Cont ID  
Sent By rmcdouga Date 2012-10-12 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2012-10-12 Time 11:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-10-03 Cont ID  
Sent By rmcdouga Date 2012-10-03 Time 10:17 Rev Time 0.00
Received By rmcdouga Date 2012-10-03 Time 09:47 Sent To  
Notes
2012-10-03 10:17:252010 FBC
  
 DENIED BY BUILDING
  
 1) THE EQUIPMENT SIZING CALCULATIONS SPECIFY 28,841
 TOTAL BTUH AND 2.4 COOLING TONS, WHICH REQUIRES A 2.5
 TON A/C UNIT. THE ENERGY CALCULATION FORM THAT WAS
 SUBMITTED PREVIOUSLY ALSO LISTS A 30,000 BTUH (2.5 TON)
 UNIT, IN ADDITION TO A 36,000 BTUH (3 TON) UNIT AND A
 60,000 BTUH (5 TON) UNIT. HOWEVER, THE EQUIPMENT
 SCHEDULE ON THE PLANS LISTS TWO 3 TON AND ONE 5 TON
 UNITS. PLEASE CORRECT. FBCR M1401.3 & FBC ENERGY
 CONSERVATION SECTION 405
  
 2) THE PREVIOUSLY SUBMITTED ENERGY CALCULATION FORM
 SPECIFIES ALL THREE UNITS AS 16 SEER. THE EQUIPMENT
 SCHEDULE ON THE PLANS LISTS THE 5 TON AS 15 SEER PLEASE
 CORRECT. FBCR M1401.3 & FBC ENERGY CONSERVATION SECTION
 405
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]