Plan Review Details - Permit 12090280
Plan Review Stops For Permit 12090280
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-09-21 Cont ID  
Sent By jgomez Date 2012-09-21 Time 09:21 Rev Time 0.00
Received By jgomez Date 2012-09-21 Time 09:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-13 Cont ID  
Sent By jgomez Date 2012-09-13 Time 10:15 Rev Time 0.00
Received By jgomez Date 2012-09-13 Time 09:06 Sent To  
Notes
2012-09-13 10:29:16ROOF-RECOVER BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ACCORDING TO SEC. 1609.4.3 THIS BUILDING IS LOCATED
 ON EXPOSURE "C" NOT EXPOSURE "B". ENGINEER NEEDS TO
 REVISE THE ROOF COMPONENTS AND CLADDING CALCULATIONS
 AND THE RAS 117 CALCULATIONS AS REQUIRED.
  
 2- ENGINEER CALCULATIONS SUBMITTED SPECIFY ROOF
 COMPONENTS AND CLADDING FOR GABLE/HIP ROOFS. THIS
 BUILDING HAS A LOW SLOPE ROOF. CLARIFY AND REVISE AS
 REQUIRED. SEC. 107.2.1.2 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-21 Cont ID  
Sent By jgomez Date 2012-09-21 Time 09:21 Rev Time 0.00
Received By jgomez Date 2012-09-21 Time 09:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-13 Cont ID  
Sent By jgomez Date 2012-09-13 Time 09:07 Rev Time 0.00
Received By jgomez Date 2012-09-13 Time 09:07 Sent To  
Notes
***NONE***