Plan Review Details - Permit 12090265
Plan Review Stops For Permit 12090265
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-11-06 Cont ID  
Sent By rmcdouga Date 2012-11-06 Time 11:13 Rev Time 0.00
Received By rmcdouga Date 2012-11-02 Time 16:28 Sent To  
Notes
2012-11-06 11:13:032010 FBC
  
 REVISED PLANS REQUIRED
  
 1) SHEET T-1 FOR BUILDINGS A & B, DOES NOT LIST
 STRUCTURAL SHEET S-4 IN THE DRAWING INDEX. TWO T-1
 SHEETS FOR BUILDING B WERE SUBMITTED. PLEASE CORRECT.
 CITY AMENDMENTS 107.2.1
  
 2) ON SHEET A-2 FOR BLDG. B, THE SECOND FLOOR PLAN IS
 LABELED AS FIRST FLOOR PLAN. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1
  
 3) ON SHEET A-6 FOR BLDG. A, THERE IS A REVISION DATED
 8/31/11 IN THE TITLE BLOCK. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1 ( PREVIOUS COMMENT #8 )
  
 4) ON SHEET A-7 FOR BLDG. A, THERE IS A TYPO AT THE TOP
 OF THE TITLE BLOCK WHERE REVISION 5 IS PRINTED OVER THE
 NOTES. PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-10-17 Cont ID  
Sent By rmcdouga Date 2012-10-17 Time 15:30 Rev Time 0.00
Received By rmcdouga Date 2012-10-17 Time 08:15 Sent To  
Notes
2012-10-17 15:27:492010 FBC
  
 DENIED BY BUILDING
  
 1) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD OF THE PROJECT PER
 CITY AMENDMENTS 107.3.4.1
  
 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE 8"
 LINTELS. DCA RULE 9N-3
  
 3) SUBMIT TWO COPIES OF THE EVALUATION REPORTS FOR THE
 DEMILEC SPRAY FOAM INSULATION. FBC R316
  
 4) SUBMIT TWO COPIES OF THE EVALUATION REPORTS FOR THE
 HUBER ROOF SHEATHING SYSTEM. FBC R803 AND CITY
 AMENDMENTS 107.2.1.3
  
 5) ON SHEET T-1 FOR BUILDING A, UNDER THE PROJECT
 ANALYSIS EXPOSURE B IS SPECIFIED RATHER THAN C. FBC
 R301.2.1.4
  
 6) ON SHEET A-2 BLDG. A, THERE IS A DETAIL TAG FOR 2 ON
 A3.2 AT THE LAUNDRY ROOM THAT APPEARS TO BE A TYPO.
 PLEASE CLARIFY. CITY AMENDMENTS 107.2.1
  
 7) ON A-4 FOR BLDG. A, THE LEFT SIDE ELEVATION IS
 MIS-LABELED AS RIGHT SIDE ELEVATION. CITY AMENDMENTS
 107.2.1
  
 8) ON SHEET A-6 BLDG. A, THERE IS A REVISION DATED
 8/31/11 IN THE TITLE BLOCK. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1
  
 9) ON SHEETS A-1 AND A-2, BOTH BUILDING TYPES HAVE NOTE
 2 ON THE DOOR SCHEDULE THAT REFERENCES THE 2011 FBC.
 PLEASE CORRECT TO THE 2010 FBC.
  
 10) THE FLOOR PLANS ON SHEETS A-1 AND A-2 FOR BUILDING
 B ARE MISSING THE DIMENSION LINES. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1
  
 11) SHEET A-2 BLDG. B HAS REVISIONS FROM 2009 NOTED IN
 THE TITLE BLOCK. PLEASE CHECK ALL SHEETS FOR OLD
 REVISIONS NOTES THAT DO NOT PERTAIN TO THIS PERMIT AND
 REMOVE THEM. CITY AMENDMENTS 107.2.1 AND FS 481
  
 12) ON SHEET A-4A BLDG. B THE LEFT ELEVATION IS NOT
 LABELED AND THERE IS A TYPO WHERE THE FLOOR/BEAM
 ELEVATIONS ARE PRINTED OVER THE TITLE BLOCK. PLEASE
 CORRECT. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-11-06 Cont ID  
Sent By rmcdouga Date 2012-11-06 Time 09:23 Rev Time 0.00
Received By rmcdouga Date 2012-11-02 Time 16:25 Sent To  
Notes
2012-11-06 09:30:472010 FBC & 2008 NEC
  
 REVISED PLANS REQUIRED
  
 1) ON SHEET E-2 FOR BUILDING A THE FLOOR PLAN IS
 LABELED AS FIRST FLOOR PLAN AND IT IS THE SECOND FLOOR
 PLAN. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-10-16 Cont ID  
Sent By rmcdouga Date 2012-10-16 Time 15:52 Rev Time 0.00
Received By rmcdouga Date 2012-10-16 Time 15:52 Sent To  
Notes
2012-10-16 16:54:272010 FBC & 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) PROVIDE ELECTRICAL RISER DIAGRAMS WITH WIRE SIZES,
 CONDUIT DETAIL AND GROUNDING DETAIL ON THE PLANS FOR
 BUILDING A & BUILDING B. CITY AMENDMENTS FBC 107.3.5.3
  
 2) THE OVERHEAD GARAGE DOOR RECEPTACLE FOR THE LEFT
 UNIT ON SHEET E-1 OF BUILDING B IS NOT SPECIFIED AS
 GFCI. NEC 210.8
  
 3) REVISE THE NOTE FOR AFCI PROTECTION IN THE
 ELECTRICAL LEGEND TO INCLUDE IN ADDITION TO BEDROOMS
 THE OTHER ROOMS LISTED IN NEC 210.12(B).
  
 4) CORRECT THE NOTE BELOW THE LOAD CALCULATIONS ON
 SHEET E2 OF BUILDING A THAT REFERENCES THE 2005 NEC.
 THE CURRENT EDITION IS 2008 NEC.
  
 5) THE LIGHT AND RECEPTACLE AT THE ATTIC ACCESS IS
 SHOWN IN THE WRONG CLOSETS ON SHEET E2 OF BUILDING A.
 NEC 210.70 (3)
  
 6) THERE ARE REVISION NOTES IN THE TITLE BLOCK FROM
 2009 ON SHEETS E1 OF BUILDING A & E2 OF BUILDING B.
 CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2012-10-17 Cont ID  
Sent By rmcdouga Date 2012-10-17 Time 15:30 Rev Time 0.00
Received By rmcdouga Date 2012-10-17 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2012-10-10 Cont ID  
Sent By rmcdouga Date 2012-10-10 Time 07:30 Rev Time 0.00
Received By rmcdouga Date 2012-10-10 Time 07:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-29 Cont ID  
Sent By rmcdouga Date 2012-11-29 Time 10:14 Rev Time 0.00
Received By rmcdouga Date 2012-10-22 Time 10:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-17 Cont ID  
Sent By rmcdouga Date 2012-10-17 Time 15:31 Rev Time 0.00
Received By rmcdouga Date 2012-09-11 Time 16:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2012-10-10 Cont ID  
Sent By rmcdouga Date 2012-10-10 Time 07:30 Rev Time 0.00
Received By rmcdouga Date 2012-10-10 Time 07:30 Sent To  
Notes
2012-10-10 07:31:05IMPACT FEES WILL BE PAID WHEN APPLICATIONS ARE
 SUBMITTED UNDER THIS MASTER.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-11-06 Cont ID  
Sent By rmcdouga Date 2012-11-06 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2012-11-06 Time 10:52 Sent To  
Notes
2012-11-06 10:53:092010 FBC
  
 PROVISO
  
 1) SUBMIT ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS ( MANUAL J) FOR THE UNITS IN BUILDINGS A
 AND B. FBCR M1401.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-10-17 Cont ID  
Sent By rmcdouga Date 2012-10-17 Time 07:41 Rev Time 0.00
Received By rmcdouga Date 2012-10-17 Time 07:41 Sent To  
Notes
2012-10-17 08:12:542010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS ( MANUAL J) FOR THE UNITS IN BUILDINGS A
 AND B. FBCR M1401.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-10-10 Cont ID  
Sent By rmcdouga Date 2012-10-10 Time 07:29 Rev Time 0.00
Received By rmcdouga Date 2012-10-10 Time 07:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-11-15 Cont ID  
Sent By eschneid Date 2012-11-14 Time 15:56 Rev Time 2.00
Received By eschneid Date 2012-11-14 Time 15:56 Sent To  
Notes
2012-11-15 09:04:26PASSED W/PROVISO
  
 1) THE SCREEN ENCLOSURES REQUIRE SEPARATE PERMITS.
  
 2) IF THE WALL OPTION IS PROVIDED, THEN THE LANDSCAPE
 REQUIRED BETWEEN THE PATIOS SHALL BE RELOCATED TO THE
 END OF THE WALL.
  
 3) THE WALL HEIGHT SHALL BE MEASURED FROM GRADE. THE
 WALL HEIGHT SHALL NOT EXCEED SIX (6) FEET WITHIN 10
 FEET OF THE REAR PROPERTY LINE.
  
 4) NOTE: THE FACADE TREATMENTS ON EACH BUILDING SHOULD
 COMPLEMENT EACH OTHER, AS SHOWN ON THE NON-OPTIONAL
 FRONT ELEVATION OF BUILDING B. THE MIXING OF RADICALLY
 DIFFERING FACADE TREATMENTS, AS SHOWN ON THE FRONT
 ELEVATION OF BUILDING A AND THE BUILDING B OPTIONS, DO
 NOT PRODUCE A HARMONIOUS VISUAL PRODUCT WHEN USED WITH
 JUST TWO ATTACHED UNITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-10-10 Cont ID  
Sent By eschneid Date 2012-09-25 Time 14:56 Rev Time 2.00
Received By eschneid Date 2012-09-25 Time 14:56 Sent To  
Notes
2012-09-25 14:59:47FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE SCREEN ENCLOSURES REQUIRE A SEPARATE PERMIT.
  
 2) PLEASE EXPLAIN WHAT IS DIFFERENT BETWEEN THE
 BUILDING A SIDE ELEVATIONS AND THE BUILDING A OPTIONAL
 SIDE ELEVATIONS.
  
 3) PLEASE EXPLAIN WHAT IS DIFFERENT BETWEEN THE
 BUILDING B RIGHT SIDE ELEVATION AND THE BUILDING B
 OPTIONAL RIGHT SIDE ELEVATION.
  
 4) THE PRIVACY WALL IS NOT AN APPROVED OPTION FOR
 OAKTON PRESERVE. AN APPROVED MINOR PLANNED DEVELOPMENT
 AMENDMENT IS REQUIRED WHICH WOULD SHOW THE WALL DETAILS
 AND THE PROGRAM FOR THE RELOCATION OF THE SHRUBS WHICH
 WERE TO BE LOCATED AT THE PROPOSED WALL LOCATION BEFORE
 ZONING STAFF WILL APPROVE THE PRIVACY WALL.
  
 5) NOTE: THE FACADE TREATMENTS ON EACH BUILDING SHOULD
 COMPLEMENT EACH OTHER, AS SHOWN ON THE FRONT ELEVATION
 OF BUILDING B. THE MIXING OF RADICALLY DIFFERING FACADE
 TREATMENTS, AS SHOWN ON THE FRONT ELEVATION OF BUILDING
 A, DOES NOT PRODUCE A HARMONIOUS VISUAL PRODUCT WHEN
 USED WITH JUST TWO ATTACHED UNITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  