Plan Review Details - Permit 12090498
Plan Review Stops For Permit 12090498
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2012-10-22 Cont ID  
Sent By wjolin Date 2012-10-22 Time 12:55 Rev Time 0.00
Received By wjolin Date 2012-10-22 Time 12:47 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-10-11 Cont ID  
Sent By wjolin Date 2012-10-11 Time 13:45 Rev Time 0.00
Received By wjolin Date 2012-10-11 Time 13:15 Sent To M
Notes
2012-10-11 13:45:322275 PALM BEACH LAKES BOULEVARD
 PERMIT #12090498
 MASTER #12030334
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SPRINKLER PLANS
 REPEAT COMMENT: THE SPRINKLER PLANS AND HYDRAULIC
 CALCULATIONS ARE NOT SIGNED AND SEALED BY THE
 PROFESSIONAL ENGINEER (B. MASKOL).
 NEW COMMENT: NO FIRE PROTECTION ENGINEERING DOCUMENTS
 WERE EVER SUBMITTED WITH THE MASTER PERMIT (#12030334);
 THEREFORE, THE SHOP DRAWINGS NEED TO BE SIGNED/SEALED
 OR ENGINEERING DOCUMENTS NEED TO BE SIGNED/SEALED AND
 SUBMITTED WITH THE ISSUED MASTER PERMIT.
  
 REPEAT COMMENT: PLEASE PROVIDE HYDRAULIC CALCULATIONS
 FOR THE SOUTHWEST (CLASSROOM AREA) OF THE BUILDING
 (ROOM #105A & #105B).
 NEW COMMENT: PLEASE INCLUDE THE NODES ON THE FLOOR
 PLAN. THE HYDRAULIC AREA (ROOM #105A & #105B) IS FOR
 INDICATING LOCATION ONLY, THE REMOTE AREA STILL NEEDS
 TO BE AT LEAST 900 SQ.FT. (DEPENDENT UPON CEILING
 HEIGHT) AND HAVE A LENGTH OF 1.2 X SQUARE ROOT OF THE
 REMOTE AREA.
  
  
 NOTE:THE FOLLOWING CIVIL PLAN REVIEW COMMENTS ARE FOR
 INFORMATIONAL PURPOSES ONLY. A SPRINKLER PERMIT FOR THE
 INTERIOR WORK CAN BE ISSUED AS THE UNDERGROUND PIPING
 WILL REQUIRE A SEPARATE PERMIT.
  
 METRO FIRE SPRINKLER HAS INDICATED THAT THEIR SCOPE OF
 WORK BEGINS AT 1'-0" ABOVE FINISHED FLOOR; THEREFORE A
 SEPARATE PLAN AND PERMIT WILL BE NEEDED FOR THE
 UNDERGROUND FIRE SERVICE MAIN.
  
 A FIRE HYDRANT IS NEEDED WITHIN 150 FEET OF THE FIRE
 DEPARTMENT CONNECTION.
  
 **FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES OF
 7'-6" TO THE FRONT AND SIDES AND 4' TO THE BACKSIDE PER
 SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION. THESE
 CLEARANCES WILL AFFECT THE ADJACENT PARKING SPACES.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-09-25 Cont ID  
Sent By wjolin Date 2012-09-25 Time 10:54 Rev Time 0.00
Received By wjolin Date 2012-09-25 Time 09:29 Sent To M
Notes
2012-09-25 10:54:492275 PALM BEACH LAKES BOULEVARD
 PERMIT #12090498
 MASTER #12030334
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SPRINKLER PLANS
 THE SPRINKLER PLANS AND HYDRAULIC CALCULATIONS ARE NOT
 SIGNED AND SEALED BY THE PROFESSIONAL ENGINEER (B.
 MASKOL).
  
 PLEASE PROVIDE HYDRAULIC CALCULATIONS FOR THE SOUTHWEST
 (CLASSROOM AREA) OF THE BUILDING (ROOM #105A & #105B).
  
  
 CIVIL PLANS
 METRO FIRE SPRINKLER HAS INDICATED THAT THEIR SCOPE OF
 WORK BEGINS AT 1'-0" ABOVE FINISHED FLOOR; THEREFORE A
 SEPARATE PLAN AND PERMIT WILL BE NEEDED FOR THE
 UNDERGROUND FIRE SERVICE MAIN.
  
 A FIRE HYDRANT IS NEEDED WITHIN 150 FEET OF THE FIRE
 DEPARTMENT CONNECTION.
  
 **FIRE HYDRANTS SHALL BE PROVIDED WITH CLEARANCES OF
 7?-6? TO THE FRONT AND SIDES AND 4? TO THE BACKSIDE PER
 SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION. THESE
 CLEARANCES WILL AFFECT THE ADJACENT PARKING SPACES.
  
 PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR
 SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
2012-09-20 13:54:00WITH FIRE DD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-10-24 Cont ID  
Sent By hmoser Date 2012-10-24 Time 07:04 Rev Time 0.00
Received By hmoser Date 2012-10-16 Time 13:07 Sent To  
Notes
2012-10-16 13:09:01INFORMATION SUBMITTED BEFORE COMPLETING THE MECHANICAL
 REVIEW. SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-24 Cont ID  
Sent By hmoser Date 2012-10-24 Time 07:03 Rev Time 0.00
Received By hmoser Date 2012-10-09 Time 12:04 Sent To  
Notes
2012-10-09 12:04:56FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-04 Cont ID  
Sent By hmoser Date 2012-10-04 Time 13:01 Rev Time 0.00
Received By hmoser Date 2012-09-19 Time 07:45 Sent To  
Notes
2012-09-20 07:46:03SENT TO FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-10-24 Cont ID  
Sent By hmoser Date 2012-10-24 Time 07:03 Rev Time 0.00
Received By hmoser Date 2012-10-24 Time 06:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-10-04 Cont ID  
Sent By hmoser Date 2012-10-04 Time 13:01 Rev Time 0.00
Received By hmoser Date 2012-10-04 Time 12:57 Sent To  
Notes
2012-10-04 13:01:20PLANS DENIED
 PLANS NOT STAMPED BY A ENGINEER
 PER SECTION 633.021 (5) (E) FLORIDA STATUTES.
 PLAN REVIEW BY HAROLD MOSER