Plan Review Details - Permit 12080975
Plan Review Stops For Permit 12080975
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-10-09 Cont ID  
Sent By wjolin Date 2012-10-09 Time 13:36 Rev Time 0.00
Received By wjolin Date 2012-10-09 Time 13:25 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-09-25 Cont ID  
Sent By wjolin Date 2012-09-25 Time 11:25 Rev Time 0.00
Received By wjolin Date 2012-09-07 Time 12:39 Sent To M
Notes
2012-09-07 12:41:14DATE: 09/07/12 WAITING FOR THE ELECTRONIC FILES IN
 PROJECTDOX TO BE AVAILABLE SO SPRINKLER SHOP DRAWINGS
 CAN BE CHECKED AGAINST ENGINEERING DRAWINGS FOR
 COMPLIANCE.
  
  
 4801 DREHER TRAIL NORTH
 PERMIT #12080975
 MASTER #12020414
 REVIEW COMMENTS - FIRE DEPARTMENT
 DATE:09/25/12
  
 THE ENGINEERING CONSTRUCTION DDOCUMENTS ALREADY
 ESTABLISH J. SMITH AS THE ENGINEER OF RECORD FOR THE
 FIRE SPRINKLER SYSTEM; THEREFORE, THE FIRE SPRINKLER
 SHOP DRAWINGS AND HYDRAULIC CALCULATIONS SHALL NOT BE
 SIGNED OR SEALED.
  
 SHEET F-001 OF THE CONSTRUCTION DOCUMENTS INDICATE THE
 PERMANENT EXHIBIT AREA AND TRAVELING EXHIBIT AREAS
 SHALL BE DESIGNED AS ORDINARY HAZARD, GROUP II WITH A
 DESIGN DENSITY OF 0.20 GPM/SQ.FT. THE SHOP DRAWINGS
 INDICATE THESE AREAS ARE LIGHT HAZARD.
  
 CONFIRM WITH THE ENGINEER OF RECORD THAT EXTENDED
 COVERAGE SPRINKLER ARE AN ACCEPTABLE ALTERNATIVE TO THE
 STANDARD SPRAY SPRINKLERS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-11 Cont ID  
Sent By hmoser Date 2012-10-11 Time 11:02 Rev Time 0.00
Received By hmoser Date 2012-10-03 Time 13:29 Sent To  
Notes
2012-10-04 13:58:40IN FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-28 Cont ID  
Sent By hmoser Date 2012-09-28 Time 10:55 Rev Time 0.00
Received By hmoser Date 2012-08-29 Time 09:38 Sent To  
Notes
2012-08-30 09:39:14IN FIRE BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-10-11 Cont ID  
Sent By hmoser Date 2012-10-11 Time 11:02 Rev Time 0.00
Received By hmoser Date 2012-10-11 Time 10:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-09-28 Cont ID  
Sent By hmoser Date 2012-09-28 Time 10:54 Rev Time 0.00
Received By hmoser Date 2012-09-28 Time 10:22 Sent To  
Notes
2012-09-28 10:53:52PLANS DENIED
 SEE NOTES FROM FIRE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732