Plan Review Details - Permit 12090213
Plan Review Stops For Permit 12090213
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-11-08 Cont ID  
Sent By shill Date 2012-11-08 Time 18:07 Rev Time 0.00
Received By shill Date 2012-11-08 Time 18:07 Sent To  
Notes
2012-11-08 18:11:45****PROVISO****
 ****ISSUED AT OWNER/CONTRACTOR'S RISK****
 ****REVISION REQUIRED****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 PER OWNER, EXISTING SLAB MEASURES 8" AND NEW SLAB WILL
 BE THICKENED AT EDGE TO ENSURE CONCRETE COVERAGE
 REQUIRED BY FBC 2010 RESIDENTIAL 404.1.2.3.7.4.
  
 REVISE DRAWING TO REFLECT FIELD CONDITION OF EXISTING
 SLAB, ADDITIONAL THICKNESS OF NEW SLAB EDGE, PATIO
 CONNECTION DETAIL W/DIMENSIONS
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-11-02 Cont ID  
Sent By shill Date 2012-11-02 Time 16:22 Rev Time 0.00
Received By shill Date 2012-11-02 Time 16:21 Sent To  
Notes
2012-11-02 16:29:56****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. OK.
  
 2. PROVIDE A STRUCTURAL DETAIL/SECTION SHOWING THE
 CONNECTION OF THE NEW CONCRETE TO EXISTING PATIO SLAB.
 IT SHOWS REBAR EMBEDDED INTO EXISTING, WITH A DECO
 DRAIN AT THE SAME LOCATION, SEE FBC R 404.1.2.3.7.4,
 CONCRETE COVER OF REINFORCEMENT, FBC 106.
  
 DETAIL NOT CLEAR. THE SLAB IS SHOWN AS 4", 2" DECO
 DRAIN WITH 1" ABOVE THE #3 REBAR AND 1" BELOW THE #3
 REBAR - THE REBAR HAS NO THICKENSS? PLEASE SEE CONCRETE
 COVERAGE REQUIREMENTS. PLEASE HAVE ENGINEER WHO SEALED
 THE PLAN CONTACT ME.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-24 Cont ID  
Sent By shill Date 2012-09-24 Time 11:37 Rev Time 0.00
Received By shill Date 2012-09-24 Time 11:37 Sent To  
Notes
2012-09-24 11:49:12****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A SITE PLAN SHOWING PROPOSED IMPROVEMENTS
 RELATIVE TO PROPERTY LINE, FBC 106.
  
 2. PROVIDE A STRUCTURAL DETAIL/SECTION SHOWING THE
 CONNECTION OF THE NEW CONCRETE TO EXISTING PATIO SLAB.
 IT SHOWS REBAR EMBEDDED INTO EXISTING, WITH A DECO
 DRAIN AT THE SAME LOCATION, SEE FBC R 404.1.2.3.7.4,
 CONCRETE COVER OF REINFORCEMENT, FBC 106.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-02 Cont ID  
Sent By shill Date 2012-11-02 Time 16:30 Rev Time 0.00
Received By shill Date 2012-10-18 Time 07:39 Sent To  
Notes
2012-10-18 07:41:24TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-24 Cont ID  
Sent By shill Date 2012-09-24 Time 11:49 Rev Time 0.00
Received By shill Date 2012-09-10 Time 15:39 Sent To  
Notes
2012-09-13 15:40:18SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2012-10-18 Time   Rev Time 0.00
Received By mdekle Date 2012-10-18 Time 14:02 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-09-20 Cont ID  
Sent By mdekle Date 2012-09-20 Time   Rev Time 0.00
Received By mdekle Date 2012-09-13 Time 16:43 Sent To B
Notes
2012-09-20 16:54:05THE APPLICANT MUST SUBMIT A SURVEY DEPICTING THE
 LOCATION OF THE PROPOSED IMPROVEMENTS IN RELATION TO
 PROPERTY LINES AND EXISTING STRUCTURES.