Plan Review Details - Permit 12090015
Plan Review Stops For Permit 12090015
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-03 Cont ID  
Sent By jwitmer Date 2012-10-03 Time 12:58 Rev Time 0.00
Received By jwitmer Date 2012-10-03 Time 12:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-12 Cont ID  
Sent By jwitmer Date 2012-09-12 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2012-09-11 Time 16:39 Sent To  
Notes
2012-09-12 07:07:54BUILDING PLAN REVIEW
 PERMIT: 12090015
 ADD: 412 CLEMATIS ST.
 CONT: ANDERSON-MOORE CORP
 TEL: (561)662-1819
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 SEPT. 12/ 2012
 ACTION: DENIED
  
 1) SHEET A1 GENERAL BUILDING CODE ANALYSIS INDICATES
 THIS TO BE A CHANGE OF OCCUPANCY, PLEASE UPDATE THE
 PERMIT APPLICATION TO INDICATE A CHANGE OF OCCUPANCY,
 2010 EXISTING BLDG CODE :
 901.3.1 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY CLASSIFICATION, SECTION 912 SHALL APPLY.
  
 901.4 CERTIFICATE OF OCCUPANCY REQUIRED.
 A CERTIFICATE OF OCCUPANCY SHALL BE ISSUED WHERE A
 CHANGE OF OCCUPANCY OCCURS THAT RESULTS IN A DIFFERENT
 OCCUPANCY CLASSIFICATION AS DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2) SHEET A1 THE CURRENT CONFIGURATION OF THE EXISTING
 RESTROOMS DOES NOT MEET THE REQUIREMENTS OF THE 2010
 FLORIDA ACCESSIBILITY CODE WITH THE REQUIRED 60 INCHES
 WHERE NO OTHER FIXTURES (LAVATORY) OR OBSTRUCTIONS
 SHALL BE LOCATED WITHIN THE WATER CLOSET CLERANCES. SEE
 FIGURE 604.8.1.6.
 PLEASE REVIEW SECTION S 2010 FL ACCESSIBLITY SECTIONS
 202.4.1 DISPROPORTIONATE COST AND 202.4.2 ACCESSIBLE
 FEATURES IN THE EVENT OF DISPROPORTIONALITY.
 AN ADDITIONAL $19,000.00 WILL NEED TO BE SPENT IN
 UPGRADING TO MEET THE 2010 ACCESSIBILITY CODE.
  
 3) PLEASE UPDATE CODE SECTIONS LISTED UNDER THE HEADING
 LIFE SAFETY LEGEND WITH 2007 FBC REFERENCES. SEE 2010
 FBC-B 1018.2. CORRIDOR WIDTH.
  
 4) SHEET A-3 FRONT COUNTER DETAIL WITH SOFFIT ABOVE,
 THE DETAIL DOE NOT PROVIDE ANCHORING OF THE SOFFIT
 FRAMING TO FRAMING MEMBERS ABOVE, TYPE OF ANCHOR, SIZE
 NOR SPACING OF ANCHORS, 2010 FBC-B TABLE 2506.2 STEEL
 STUDS NON-LOAD BEARING.
  
 5) POINT OF CONSIDERATION/ UNDER SEPERATE PERMIT: 2010
 FBC-B:
  
 904.2.1 COMMERCIAL HOOD AND DUCT SYSTEMS. [F]
 EACH REQUIRED COMMERCIAL KITCHEN EXHAUST HOOD AND DUCT
 SYSTEM REQUIRED BY THE FLORIDA FIRE PREVENTION CODE OR
 CHAPTER 5 OF THE FLORIDA BUILDING CODE, MECHANICAL TO
 HAVE A TYPE I HOOD SHALL BE PROTECTED WITH AN APPROVED
 AUTOMATIC FIRE-EXTINGUISHING SYSTEM INSTALLED IN
 ACCORDANCE WITH THIS CODE.
  
 904.3.2 ACTUATION. [F]
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS SHALL BE
 AUTOMATICALLY ACTUATED AND PROVIDED WITH A MANUAL MEANS
 OF ACTUATION IN ACCORDANCE WITH SECTION 904.11.1.
  
 904.11.1 MANUAL SYSTEM OPERATION. [F]
 A MANUAL ACTUATION DEVICE SHALL BE LOCATED AT OR NEAR A
 MEANS OF EGRESS FROM THE COOKING AREA A MINIMUM OF 10
 FEET (3048 MM) AND A MAXIMUM OF 20 FEET (6096 MM) FROM
 THE KITCHEN EXHAUST SYSTEM. THE MANUAL ACTUATION DEVICE
 SHALL BE INSTALLED NOT MORE THAN 48 INCHES (1200 MM) OR
 LESS THAN 42 INCHES (1067 MM) ABOVE THE FLOOR AND SHALL
 CLEARLY IDENTIFY THE HAZARD PROTECTED. THE MANUAL
 ACTUATION SHALL REQUIRE A MAXIMUM FORCE OF 40 POUNDS
 (178 N) AND A MAXIMUM MOVEMENT OF 14 INCHES (356 MM) TO
 ACTUATE THE FIRE SUPPRESSION SYSTEM.
  
 6) SHEET M-1 A/C UNIT RACK DETAIL:
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(F)PRE-ENGINEERED A/C STANDS
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) SHEET M-2 UP-BLAST/ EXHAUST FAN DETAIL: WILL HAVE TO
 PROVIDE COMPLIANCE WITH SECTION 2010 FBC-B 1609.8
 ROOFTOP EQUIPMENT, PROVIDE DOCUMENTATION.
  
 9) SHEET M-2 ROOF CURB DETAIL DOES NOT PROVIDE
 ANCHORAGE TO THE ROOF FRAMING NOR DOES THE PLANS
 INDICATE THE TYPE OF ROOF FRAMING AND DECKING THE CURB
 WILL BE ATTACHED TOO. 2010 FBC-B 1609.8 ROOFTOP
 EQUIPMENT.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-10-01 Cont ID  
Sent By rlecky Date 2012-10-01 Time 11:11 Rev Time 0.00
Received By rlecky Date 2012-10-01 Time 11:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-09-05 Cont ID  
Sent By rlecky Date 2012-09-05 Time 16:52 Rev Time 0.00
Received By rlecky Date 2012-09-05 Time 14:39 Sent To  
Notes
2012-09-05 16:53:5412090015
 412 CLEMATIS STREET #412
 FIELD OF GREENS
  
 PROVIDE A DESIGNATED LOCATION FOR THE PANEL BOARDS
 WHICH REMAINS CLEAR OF OBSTRUCTION AND STORAGE AT ALL
 TIMES. INCLUDE A RISER PLAN SHOWING THE EXISTING
 ELECTRIC SERVICE COMPONENTS WITH MAIN DISCONNECTS. NEC
 110.26, 215.5, 240.24
  
 PROVIDE A DETAIL VERIFYING THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED FOR THE ELECTRICAL PANEL BOARDS. NEC 110.26,
 240.24, 408.17
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-10-04 Cont ID  
Sent By wjolin Date 2012-10-04 Time 10:17 Rev Time 0.00
Received By wjolin Date 2012-10-04 Time 10:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-09-08 Cont ID  
Sent By wjolin Date 2012-09-08 Time 14:40 Rev Time 0.00
Received By wjolin Date 2012-09-08 Time 14:08 Sent To  
Notes
2012-09-08 14:40:24412 CLEMATIS STREET - SUITE #412
 PERMIT #12090015
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES BOTH AN ADDRESS AND A
 SUITE NUMBER OF 412. IS THIS ACCURATE?
  
 THE PERMIT APPLICATION DOES NOT INDICATE THIS IS A
 CHANGE OF USE FROM A BUSINESS OCCUPANCY TO AN ASSEMBLY
 OCCUPANCY.
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 EVERY ASSEMBLY OCCUPANCY SHALL HAVE THE OCCUPANT LOAD
 OF THE ROOM POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN
 EXIT FROM THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE
 THE NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 INDICATE THE LOCKING/LATCHING MECHANISM FOR THE
 EXISTING EXIT DOORS.
  
 SHEET A-1: PROVIDE AN EXIT SIGN IN THE DINING AREA
 INDICATING THERE IS A SECONDARY EXIT IN THE REAR OF THE
 BUILDING.
  
 SHEET M-1: VERIFY THERE ARE EXISTING DUCT SMOKE
 DETECTOR(S) FOR THE 10-TON UNIT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-05 Cont ID  
Sent By shill Date 2012-10-05 Time 08:53 Rev Time 0.00
Received By shill Date 2012-09-26 Time 10:33 Sent To  
Notes
2012-09-28 10:40:23C13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-17 Cont ID  
Sent By rlecky Date 2012-09-17 Time 17:04 Rev Time 0.00
Received By rlecky Date 2012-09-05 Time 11:26 Sent To  
Notes
2012-09-06 17:50:039/6/12
 EXPEDITED REQUEST

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2012-10-05 Cont ID  
Sent By shill Date 2012-10-05 Time 08:53 Rev Time 0.00
Received By shill Date 2012-10-05 Time 08:53 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-09-17 Cont ID  
Sent By rlecky Date 2012-09-17 Time 17:04 Rev Time 0.00
Received By rlecky Date 2012-09-17 Time 17:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-10-03 Cont ID  
Sent By jwitmer Date 2012-10-03 Time 12:58 Rev Time 0.00
Received By jwitmer Date 2012-10-03 Time 12:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-09-13 Cont ID  
Sent By hmoser Date 2012-09-13 Time 13:48 Rev Time 0.00
Received By hmoser Date 2012-09-13 Time 13:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-10-04 Cont ID  
Sent By lwagner Date 2012-10-04 Time 15:47 Rev Time 0.00
Received By lwagner Date 2012-10-04 Time 15:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-09-11 Cont ID  
Sent By lwagner Date 2012-09-11 Time 10:08 Rev Time 0.00
Received By lwagner Date 2012-09-07 Time 12:19 Sent To  
Notes
2012-09-11 10:06:09FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET P-1 & P-2: PLEASE SHOW THAT THE MOP SINK IS
 INSTALLED ON THE GREASE SYSTEM.
 P 1003.3.1 ...GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES SHALL RECEIVE WASTE ONLY FROM FIXTURES
 AND EQUIPMENT THAT ALLOW FATS, OILS OR GREASE TO BE
 DISCHARGED.
  
 2. SHEET P-1 & P-2: A VENT WILL BE REQUIRED SOMEWHERE
 ON THE GREASE LINE. P 912.2.2
  
 3. THE EXISTING RESTROOMS DO NOT APPEAR TO MEET THE
 REQUIREMENTS OF THE 2010 ACCESSIBILITY CODE 604.3.1 &
 604.3.2 (5' SIDE CLEARANCE FOR THE WATER CLOSET WITH NO
 OTHER FIXTURES WITHIN THAT SPACE). PLEASE SEE THE CODE
 SECTIONS BELOW FOR CHANGE OF OCCUPANCY REQUIREMENTS:
  
 EXISTING BUILDING
 912.1.4 ACCESSIBILITY.
 ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 912.8.
  
 912.8 ACCESSIBILITY.
 EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 ACCESSIBILITY
 202.4 ALTERATIONS AFFECTING PRIMARY FUNCTION AREAS.
 IN ADDITION TO THE REQUIREMENTS OF 202.3, AN ALTERATION
 THAT AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS
 TO AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE
 SO AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE,
 THE PATH OF TRAVEL TO THE ALTERED AREA, INCLUDING THE
 REST ROOMS, TELEPHONES, AND DRINKING FOUNTAINS SERVING
 THE ALTERED AREA, ARE READILY ACCESSIBLE TO AND USABLE
 BY INDIVIDUALS WITH DISABILITIES, UNLESS SUCH
 ALTERATIONS ARE DISPROPORTIONATE TO THE OVERALL
 ALTERATIONS IN TERMS OF COST
  
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-09-14 Cont ID  
Sent By aaponte Date 2012-09-14 Time 15:15 Rev Time 0.00
Received By aaponte Date 2012-09-14 Time 15:15 Sent To  
Notes
***NONE***