Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-09-20 Cont ID  
Sent By rlecky Date 2012-09-20 Time 16:08 Rev Time 0.00
Received By rlecky Date 2012-09-20 Time 16:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-09-17 Cont ID  
Sent By rlecky Date 2012-09-17 Time 10:01 Rev Time 0.00
Received By rlecky Date 2012-09-17 Time 09:19 Sent To  
Notes
2012-09-17 10:02:1612090202
 1801 PALM BEACH LAKES BLVD.
 TEMPORARY SITE LIGHTING.
  
 PROVIDE DETAIL ON THE SELECTED WIRING METHOD FOR THE
 LIGHTING. NEC 215.5, 225.4, 225.12,
 PROVIDE DETAIL AND ENGINEERING FOR THE LIGHT POLES WITH
 FIXTURES WHICH INDICATES CAPABILITY TO WITH STAND HIGH
 WIND. PROVIDE AN EXPOSURE CATEGORY AND IMPORTANCE
 FACTOR FOR THE DESIGN. FBC 1609, ASCE 7-10
 PROVIDE SIGNED AND SEALED WIND LOADING CERTIFICATION
 FOR THE LIGHT POLE ASSEMBLY WITH FIXTURES. 2010 FBC
 1609.1., ASCE 7-10
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER