2012-10-05 16:42:08 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS. |
| CODE: FBC-2010-RESIDENTIAL. |
| |
| 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS |
| AND COPY OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY |
| COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND |
| DEVELOPMENT CODE. |
| |
| 2- ACCORDING TO CITY RECORDS THIS HOUSE WAS DESIGNED TO |
| HAVE ROOF SHINGLES. PROVIDE ENGINEERING SHOWING THAT |
| THE EXISTING HOUSE IS ADEQUATE TO RECEIVE THE |
| ADDITIONAL CONCRETE TILE LOAD. SEC. 107.2.1.3 CITY |
| AMENDMENTS TO FBC. |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) CONCRETE TILE. |
| |
| B) ROOF TILE ADHESIVE. SEE CONCRETE TILE PRODUCT |
| APPROVAL FOR LISTED ADHESIVES. |
| |
| C) ROOF UNDERLAYMENT AS SPECIFIED ON SHEET A2.2. |
| |
| D) CUSTOM ENTRY DOOR. NEED TO PROVIDE COMPLETE |
| ENGINEERING PACKAGE TO APPLY FOR LOCAL PRODUCT APPROVAL |
| BY ROBERT BROWN. CONTACT HIM AT 805-6652 FOR THE |
| INFORMATION REQUIRED TO GET THE LOCAL PRODUCT APPROVAL. |
| |
| E) GARAGE DOOR AS SHOWN BY ARCHITECT ON PLANS. |
| |
| F) FLAT ROOF. AND PROVIDE THE RAS 117 CALCULATIONS |
| REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF THE |
| NOA. SIGNED & SEALED IF REQUIRED BY THE NOA. |
| |
| G) COLONIAL SHUTTERS AS SHOWN ON PLANS. AND, PROVIDE |
| COMPLETE INSTALLATION SCHEDULE. |
| |
| H) PLASTPRO FLORIDA PRODUCT APPROVAL FL15180.1 |
| SUBMITTED FOR SINGLE OUTSWING IMPACT DOOR DOESN'T MEET |
| THE SIZE OF DOOR SHOWN ON PLANS BY THE ARCHITECT. |
| |
| I) PLASTPRO FLORIDA PRODUCT APPROVAL FL15180.4 |
| SUBMITTED FOR DOUBLE OUTSWING IMPACT DOORS DOESN'T MEET |
| THE SIZE OF DOOR SHOWN ON PLANS. AND, CLARIFY WHERE IS |
| THIS DOOR GONG TO BE INSTALLED?. SEE PLANS. |
| |
| J) PLASTPRO FLORIDA PRODUCT APPROVAL FL15180.3 |
| SUBMITTED FOR SINGLE DOOR WITH SIDELITES DOESN'T MEET |
| THE SIZE OF DOOR SHOWN ON PLANS. AND, CLARIFY WHERE IS |
| THIS DOOR GOING TO BE INSTALLED?. |
| |
| K) PLASTPRO FLORIDA PRODUCT APPROVAL FL15180.11 |
| SUBMITTED FOR SINGLE FIBERGLASS DOOR DOESN'T MEET THE |
| SIZE OF DOOR SHOWN ON PLANS. AND, CLARIFY WHERE IS THIS |
| DOOR GOING TO BE INSTALLED. |
| |
| 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC. |
| 107.3.4.1 CITY AMENDMENTS. |
| |
| 5- SHEET D1.1: NOTE ON THE NORTH WEST CORNER STATES |
| "REMOVE EXISTING STORAGE SHED ROOF ONLY - WALL AND SLAB |
| TO REMAIN". NEED TO PROVIDE MORE INFORMATION. HOW IS |
| THE ROOF GOING TO BE REBUILT. ALSO, COORDINATE WITH |
| ZONING COMMENTS. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 6- PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT THE |
| EGRESS WINDOWS "PGT 24EH" SPECIFIED ON PLANS MEET THE |
| OPENINGS REQUIREMENTS OF SEC. R310. THIS WINDOW SIZE IS |
| NOT SHOWN ON NOA 11-1013.14 SUBMITTED. |
| |
| 7- SPECIFY SIZE OF ATTIC ACCESS. ALSO, SHOW THAT ATTIC |
| ACCESS IN STORAGE ROOM BY THE FAMILY/DINING ROOM |
| PROVIDES THE REQUIRED HEIGHT REQUIRED BY SEC. R807. |
| |
| 8- PROVIDE ICYNENE MANUFACTURER SPECIFICATIONS TO |
| VERIFY COMPLIANCE WITH SEC. R316 AND INSULATION R- |
| VALUE SPECIFIED ON ENERGY CALCULATIONS. |
| |
| 9- SHEET S3.0: |
| A) DESIGN LOAD SCHEDULE: SPECIFY ALL DESIGN LOADS AS |
| REQUIRED BY SEC. R301.1 AND TABLE R301.5. INCLUDE THE |
| ATTIC LIVE LOAD AND SPECIFY STORAGE OR NON STORAGE. |
| |
| B) UPDATE FLORIDA PRODUCT APPROVAL NUMBERS SPECIFIED ON |
| THE TRUSS CONNECTOR SCHEDULE. FL1901 AND FL474 ARE NOT |
| APPROVED FOR THE 2010 FBC VERSION. |
| |
| 10- ARCHITECT TO PROVIDE IN THE TITLE BLOCK AL THE |
| INFORMATION REQUIRED BY SEC. 61G1-16.004 OF FLORIDA |
| ADMINISTRATIVE CODE. NEED FIRM'S LICENSE NUMBER AND |
| NAME OF ARCHITECT SIGNING THE PLANS. SEC. 107.1 CITY |
| AMENDMENTS. |
| |