Plan Review Details - Permit 12090138
Plan Review Stops For Permit 12090138
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-01-07 Cont ID  
Sent By jwitmer Date 2013-01-07 Time 13:50 Rev Time 0.00
Received By jwitmer Date 2013-01-07 Time 13:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-10-30 Cont ID  
Sent By jwitmer Date 2012-09-26 Time 15:57 Rev Time 0.00
Received By jwitmer Date 2012-09-26 Time 10:03 Sent To  
Notes
2012-09-26 14:35:57BUILDING PLAN REVIEW
 PERMIT: 12090138
 ADD: 444 W RAILROAD AVE 5TH FL.
 CONT: TBD
 TEL: (561)###-####
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 SEPT. 26/ 2012
 ACTION: DENIED
  
 1) SHEET LS1.1 GENERAL BUILDING DATA, BUILDING TYPE IS
 INDICATED AS A IIIB PLEASE RECLASSIFY THE BUILDING.
 THIS BUILDING WAS BUILT UNDER THE 2001 FBC-B AND WAS
 CLASSIFIED AS MINIMUM BUILDING TYPE II, UNDER THE 2010
 CODE THE BUILDING IS CLASSIFIED AS A IB SEE CODE
 CONVERSIONS 2001 TO 2004 FBC.
  
 2) SHEET LS1.1 LIFE SAFETY SHEET IS MISSING CERTAIN
 CODE CRITERIA:
 2010 FBC-B 107.3.5.1.1(6) OCCUPANCY LOAD/ EGRESS
 CAPACITY AT DOORS AND STAIRS, TABLE 1004.1.1.
  
 3) SHEET A1.1 INDICATES A WALL TYPE TAG AS A WT-5 FOR
 ALL TENANT SEPERATION WALLS THAT ARE COMMON TO ELEVATOR
 LOBBY 521 & 530. SHEET A4.2 WALL TYPES ONLY INDICATE
 WALL TAG TYPE WT-6 AS A 1 HDOORR FIRE RATED WALL. 2010
 FBC-B 709.1(6) REQUIRES A 1 HOUR FIRE RATING.
 MECHANICAL SHEETS INDICATE FIRE RATED DAMPERS IN THESE
 WALLS AS WELL.
  
 4) SHEET A1.1 FIFTH FLOOR DOORS 27 & 28 DOORS IN SERIES
 PLEASE REVIEW 2010 ACCESSIBILITY CODE SECTION 404.2.6
 DOORS IN SERIES REQUIRE 48" BETWEEN DOORS AND THERE
 SWING.
  
 5) A1.6 INDICATES A SECURE PARKING SLIDING GATE HOW
 WILL THE FIRE DEPARTMENT GAIN ENTRANCE IN CASE OF
 EMERGENCY?
  
 6) A1.7 SOUTH STAIR TOWER , NOTE DEA ANTENNAS CAN NOT
 HAVE CABLEING GOING THROUGH THE STAIR TOWER PER 2010
 FBC-B 1022.4 PENETRATIONS.
  
 7) SHEET A-3.1 BREAKROOM # 515 & 516 INDICATE THE SINK
 TO BE AT A MAXIMUM HEIGHT OF 3'-0". PLEASE REVIEW
 SECTION 2010 FBC-ACCESSIBILTY CODE 606.3.
  
 8) SHEET A-3.2 GRAB BAR DETAIL MEASURES THE HEIGHT OF
 THE GRAB BARS FROM THE FLOOR TO THE CENTER LINE OF THE
 BAR, THERE WAS A CHANGE IN THE 2010 ACCESSIBLTY CODE
 WHERE THE MEASUREMENT IS TAKEN TO THE TOP OF GRAB BARS,
 SECTION 609.4.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-01-04 Cont ID  
Sent By rlecky Date 2013-01-04 Time 16:32 Rev Time 0.00
Received By rlecky Date 2013-01-04 Time 16:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-10-01 Cont ID  
Sent By rlecky Date 2012-10-01 Time 14:51 Rev Time 0.00
Received By rlecky Date 2012-10-01 Time 14:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-01-12 Cont ID  
Sent By wjolin Date 2013-01-12 Time 15:32 Rev Time 0.00
Received By wjolin Date 2013-01-12 Time 15:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-10-12 Cont ID  
Sent By wjolin Date 2012-10-12 Time 10:58 Rev Time 0.00
Received By wjolin Date 2012-10-12 Time 08:46 Sent To  
Notes
2012-10-12 10:40:39444 WEST RAILROAD AVENUE - 5TH FLOOR
 PERMIT #12090138
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: ALL DEMOLITION AND CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED IN WRITING AND APPROVED BY
 THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH
 DIXIE HIGHWAY.
  
 GENERAL: PORTABLE FIRE EXTINGUISHERS SHALL HAVE A
 MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY A
 LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL DISTANCE TO
 EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SHEET LS1.1: EVERY DOOR ASSEMBLY IN A STAIR ENCLOSURE
 SERVING MORE THAN FOUR STORIES NEEDS TO ALLOW THE
 GENERAL PUBLIC AND EMERGENCY RESPONDERS UNRESTRICTED
 RE-ENTRY BACK ONTO TWO LEVELS. ONE OF THE RE-ENTRY
 FLOORS IS REQUIRED TO BE THE TOP STORY OR NEXT- TO-TOP
 STORY AND SUCH STORY SHALL ALLOW ACCESS TO ANOTHER
 EXIT. DOOR ASSEMBLIES ALLOWING RE-ENTRY SHALL BE
 IDENTIFIED AS SUCH ON THE STAIR SIDE OF THE DOOR LEAF
 (NFPA 101 SECTION 7.2.1.5.7).
  
 SHEET A1.6: DOOR ASSEMBLIES ALLOWING RE-ENTRY SHALL BE
 IDENTIFIED AS SUCH ON THE STAIR SIDE OF THE DOOR LEAF
 (NFPA 101 SECTION 7.2.1.5.7).
  
 SHEET A1.6: PROVIDE A KNOX KEY SWITCH TO ALLOW GATE
 ACCESS TO EMERGENCY RESPONDERS. KEY SWITCH CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 SHEET E3.1.1: PENETRATIONS INTO, AND OPENINGS THROUGH,
 AN EXIT ENCLOSURE ASSEMBLY SHALL BE LIMITED TO THE
 FOLLOWING: DOOR ASSEMBLIES, ELECTRICAL CONDUIT SERVING
 THE EXIT ENCLOSURE, REQUIRED EXIT DOOR OPENINGS,
 DUCTWORK AND EQUIPMENT NECESSARY FOR INDEPENDENT STAIR
 PRESSURIZATION, WATER OR STEAM PIPING NECESSARY FOR THE
 HEATING OR COOLING OF THE EXIT ENCLOSURE, SPRINKLER
 PIPING, STANDPIPES AND PENETRATIONS FOR FIRE ALARM
 CIRCUITS, WHERE THE CIRCUITS ARE INSTALLED IN METAL
 CONDUIT AND THE PENETRATIONS ARE PROTECTED IN
 ACCORDANCE WITH 8.3.5. (SECTION 7.1.3.2 OF NFPA 101).
 SECURITY CAMERAS AND CARD READERS ARE NOT ESSENTIAL
 FUNCTIONS SERVING THE STAIRS.
  
 SHEET FA0.1: PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM CONDITION.
  
 FIRE SPRINKLER: FOR ISSUANCE OF A GENERAL BUILDING
 PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING
 CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION
 DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE
 AUTOMATIC FIRE SPRINKLERS. NO SPRINKLER PLANS
 SUBMITTED. PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-01-31 Cont ID  
Sent By rregueir Date 2013-01-31 Time 14:28 Rev Time 0.00
Received By rregueir Date 2013-01-04 Time 08:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-01-04 Cont ID  
Sent By rregueir Date 2012-10-30 Time 08:17 Rev Time 0.00
Received By rregueir Date 2012-09-20 Time 08:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-01-31 Cont ID  
Sent By rregueir Date 2013-01-31 Time 14:28 Rev Time 0.00
Received By rregueir Date 2013-01-31 Time 14:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-01-04 Cont ID  
Sent By rregueir Date 2012-10-30 Time 08:17 Rev Time 0.00
Received By rregueir Date 2012-10-30 Time 08:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-01-14 Cont ID  
Sent By lwagner Date 2013-01-14 Time 09:41 Rev Time 0.00
Received By lwagner Date 2013-01-14 Time 08:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-10-05 Cont ID  
Sent By lwagner Date 2012-10-05 Time 14:57 Rev Time 0.00
Received By lwagner Date 2012-10-05 Time 14:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-02-20 Cont ID  
Sent By rregueir Date 2013-02-20 Time 14:39 Rev Time 0.00
Received By rregueir Date 2013-02-20 Time 14:39 Sent To  
Notes
***NONE***