Plan Review Details - Permit 12080493
Plan Review Stops For Permit 12080493
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-10-30 Cont ID  
Sent By jwitmer Date 2012-10-30 Time 15:30 Rev Time 0.00
Received By jwitmer Date 2012-10-30 Time 15:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-04 Cont ID  
Sent By jwitmer Date 2012-09-04 Time 09:51 Rev Time 0.00
Received By jwitmer Date 2012-08-30 Time 16:38 Sent To  
Notes
2012-09-04 09:50:51BUILDING PLAN REVIEW
 PERMIT: 12080493
 ADD: 255 WALTON
 CONT: ANCHOR GENERAL CONTRACTING
 TEL: (561)386-1266
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) DISCREPANCY BETWEEN THE DESCRIPTION OF WORK INCLUDED
 WITH IN THE PLANS, SECTIONS SCRATCHED OUT IN PEN ON THE
 PLANS AND THE WRITTEN PERMIT APPLICATION UNDER THE
 HEADING WORK DESCPRIPTION. PLEASE CORRELATE ALL THE
 WORK TO BE COVERED UNDER THIS PERMIT. 2010 FBC-B
 ADMINISTRATIVE SECTION 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 2) NEITHER THE A-1 OR E-1 INDICATE COMPLIANCE WITH 2010
 FBC-B 916.1.1, CARBON MONOXIDE ALARMS, 916.1.2
 COMBINATION ALARMS OR 907.2.11.2.SMOKE ALARMS IN R-2
 RESIDENCIES.
  
 3) PLEASE NOTE THAT ROOM NUMBER 3 & 5 DO NOT MEET THE
 ROOM SIZE REQUIREMENTS FOR AN EFFICIENCY DWELLING UNIT.
 2010 FBC-B 1208.4 EFFICIENCY DWELLING UNITS.
 AN EFFICIENCY LIVING UNIT SHALL CONFORM TO THE
 REQUIREMENTS OF THE CODE EXCEPT AS MODIFIED HEREIN:
  
 1. THE UNIT SHALL HAVE A LIVING ROOM OF NOT LESS THAN
 220 SQUARE FEET (20.4 M2) OF FLOOR AREA. AN ADDITIONAL
 100 SQUARE FEET (9.3 M2) OF FLOOR AREA SHALL BE
 PROVIDED FOR EACH OCCUPANT OF SUCH UNIT IN EXCESS OF
 TWO.
 2. THE UNIT SHALL BE PROVIDED WITH A SEPARATE CLOSET.
 3. THE UNIT SHALL BE PROVIDED WITH A KITCHEN SINK,
 COOKING APPLIANCE AND REFRIGERATION FACILITIES, EACH
 HAVING A CLEAR WORKING SPACE OF NOT LESS THAN 30 INCHES
 (762 MM) IN FRONT. LIGHT AND VENTILATION CONFORMING TO
 THIS CODE SHALL BE PROVIDED.
 4. THE UNIT SHALL BE PROVIDED WITH A SEPARATE BATHROOM
 CONTAINING A WATER CLOSET, LAVATORY AND BATHTUB OR
 SHOWER.
  
 WEST PALM BEACH MUNICIPLE CODE SEC. 18-109. - CONFLICT
 WITH OTHER CODES.
  
 IN ANY CASE WHERE A PROVISION OF ANY ZONING, BUILDING,
 ELECTRICAL, PLUMBING, HEALTH, FIRE, OR SAFETY CODE OF
 THE CITY IS IN CONFLICT, THE PROVISION WHICH
 ESTABLISHES THE HIGHER STANDARD FOR THE PROMOTION AND
 PROTECTION OF THE PUBLIC HEALTH AND SAFETY SHALL
 PREVAIL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-11-07 Cont ID  
Sent By rlecky Date 2012-11-07 Time 13:54 Rev Time 0.00
Received By rlecky Date 2012-11-07 Time 13:12 Sent To  
Notes
2012-11-07 13:59:5512080493
 255 WALTON BLVD.
 MULTIFAMILY RENOVATION
  
 THE FOLLOWING NEC CODE REQUIREMENTS WERE NOTED ON THE
 PLAN.
  
 MINIMUM WIRE SIZE FOR 100 AMP FEEDER IS # 3 COPPER. NEC
 T. 310.16
 MINIMUM WIRE SIZE FOR 400 AMP SERVICE IS 500 KCMIL
 COPPER. NEC T 310.16
 BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH CIRCUIT.
 NEC 210.11 (C) (3)
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-08-20 Cont ID  
Sent By rlecky Date 2012-08-20 Time 09:21 Rev Time 0.00
Received By rlecky Date 2012-08-20 Time 08:45 Sent To  
Notes
2012-08-20 09:21:3912080493
 255 WALTON BLVD.
 APARTMENT RENOVATION
  
 THE PLANS ARE UNCLEAR AS TO THE SCOPE OF THE ELECTRICAL
 WORK. PLEASE PROVIDE THE FOLLOWING INFORMATION:
  
 IDENTIFY ON THE PLAN WHAT PORTION OF THE ELECTRICAL
 SYSTEM WILL BE UNDER GOING RENOVATION AND WHAT PORTION
 WILL REMAIN AS EXISTING. NEC 215.5
  
 REMODELING OF AN EXISTING STRUCTURE WITH SLEEPING AREAS
 IS REQUIRED TO INCLUDE INTERCONNECTED SMOKE DETECTORS.
 IF THE STRUCTURE HAS GAS APPLIANCES, AN ATTACHED GARAGE
 OR A FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. 2010
 FBC R314, 315, 210 FBC 916.1, FBC EXISTING BUILDING
 704.4.3
  
  
 ROBERT LECKY
 PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-10-25 Cont ID  
Sent By wjolin Date 2012-10-25 Time 11:30 Rev Time 0.00
Received By wjolin Date 2012-10-25 Time 11:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-08-26 Cont ID  
Sent By wjolin Date 2012-08-26 Time 15:05 Rev Time 0.00
Received By wjolin Date 2012-08-26 Time 14:20 Sent To  
Notes
2012-08-26 15:05:14REFER TO ELECTRICAL REVIEW COMMENTS FOR SMOKE/CARBON
 MONOXIDE DETECTION.

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2012-11-15 Cont ID  
Sent By lwagner Date 2012-11-15 Time 12:57 Rev Time 0.00
Received By lwagner Date 2012-11-15 Time 12:57 Sent To  
Notes
2012-11-15 12:58:12SEE SEPARATE GAS PERMIT

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2012-08-23 Cont ID  
Sent By lwagner Date 2012-08-23 Time 14:48 Rev Time 0.00
Received By lwagner Date 2012-08-23 Time 14:48 Sent To  
Notes
2012-08-23 14:49:01FBC FUEL GAS 2010
 DENIED:
  
 NO PLAN WAS SUBMITTED WITH APPLICATION.
 PLEASE INCLUDE WITH PLAN THE FOLLOWING:
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2007 FUEL GAS.
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL).
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2007 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2007
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2012-10-02 Cont ID  
Sent By fmittner Date 2012-10-02 Time 14:27 Rev Time 0.00
Received By fmittner Date 2012-10-02 Time 14:27 Sent To  
Notes
2012-10-02 14:27:46GIVEN TO MURRIAH FOR ZONING REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-15 Cont ID  
Sent By rlecky Date 2012-11-15 Time 11:16 Rev Time 0.00
Received By rlecky Date 2012-10-18 Time 17:35 Sent To  
Notes
2012-10-22 17:35:58B--6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-10-22 Cont ID  
Sent By lmartine Date 2012-10-02 Time 17:34 Rev Time 0.00
Received By lmartine Date 2012-08-16 Time 09:32 Sent To  
Notes
2012-08-16 09:49:12B06

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-08-20 Cont ID  
Sent By lwagner Date 2012-08-20 Time 15:25 Rev Time 0.00
Received By lwagner Date 2012-08-20 Time 14:43 Sent To  
Notes
2012-08-20 14:55:59 
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-10-02 Cont ID  
Sent By fmitter Date 2012-10-02 Time   Rev Time 0.00
Received By mdekle Date 2012-10-02 Time   Sent To  
Notes
***NONE***