Plan Review Details - Permit 12080740
Plan Review Stops For Permit 12080740
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-15 Cont ID  
Sent By rmcdouga Date 2012-10-15 Time 13:14 Rev Time 0.00
Received By rmcdouga Date 2012-10-15 Time 13:14 Sent To  
Notes
2012-10-15 13:31:58REVISION REQUIRED
  
 1) SPECIFY WHICH ONE OF THE ASSEMBLIES FROM THE
 HYDRO-STOP PREMIUM COAT SYSTEM PRODUCT APPROVAL THAT
 WAS SUBMITTED WILL BE INSTALLED. ALL THREE OF THE
 ASSEMBLIES REQUIRE A MECHANICALLY FASTENED INSULATION
 BASE LAYER TO WHICH THE PREMIUM COAT SYSTEM IS APPLIED.
 THE MAXIMUM DESIGN PRESSURE LISTED IN THE NOA IS -60
 PSF WHICH DOES NOT MEET THE HIGHER UPLIFT PRESSURES AT
 THE PERIMETER AND CORNER AREAS. THE STRUCTURE IS
 LOCATED IN 170 MPH VULT / 132 VASD EXPOSURE C PER FBC
 R301.2.1.4. PLEASE SUBMIT 2 SETS OF RAS 117
 CALCULATIONS FOR THE ENHANCED FASTENING OF THE
 INSULATION THAT HAVE BEEN SIGNED AND SEALED BY A
 FLORIDA ENGINEER, ARCHITECT OR REGISTERED ROOF
 CONSULTANT AS REQUIRED BY LIMITATION NUMBER 7.
 FBCR301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-10-04 Cont ID  
Sent By rmcdouga Date 2012-10-04 Time 08:24 Rev Time 0.00
Received By rmcdouga Date 2012-10-03 Time 16:51 Sent To  
Notes
2012-10-03 16:52:492010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 DIMENSIONAL ROOF SHINGLES AND LIQUID APPLIED ROOFING
 SYSTEM AS REQUIRED BY DCA RULE 9N-3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-10-05 Cont ID  
Sent By rlecky Date 2012-10-05 Time 11:54 Rev Time 0.00
Received By rlecky Date 2012-10-05 Time 11:35 Sent To  
Notes
2012-10-05 11:55:01SEE NOTES ON PLAN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-08-27 Cont ID  
Sent By rlecky Date 2012-08-27 Time 14:32 Rev Time 0.00
Received By rlecky Date 2012-08-27 Time 14:22 Sent To  
Notes
2012-08-27 14:32:5712080740
 309 DIVISION AVE
 RESIDENTIAL RENOVATION
  
 PROVIDE AN ELECTRIC SERVICE RISER PLAN WITH WIRE SIZES,
 GROUNDING ETC. NEC 215.15
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. 2010 FBC R314,
 315
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS. NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-10-03 Cont ID  
Sent By fmittner Date 2012-10-03 Time 11:16 Rev Time 0.00
Received By fmittner Date 2012-10-03 Time 11:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-10-15 Cont ID  
Sent By rmcdouga Date 2012-10-15 Time 16:06 Rev Time 0.00
Received By rmcdouga Date 2012-10-11 Time 14:17 Sent To  
Notes
2012-10-11 14:17:52TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-10-05 Cont ID  
Sent By rlecky Date 2012-10-05 Time 12:02 Rev Time 0.00
Received By rlecky Date 2012-10-03 Time 14:37 Sent To  
Notes
2012-10-04 15:03:07GAVE TO LECKY
 ELECTRIC SUBMITTAL
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-10-04 Cont ID  
Sent By rmcdouga Date 2012-10-04 Time 08:25 Rev Time 0.00
Received By rmcdouga Date 2012-09-05 Time 13:46 Sent To  
Notes
2012-09-05 13:47:47SENT TO R11- SINGLE FAMILY RESIDENTIAL. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-05 Cont ID  
Sent By jwitmer Date 2012-09-05 Time 13:46 Rev Time 0.00
Received By jwitmer Date 2012-09-05 Time 13:46 Sent To  
Notes
2012-08-23 09:39:53B11

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-10-15 Cont ID  
Sent By rmcdouga Date 2012-10-15 Time 16:06 Rev Time 0.00
Received By rmcdouga Date 2012-10-15 Time 16:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-10-03 Cont ID  
Sent By rmcdouga Date 2012-10-03 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2012-10-03 Time 16:51 Sent To  
Notes
2012-10-03 16:51:442010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF EQUIPMENT SIZING CALCULATIONS AS
 REQUIRED BY FBCR M1401.3
  
 2) SUBMIT TWO SETS OF MECHANICAL PLANS WITH THE
 LOCATIONS AND SIZES OF ALL SUPPLY AND RETURN DUCTS
 SPECIFIED. SPECIFY THE GRILL SIZES FOR THE SUPPLIES AND
 RETURNS AND THE CFMS FOR EACH OF THE SUPPLY OUTLETS.
 CITY AMENDMENTS 107.3.5.3
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT IS
 COORDINATED WITH THE SIZING CALCULATIONS. FBCR M1401.3
  
 4) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED
 RETURN AIR REQUIREMENTS ON THE PLANS.
  
 5) SHOW THE LOCATION OF ALL HVAC EQUIPMENT ON THE
 PLANS. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2012-08-24 Cont ID  
Sent By lwagner Date 2012-08-24 Time 14:29 Rev Time 0.00
Received By lwagner Date 2012-08-24 Time 14:24 Sent To  
Notes
2012-08-24 14:29:53NO PLUMBING AT THIS TIME.