Plan Review Details - Permit 12090535
Plan Review Stops For Permit 12090535
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-09-24 Cont ID  
Sent By rlecky Date 2012-09-24 Time 13:58 Rev Time 0.00
Received By rlecky Date 2012-09-24 Time 13:48 Sent To  
Notes
2012-09-24 14:01:4912090535
 2840 WILDERNESS ROAD
 KITCHEN AND BATH REMODEL
  
 THE FOLLOWING CODE REQUIREMENTS WERE NOTED ON THE PLAN.
  
 PROVISO:
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
 RECEPTACLES SERVICING KITCHEN COUNTERTOP SURFACES AND
 BATH ROOMS REQUIRE GROUND FAULT PROTECTION. NEC 210.8
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER