Plan Review Details - Permit 12090196
Plan Review Stops For Permit 12090196
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-14 Cont ID  
Sent By jwitmer Date 2012-10-14 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2012-10-14 Time 09:04 Sent To  
Notes
2012-10-14 10:24:14BUILDING PLAN REVIEW
 PERMIT:12090196
 ADD: 1000-A OKEECHOBEE BLVD.
 CONT: SOUTH PALM CONSTRUCTION
 TEL: (561)301-81831
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 SUNDAY OCT. 14/ 2012
  
 NOTE: PLANS COMING BACK FROM ZONING ARE MISSING THE
 PERMIT APPLICATION, IF NOT LOCATED THE CONTRACTOR WILL
 NEED TO SUBMIT A SECOND ORIGINAL SO PERMIT MAY BE
 ISSUED. SEE NOTES ON FRONT SCREEN.
  
 BUILDING PROVISO: WILL NEED VALUES FOR WORK REQUIRED
 FOR ACCESSIBILITY CODE FROM EITHER THE DESIGN
 PROFESSIONAL OR THE CONTRACTOR BEFORE PERMIT ISSUANCE,
 PLANS APPEAR TO BE CODE COMPLIANT. I SPOKE WITH
 CONTRACTOR TO BE AWARE OF REQUIRED LETTER. CONTRACT
 VALUE OF $50,000.00 DOLLARS/ 20%= #10,000.00 DOLLARS
 ARE TO BE SPENT IN UPDATING THE BUILDING TO MEET THE
 ACCESSIBILITY CODE.
  
 2010 FLORIDA ACCESSIBILITY CODE: 202.4.1
 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 10/15/12
 CONTRACTOR E-MAILED BREAK DOWN FOR THE DISPROPORTIONATE
 COST. J WITMER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-18 Cont ID  
Sent By jwitmer Date 2012-09-18 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2012-09-18 Time 08:29 Sent To  
Notes
2012-09-18 10:23:29BUILDING PLAN REVIEW
 PERMIT:12090196
 ADD: 1000-A OKEECHOBEE BLVD.
 CONT: SOUTH PALM CONSTRUCTION
 TEL: (561)301-81831
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 SEPT. 18 / 2012
 ACTION: DENIED
  
 NOTE: 2010 FBC-P ) 315.1 REQUIREMENTS. PUBLIC FOOD
 SERVICE ESTABLISHMENTS AND FOOD ESTABLISHMENTS, AS
 DEFINED IN CHAPTER 381 FLORIDA STATUTES, CHAPTER 500
 FLORIDA STATUTES AND CHAPTER 509 FLORIDA STATUTES,
 SHALL COMPLY WITH THE APPLICABLE CODE REQUIREMENTS
 FOUND IN THE FLORIDA BUILDING CODE, BUILDING, CHAPTER
 4, SPECIAL DETAILED REQUIREMENTS BASED ON USE AND
 OCCUPANCY. PLEASE SEE DBPR WEBSITE FOR ADDITIONAL INFO:
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/HR/LICENSING/
 PLANREVIEWINDEX.HTML
  
 1) SHEET A4 VERSES A7:
  
 1A) SHEET A4 THE FLOOR PLAN DEPICTS THE RESTROOM DOORS
 BEING 21068 WHERE AS THE DOOR SCHEDULE INDICATES THE
 DOORS AS 3068, PLEASE UPDATE THE DISCREPANCY,
 WPB ADMINISTRATIVE CODE 107.2.1.3.
  
 1B) SHEET A4 AT THE VESTIBULE OPENING IT APPEARS TO BE
 A CASED OPENING WHERE AS A7 THE DOOR SCHEDULE IS
 INDICATED AS DOOR 102, TYPE B DOOR PLEASE UPDATE THE
 DISCREPANCY, WPB ADMINISTRATIVE CODE 107.2.1.3.
  
 1C) SHEET A4 THE DOUBLE ACTION DOOR THAT LEADS INTO THE
 KITCHEN IS DEPICTED AS 30 INCH DOOR WITH A WALL SECTION
 ADJACENT BEING 18 INCHES WHEN A DOOR MEETING THE
 ACCESSIBLITY CODE IS PROVIDED THEN THE ADJACENT WALL
 WILL NOT MEET THE REQUIREMENTS OF 2010 ACESSIBILITY
 CODE 404.2.4 MANEUVERING CLEARENCES.
  
 2) SHEET A4 VESTIBULE WIDTH OF 3'-8 1/2" PLEASE REVIEW
 2010 ACCESSIBILITY FIGURE 404.2.4.1(H) WHICH REQUIRES
 THE VESTIBULE TO BE A MINIMUM OF 48 INCHES IN WIDTH.
  
 3) SHEET A3 VS P1, THE A3 SHEET LIFE SAFETY SHEET DOE
 NOT INDICATE WHICH WALL IS A TENANT SEPERATION WALL AS
 IS INDICATED ON THE P1 SHEET. PLEASE PROVIDE
 WALL RATING AT THE TENANT SEPERATION WALL. 2010 FBC-B
 709.1.6. WALLS SEPERATING INDIVIDUAL TENANT SPACES.
  
 4) SHEET A1, OCCUPANCY TYPE IS LISTED AS A A2 RESTARANT
 PLEASE REVIEW 2010 FBC-B SECTION 303.1.1. RESTAURANTS
 AND DRINKING ESTABLISHMENTS WITH AN OCCUPANT LOAD OF
 LESS THAN 50 PERSONS SHALL BE CLASSIFIED AS GROUP M,
 MERCANTILE.
  
 5) SHEET A1 OCCUPANCY SEPERATION IS INDICATED AS A2 TO
 A2 ONLY TENANT SEPERATION REQUIRED, WITH THE NEW
 RESTARAUNT BEING CLASSIFIED AS MERCANTILE AND THE
 ADJACENT TENANT BEING A A2 RESTARAUNT THEN 2010 FBC-B
 TABLE 508.3.3 NON-SPRINKLERED WILL REQUIRE A 2 HOUR
 FIRE RATED WALL.
  
 6) PLUMBING SHEET P2 INDICATES THE GREAT BASIN GREASE
 SEPERATOR TO BE LOCATED ON THE EXTERIOR OF THE
 BUILDING, PLEASE BE AWARE THAT TRAFFIC PATERNS DO
 SURROUND THIS BUILDING AND A DETAIL FOR CONCRETE PAD
 WILL BE REQUIRED AND TRAFFIC BEARING TOP FOR GREASE
 INTERCEPTOR, PLEASE SEE MANUFACTURERS SPECIFICATIONS
 GREAT BASIN INSTALATION, OPERATION AND MAINTENANCE
 GUIDE SHEET 3 OF 7 REV. 3 11/07/11.
  
 7) SHEET A4 INDICATES A NEW EXTERIOR FRONT DOOR, THE
 DESIGNER OF RECORD INDICATES TYPE OF UNIT TO BE
 INSTALLED BUT THE CONTRACTOR DID NOT PROVIDE PRODUCT
 APPROVAL FOR THIS DOOR. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 8) SHEET A7 ROOM FINISH SCHEDULE INDICATES THE USE OF
 MR BOARD IN THE RESTROOMS BUT THE PLANS ARE SILENT TO
 THE FINISH AROUND THE WET AREAS THERE IS TWO INFORMAL
 INTERPRETATIONS FROM BOAF ON SECTION 1210.2 THAT THE
 CODE SECTION DOES NOT REGULATE THE TYPE OF WALL
 MATERIAL, JUST THE FINISH ON THE WALL. THE FINAL
 DECISION MUST BE MADE BY THE LOCAL JURISDICTION AS TO
 WHAT IS CONSIDERED HARD, SMOOTH AND NON-ABSORBENT. THE
 BUILDING OFFICIAL HAS ALLOWED THE USE OF EPOXY PAINT ON
 MR BOARD AS A HARD, SMOOTH AND NON-ABSORBENT SURFACE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-09-19 Cont ID  
Sent By rlecky Date 2012-09-19 Time 15:56 Rev Time 0.00
Received By rlecky Date 2012-09-19 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-10-11 Cont ID  
Sent By wjolin Date 2012-10-11 Time 11:49 Rev Time 0.00
Received By wjolin Date 2012-10-11 Time 11:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-09-24 Cont ID  
Sent By wjolin Date 2012-09-24 Time 13:59 Rev Time 0.00
Received By wjolin Date 2012-09-24 Time 13:44 Sent To  
Notes
2012-09-24 13:59:061000 OLD OKEECHOBEE ROAD
 PERMIT #12090196
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS IN THE TITLE BLOCK INFORMATION IS
 INCORRECTLY INDICATED AS "1000 OLD OKEESHOBEE DR."
  
 RESTAURANTS WITH AN OCCUPANT LOAD UNDER 50 PERSONS
 SHALL BE DEEMED A MERCANTILE OCCUPANCY.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 PROVIDE AN 8? TALL STEEL BAFFLE OR PROVIDE 16? OF SPACE
 BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE
 ADJACENT EQUIPMENT.
  
 SEPERATE PLANS AND PERMITS NEEDED FOR TYPE 1 KITCHEN
 EXHAUST HOOD AND SUPPRESSION SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-14 Cont ID  
Sent By jwitmer Date 2012-10-14 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2012-10-05 Time 13:30 Sent To  
Notes
2012-10-05 13:31:28EXPEDITED
 2ND RUN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2012-10-05 Cont ID  
Sent By jwitmer Date 2012-10-05 Time 10:24 Rev Time 0.00
Received By jwitmer Date 2012-09-10 Time 09:02 Sent To  
Notes
2012-09-18 09:26:509/18/12 REQUEST FOR 'EXPEDITED REVIEW'
2012-09-14 09:02:46SENT TO B18 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-10-23 Cont ID  
Sent By shill Date 2012-10-23 Time 15:31 Rev Time 0.00
Received By shill Date 2012-10-23 Time 15:31 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-09-18 Cont ID  
Sent By jwitmer Date 2012-09-18 Time 11:28 Rev Time 0.00
Received By jwitmer Date 2012-09-18 Time 11:28 Sent To  
Notes
2012-09-18 11:28:20BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-10-01 Cont ID  
Sent By hmoser Date 2012-10-01 Time 10:08 Rev Time 0.00
Received By hmoser Date 2012-10-01 Time 09:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-09-17 Cont ID  
Sent By lwagner Date 2012-09-17 Time 12:39 Rev Time 0.00
Received By lwagner Date 2012-09-17 Time 10:45 Sent To  
Notes
2012-09-17 12:39:14FUEL GAS & GREASE INTERSEPTORS ARE NOT INCLUDED IN THIS
 REVIEW. SEPARATE APPLICATION, PLANS, REVIEW, FEES, AND
 PERMIT REQUIRED.

Review Stop Z ZONING
Rev No 2 Status P Date 2012-10-22 Cont ID  
Sent By lfranco Date 2012-10-22 Time 17:28 Rev Time 0.00
Received By lfranco Date 2012-10-22 Time 17:28 Sent To  
Notes
2012-10-22 17:31:22PLANNING: **** PASSED WITH PROVISO FROM ANGELLA VANN,
 PLANNING AND ZONING ADMINISTRATOR: A HOLD WILL BE
 PLACED ON ALL INSPECTIONS FOR THE INTERIOR SCOPE OF
 WORK FOR THIS PERMIT, UNTIL THE OWNER/CONTRACTOR
 SUBMITS FOR SEPARATE LANDSCAPE, PAVING, AND STRIPING
 PERMITS THAT COMPLY WITH THE ZONING CODE REQUIREMENTS.
 ALL COMMENTS BELOW SHALL BE ADDRESSED ACCORDINGLY.
 *****
  
  
 1. RESPOND TO COMMENTS IN WRITING. REVISE PLANS MAY
 RESULT IN ADDITIONAL COMMENTS.
  
 2. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 3. SUBMIT A SURVEY, LESS THAN ONE YEAR OLD, OF THE
 SITE. PROVIDE LOCATION OF EXISTING PARKING. BASED ON
 THE AERIAL, THERE SEEMS TO BE NO PARKING ON SITE. BASED
 ON A PREVIOUS PERMIT (09100037) THAT WAS APPLIED FOR AN
 ADDITION OF A PATIO AREA, THERE WAS PARKING THAT WAS
 EXISTING IN THE FRONT OF THE BUILDING. PROVIDE SITE
 PLAN OR ORIGINAL SITE PLAN THAT WAS APPROVED SHOWING
 WHAT PARKING SPACES WERE PROVIDED.
  
 4. IF ACCESS TO THE PROPERTY IS FROM THE ADJACENT
 PROPERTY, A RECORDED UNITY OF TITLE WILL BE REQUIRED.
 COORDINATE WITH THE PLANNING DEPARTMENT AND CITY'S
 SURVEYOR, VINCENT NOEL (ENGINEERING DEPARTMENT) FOR THE
 DOCUMENTATION REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 ANGELLA JONES-VANN, AICP
 PLANNING AND ZONING ADMINISTRATOR
 PLANNING DIVISION
 TEL: (561) 822-1441
 EMAIL: [email protected]
  
  
 PREVIOUS PERMIT NUMBER (09100037) COMMENTS FROM ERIC
 SCHNEIDER, PRINCIPAL PLANNER
 PLEASE RESPOND TO COMMENTS IN WRITING. REVISED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS.
  
 1) A SURVEY, LESS THAN ONE YEAR OLD, OF THE SITE IS
 REQUIRED.
  
 2) THE EXPANSION OF THE PATIO AREA IS REMOVING THE
 PARKING ADJACENT TO THE BUILDING. A SITE PLAN SHALL BE
 PROVIDED VERIFYING THAT THE SITE HAS SUFFICIENT PARKING
 AFTER THE PARKING REMOVAL.
  
 3) THE EXPANSION OF THE PATIO AREA APPEARS TO ENCROACH
 INTO THE DRIVE AISLES. A SITE PLAN SHALL BE PROVIDED
 VERIFYING THAT THERE IS NO REDUCTION IN THE DRIVE AISLE
 WIDTH.
  
 4) THE PERMIT APPEARS TO INCLUDE AN EXPANSION OF THE
 SEATING AREA ON THE PATIO. IF THE SEATING AREA IS BEING
 INCREASED, THEN APPLICANT SHALL PROVIDE A SITE PLAN TO
 SHOW THAT THE RESTAURANT HAS ENOUGH ADDITIONAL PARKING
 TO ACCOMMODATE THE EXPANDED SEATING AREA.
  
 5) A SEPARATE PERMIT IS REQUIRED FOR THE FENCE/RAIL.
  
 6) ARE THE PLANTER BOXES MOVABLE OR ARE THEY FIXED TO
 THE GROUND.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-10-12 Cont ID  
Sent By lfranco Date 2012-10-11 Time 09:02 Rev Time 0.00
Received By lfranco Date 2012-10-05 Time 17:19 Sent To  
Notes
2012-10-12 14:31:16PLANNING: **** FAILED *****
  
  
 1. RESPOND TO COMMENTS IN WRITING. REVISE PLANS MAY
 RESULT IN ADDITIONAL COMMENTS.
  
 2. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 3. SUBMIT A SURVEY, LESS THAN ONE YEAR OLD, OF THE
 SITE. PROVIDE LOCATION OF EXISTING PARKING. BASED ON
 THE AERIAL, THERE SEEMS TO BE NO PARKING ON SITE. BASED
 ON A PREVIOUS PERMIT (09100037) THAT WAS APPLIED FOR AN
 ADDITION OF A PATIO AREA, THERE WAS PARKING THAT WAS
 EXISTING IN THE FRONT OF THE BUILDING. PROVIDE SITE
 PLAN OR ORIGINAL SITE PLAN THAT WAS APPROVED SHOWING
 WHAT PARKING SPACES WERE PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
 PREVIOUS PERMIT NUMBER (09100037) COMMENTS FROM ERIC
 SCHNEIDER, PRINCIPAL PLANNER
 PLEASE RESPOND TO COMMENTS IN WRITING. REVISED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS.
  
 1) A SURVEY, LESS THAN ONE YEAR OLD, OF THE SITE IS
 REQUIRED.
  
 2) THE EXPANSION OF THE PATIO AREA IS REMOVING THE
 PARKING ADJACENT TO THE BUILDING. A SITE PLAN SHALL BE
 PROVIDED VERIFYING THAT THE SITE HAS SUFFICIENT PARKING
 AFTER THE PARKING REMOVAL.
  
 3) THE EXPANSION OF THE PATIO AREA APPEARS TO ENCROACH
 INTO THE DRIVE AISLES. A SITE PLAN SHALL BE PROVIDED
 VERIFYING THAT THERE IS NO REDUCTION IN THE DRIVE AISLE
 WIDTH.
  
 4) THE PERMIT APPEARS TO INCLUDE AN EXPANSION OF THE
 SEATING AREA ON THE PATIO. IF THE SEATING AREA IS BEING
 INCREASED, THEN APPLICANT SHALL PROVIDE A SITE PLAN TO
 SHOW THAT THE RESTAURANT HAS ENOUGH ADDITIONAL PARKING
 TO ACCOMMODATE THE EXPANDED SEATING AREA.
  
 5) A SEPARATE PERMIT IS REQUIRED FOR THE FENCE/RAIL.
  
 6) ARE THE PLANTER BOXES MOVABLE OR ARE THEY FIXED TO
 THE GROUND.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  