Plan Review Details - Permit 12090091
Plan Review Stops For Permit 12090091 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2012-09-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2012-09-12 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2012-09-12 |
Time |
15:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2012-09-18 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-09-18 |
Time |
14:33 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-09-18 |
Time |
11:37 |
Sent To |
|
|
Notes |
2012-09-18 14:34:11 | THE FOLLOWING CODE REQUIREMENTS HAVE BEEN NOTED ON THE | | PLAN. | | | | ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | GFCI PROTECTION. NEC 422.52 | | ALL RECEPTACLES LOCATED WITH IN SIX FEET OF A SINK MUST | | BE GFCI PROTECTED. NEC 210.8 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2012-09-08 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2012-09-08 |
Time |
17:34 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2012-09-08 |
Time |
17:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-10-09 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2012-10-09 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2012-09-05 |
Time |
10:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2012-10-09 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2012-10-09 |
Time |
14:23 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2012-10-09 |
Time |
14:20 |
Sent To |
|
|
Notes |
2012-10-09 14:23:16 | PASS PROVISO | | SEPARATE PERMIT REQUIRED FOR THE HOOD | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2012-09-11 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2012-09-11 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2012-09-11 |
Time |
13:40 |
Sent To |
|
|
Notes |
2012-09-11 14:49:14 | FUEL GAS IS NOT PART OF THIS REVIEW. SEPARATE | | APPLICATION, PLAN, REVIEW, AND PERMIT FEE REQUIRED. |
|
|
|