Plan Review Stops For Permit 12080821 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2013-02-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2013-02-08 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2013-02-08 |
Time |
09:41 |
Sent To |
|
|
Notes |
2013-02-08 11:40:57 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | 1- ENERGY CALCULATIONS, ARCHITECT'S PLANS AND PRODUCT | | APPROVALS SUBMITTED NEED TO MATCH. REVISE AS REQUIRE TO | | MATCH: WALL R-VALUE, CEILING R-VALUE, WOOD EXTERIOR | | DOOR?, GRAVEL ROOF?, HOT WATER HEATER INFORMATION?(SEE | | TABLE 403.4.3.2 FBC-ENERGY CONSERVATION). | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2012-12-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2012-12-06 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2012-12-06 |
Time |
13:46 |
Sent To |
|
|
Notes |
2012-12-06 14:01:52 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING | | REVIEW COMMENTS | | CODE: 2010 FBC. | | | | 1- REVISE ENERGY CALCULATIONS SUBMITTED (SEC. 103.2 OF | | 2010 FBC-ENERGY CONSERVATION). COORDINATE ALL THE | | INFORMATION WITH PLANS AND PRODUCT APPROVALS SUBMITTED: | | (NOTE: SEE SEC. 101.4.3 OF 2010 FBC-ENERGY | | CONSERVATION. COMPLIANCE CAN BE ACHIEVED FOR THE | | ADDITION ALONE OR FOR ENTIRE BUILDING). | | | | A) COMPLETE ALL THE INFORMATION ON TOP OF FORM. | | | | B) SPECIFY ALL WALL TYPES AS SHOWN ON PLANS. THERE ARE | | NOT CONCRETE BLOCK WALLS. SEE PLANS. AND PROPERTY | | APPRAISAL SAYS WOOD FRAME STUCCO/HOLLOW TILE. | | | | C) SPECIFY ALL CEILING TYPES AS SHOWN ON PLANS. | | | | D) CLARIFY WHY THE EF VALUE FOR THE HOT WATER SYSTEM IS | | "0". | | | | E) CLEARLY PROVIDE THE NAME OF PERSON DOING THE | | CALCULATIONS AS REQUIRED BY SEC. 405.4.2 OF 2010 | | FBC-ENERGY CONSERVATION. | | | | F) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM. | | | | G) ROOF SPECIFICATION ON SHEET 2 OF 6 TO MATCH PLANS. | | THERE ARE FLAT ROOFS AND ACCORDING TO CITY RECORDS THEY | | HAVE CLAY TILE NOT FLAT CONCRETE TILE. | | | | H) REVISE THE ATTIC INFORMATION ON SHEET 2 OF 6. THERE | | ARE VENTED AND UNVENTED ATTICS. | | | | I) REVISE WALL ON SHEET 3 OF 6. THERE ARE MASONRY WALLS | | AND FRAMED WALLS. | | | | J) THERE ARE NO WOOD DOORS. SEE PLANS AND PRODUCT | | APPROVALS SUBMITTED. REVISE PAGE 3 OF 6. | | | | 2- FLAT ROOF NOA 12-0227.18 SUBMITTED. A) SELECTED | | ASSEMBLY ON PAGE 6 OF 7 IS FOR AN INSULATED ASSEMBLY. | | ARCHITECTURAL PLANS DON'T SPECIFY INSULATED ASSEMBLY. | | COORDINATE WITH ARCHITECT AND REVISE AS REQUIRED. | | (REPEAT COMMENT. ARCHITECT IS NOT SPECIFYING INSULATED | | ASSEMBLY AS SHOWN ON NOA SUBMITTED). | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR FRENCH DOORS AS SHOWN ON PLANS. | | INCLUDING FRENCH DOORS WITH SIDELITES AS SHOWN ON | | PLANS. | | ***RESPONSE: NOA 11-1025.02 SUBMITTED WAS SUPERSEDED BY | | MIAMI-DADE. VISIT MIAMI-DADE WEBSITE AND DOWNLOAD | | CURRENT NOA. RESUBMIT. | | | | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS. (REPEAT | | COMMENT). | | ***RESPONSE: ONLY THE SIMPSON STRUCTURAL CONNECTORS | | WERE APPROVED BY THE ENGINEER. ALL THE PRODUCT | | APPROVALS NEED TO BE REVIEWED AND APPROVED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2012-09-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2012-09-27 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2012-09-27 |
Time |
08:15 |
Sent To |
|
|
Notes |
2012-09-27 11:23:58 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE ENERGY CALCULATIONS. MAKE SURE ALL THE | | INFORMATION IS COMPLETED AND SIGNED BY ALL PARTIES AT | | THE BOTTOM OF THE FORM. SEC. 103.2.1 OF 2010 FBC-ENERGY | | CONSERVATION. | | | | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) | | TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED | | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY | | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT | | CODE. | | | | 3- STORM PANELS NOA 10-0222.03 SUBMITTED: PROVIDE | | COMPLETE INSTALLATION SCHEDULE TO VERIFY COMPLIANCE | | WITH THE DESIGN PRESSURES OF SEC. R301.2.1.4.3 OF 2010 | | FBC-RESIDENTIAL. CLEARLY IDENTIFY SPECIFIC SHUTTERS | | MOUNTING CONDITION AND ANCHOR TYPE AND SPACING TO BE | | USED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | ***NOTE: CLARIFY WHY SUBMITTING STORM SHUTTERS PRODUCT | | APPROVAL. ARE ALL THE WINDOWS AND DOORS IMPACT | | RESISTANT? | | | | 4- FLAT ROOF NOA 12-0227.18 SUBMITTED. A) SELECTED | | ASSEMBLY ON PAGE 6 OF 7 IS FOR AN INSULATED ASSEMBLY. | | ARCHITECTURAL PLANS DON'T SPECIFY INSULATED ASSEMBLY. | | COORDINATE WITH ARCHITECT AND REVISE AS REQUIRED. | | | | B) PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY GENERAL | | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. | | | | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR FRENCH DOORS AS SHOWN ON PLANS. | | INCLUDING FRENCH DOORS WITH SIDELITES AS SHOWN ON | | PLANS. | | | | 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS. | | | | 7- SHEET A3: PROPOSED 2ND FLOOR PLAN SHOWS NEW ATTIC | | ACCESS. IT LOOKS LIKE IT'S NOT READILY ACCESSIBLE AS | | REQUIRED BY SEC. R807. REVISE AS REQUIRED AND PROVIDE | | DIMENSIONS. | | ***NOTE: THERE IS A NOTE THAT THE AHU IS LOCATED HERE. | | VERIFY THAT AIR HANDLER UNIT WILL BE OK IN THIS | | LOCATION. CHECK ACCESS AND REQUIRED CLEARANCES TO | | SERVICE THE EQUIPMENT. | | | | 8- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4. | | | | 9- PROVIDE COMPLETE SPECIFICATIONS FOR THE ICYNENE | | INSULATION SPECIFIED ON PLANS. SEC. 107.2.1 CITY | | AMENDMENTS. | | | | 10- A) ENGINEER TO REVISE ALL THE ROOF SHEATHING | | DETAILS AND SPECIFICATIONS. NEED TO SPECIFY MIN. 8D | | RING SHANK NAILS (NOT 10D) AS REQUIRED BY SEC. | | R803.2.3.1 AND ALSO NEED TO SPECIFY NAILS AT 4"O.C. IN | | ROOF ZONE #3. | | | | B) ARCHITECT TO REVISE ROOF SHEATHING NAILING | | SPECIFICATIONS SHOWN ON ALL THE WALL SECTIONS AND | | DETAILS TO MATCH REVISED ENGINEER SPECIFICATIONS. | | COORDINATE WITH ITEM 10(A) ABOVE. SEC. 107.2.1 CITY | | AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2012-08-27 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-08-27 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-08-27 |
Time |
14:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2013-02-11 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-02-11 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-02-01 |
Time |
17:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2012-12-14 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2012-12-14 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2012-12-06 |
Time |
11:49 |
Sent To |
|
|
Notes |
2012-12-07 11:50:45 | RESUBMITTAL PUT INTO PACKAGE | | R--26 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2012-12-14 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2012-12-14 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2012-11-20 |
Time |
16:44 |
Sent To |
|
|
Notes |
2012-11-20 16:44:32 | INCOMING SENT TO R-26 BOX. JW |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-09-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2012-09-27 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2012-08-23 |
Time |
18:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2012-12-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2012-12-06 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2012-12-06 |
Time |
13:58 |
Sent To |
|
|
Notes |
2012-12-06 13:59:48 | NO FEES DUE. MU-2012-21338 DATED NOVEMBER 19, 2012. JG. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2012-09-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2012-09-27 |
Time |
08:38 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2012-09-27 |
Time |
08:37 |
Sent To |
|
|
Notes |
2012-09-27 08:39:13 | BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT | | FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID | | RECEIPT IF FEES ARE DUE. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2013-02-11 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2013-02-11 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2013-02-11 |
Time |
10:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2012-12-14 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2012-12-14 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2012-12-14 |
Time |
13:35 |
Sent To |
|
|
Notes |
2012-12-14 13:53:43 | *** CORRECTIONS NEEDED TO MECHANICAL *** | | | | 1) SEE BUILDING REVIEW NOTE #1 REGARDING ENERGY CAL'S. | | PLEASE CORRECT REGARDING SIGNED & DATED BY OWNER/AGENT, | | SEE LINE 14 E-CAL'S. WATER HEATER AND YELLOW HIGH | | LIGHTS ON SUBMITTED ENERGY CAL'S. PLEASE CORRECT, PER | | 2010 FBC/ENERGY 103.2.3.2 & 103.33 | | | | 2) MECHANICAL PERMIT # 12080823 WAS APPLIED FOR AND | | COOLING LOAD CAL'S. WITH DUCT CALCULATIONS WAS | | SUBMITTED, BUT NO MECHANICAL PLAN WAS SUBMITTED. PLEASE | | SUBMIT MECHANICAL PLANS WITH ALL PERTINENT INFORMATION | | ON THEM, PER 2010 WPB AMEND. 107.3.5.3 (10). | | | | *** MECHANICAL PLAN REVIEW BY: TOM GORDON (HY-BYRD | | INC.) | | *** FOR ASSISTANCE CALL LUIS MARTINEZ (561) 805-6710 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2012-09-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2012-09-27 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2012-09-27 |
Time |
15:50 |
Sent To |
|
|
Notes |
2012-09-27 15:54:13 | RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- NO INFORMATION SUBMITTED. NEED COMPLETE PLANS WITH | | SPECIFIC EQUIPMENT AND EQUIPMENT SIZING CALCULATIONS. | | SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2012-12-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2012-12-06 |
Time |
17:03 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2012-12-06 |
Time |
17:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2012-09-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2012-09-27 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2012-09-27 |
Time |
10:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2013-02-07 |
|
|
Cont ID |
|
Sent By |
mdekle |
Date |
2013-02-07 |
Time |
|
Rev Time |
0.00 |
Received By |
mdekle |
Date |
2013-02-07 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2012-11-29 |
|
|
Cont ID |
|
Sent By |
mdekle |
Date |
2012-11-29 |
Time |
|
Rev Time |
0.00 |
Received By |
mdekle |
Date |
2012-11-29 |
Time |
|
Sent To |
|
|
Notes |
2012-11-29 15:26:36 | REPEAT COMMENT: I DID NOT FIND A SURVEY WITH THE | | SUBMITTAL. IN ORDER TO DETERMINE COMPLIANCE WITH ZONING | | CODE BUILDING SETBACKS, PLEASE SUBMIT A SIGNED AND | | SEALED SURVEY DEPICTING THE PROPOSED IMPROVEMENTS | | RELATED TO THE PROPERTY LINES. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2012-09-14 |
|
|
Cont ID |
|
Sent By |
mdekle |
Date |
2012-09-14 |
Time |
16:25 |
Rev Time |
|
Received By |
mdekle |
Date |
2012-09-14 |
Time |
|
Sent To |
|
|
Notes |
2012-09-14 16:25:40 | SUBMITTAL IS INCOMPLETE. I DID NOT FIND A LANDSCAPE | | PLAN OR A SURVEY WITHIN THE PACKET. PLEASE RESUBMIT. |
|
|