Plan Review Details - Permit 12080469
Plan Review Stops For Permit 12080469
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-03-13 Cont ID  
Sent By jwitmer Date 2013-03-13 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2013-03-13 Time 13:51 Sent To  
Notes
2013-03-13 14:53:26BUILDING PROVISO:
 SUBMITTED PRODUCT APPROVALS:
  
 1) STOREFRONT DOORS KAWNEER NOA 11-1013.03
 2) CURTAINWALL KAWNEER NOA 12-0622.07
 3) WALL LOUVER GREENHECK NOA 11-1103.01
 4) ROOFING FIRESTONE NOA 09-0902.10
 PAGE 6 OF 40 SINGLE PLY TPO LIMITATION # 9
 MIN PRESSURE: - 150
 MAX PRESSURE - 285
  
 5) SKYBRIDGE TO BE A SEPARATE PERMIT/ REVISION WITH
 SEPARATE REVIEWS
 SHEETS TO BE REMOVED FROM THIS SET
 710-SS-103
 710-A1-400
 710-A3-400
 710-A3-401
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-12-11 Cont ID  
Sent By jwitmer Date 2012-12-11 Time 09:00 Rev Time 0.00
Received By jwitmer Date 2012-12-11 Time 08:38 Sent To  
Notes
2012-12-11 11:22:14BUILDING PLAN REVIEW
 PERMIT: 112080469
 ADD: 6751 N JOG ROAD
 CONT: CDM CONSTRUCTORS
 TEL: (561)689-3336
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DEC. 11/2012
 ACTION: DENIED
  
 1)2ND REQUEST, SHEET710- A1-300 THIRD STORY ROOF TOP
 GARDEN AREA, TO DATE THE PLANS ONLY SHOW ONE MEANS OF
 EGRASS FROM THE 3RD STORY ROOFTOP GARDEN, PLEASE REVIEW
 SECTION 2010 FBC-B TABLE 1021.2 FOR ASSEMBLY
 OCCUPANCIES AND SINGLE EXIT. TRUE THERE IS AN ATTACHED
 SKYBRIDGE, THAT TO DATE ONLY HAS BEEN REVIEWED FOR THE
 PILING AND PILE CAP. THE SUBMITTED PLANS FOR THE
 SKYBRIDGE ARE MORE OF CONCEPT DRAWINGS.
 PLEASE PROVIDE THE LENGTH OF THE SKYBRIDGE FROM WHERE
 IT ATTACHES TO THE VISITORS CENTER OPEN VERTICAL STAIRS
 AND THE TOTAL OVERALL LENGTH OF THE SKYBRIDGE WHERE IT
 AJOINS TO THE POWER BLOCK BUILDING.. THE PLANS
 SUBMIITED FOR THE SKYBRIDGE DO NOT STATE THEY ARE FIRE
 SPRINKLERED, THE 2010 FBC-B 3104.9 LIMIT THE LENGTH TO
 200 FEEET OF EXIT ACCESS TRAVEL, EXCEPTION FOR FIRE
 SPRINKLERS IS 250 FT.
  
 2) 2ND REQUEST, THIS SAME SHEET A1-300 INDICATES A
 SKYBRIDEGE TO THE POWER BLOCK, SHEET 710-SS-103 ALSO
 MAKES REFERENECE TO THE SKYBRIDGE AND A NOTE
 INDICATEING SEE SHEET 710-S3-301 FOR WIND LOADING ON
 SKYBRIDGE AND SKYBRIDGE STAIR TOWER. THIS SHEET IS NOT
 INCLUDED IN THIS SUBMITION, AT THIS TIME WE CAN ONLY
 VIEW THIS AREA AS A SINGLE EXIT FROM THE THIRD FLOOR.
 UNTIL THE SKYBRIDGE IS REVIEWED BY BOTH THE BUILDING
 DEPARTMENT AND FIRE DEPARTMENT FOR CODE COMPLIANCE AND
 PASS THE SKYBRIDGE THE THIRD FLOOR ONLY HAS A SINGLE
 EXIT. THERE ARE GOING TO BE AREAS OF QUESTION TO CODE
 COMPLIANCE WITH THE OPENESS OF THE SKYBRIDGE AND BEING
 WITHIN TEN FEET OF THE POWER BLOCK BUILDING. AGAIN THE
 DESIN TEAM IS INDICATING THE POWER BLOCK BUILDING BEING
 A TYPE II-B BUILDING EXTERIOR WALLS NOT RATED AND THE
 SKYBRIDGE BEING WITHIN 10'-0" PARALLELING THIS
 BUILDING. 2010 FBC-B 3104.5 NEEDS TO BE ADDRESSED.
  
 3) 2ND REQUEST. SHEET 710-A1-300 INDICATES THE USE OF A
 SKYBRIDGE TO THE POWER BLOCK, PLESE REVIEW 2010 FBC-B
 3104.2 SEPERATE STRUCTURES, 3104.3 CONSTRUCTION, 3104.4
 CONTENTS & 3104.5 FIRE BARRIERS BETWEEN PEDESTRIAN
 WALKWAYS AND BUILDINGS. THE RESPONSE STATEMENT IS
 REFERENECING 3104.5 EXCEPTION# 2 WHICH I AGREE YOU CAN
 TAKE FOR THE ELEVATED WALKWAY.
 THE 2007 FBC-B CODE COMMENTARY STATES, THESE FOUR
 EXCEPTIONS APPLY TO THE WALKWAY RATHER THAN THE
 BUILDING THAT THE WALKWAY CONNECTS. SINCE THIS IS THE
 SECOND MEANS OF EGRESS FOR THE THIRD FLOOR IT IS
 NECCESSARY TO PROTECT THE GLAZED AREA ADJACENT TO THE
 WALKWAY WITH 3/4 HR OPENING PROTECTIVES AND AT THE
 FLOOR LEVEL
 AND TEN FOOT OUT AND TEN FOOT DOWN 2 HOUR PROTECTION
 FOR FIRE BARRIER PLEASE REVIEW 2007 FBC-B CODE
 COMMENTARY FIGURE 3104.5.
  
  
  
  
 4) 2ND REVIEW, SHEET 710-A1-307 & 710-HC-104, THE EAST
 STAIR TOWER HAS TWO ISSUES:
 4A) THE MECHANICAL ROOM IS NOT SEPERATED FROM THE
 VERTICAL EXIT ENCLOSURE BY A ONE HOUR RATED WALL PER
 2010 FBC-B 1022.1. THERE IS NO CEILING IN THE
 MECHANICAL ROOM SEPERATING THE MECHANICAL ROOM FROM THE
 STAIRWELL.
  
 4B) COMPLIED.
  
 4C) NEW COMMENT: SHEET 710-HC-104 WITH THE MECHANICAL
 ROOM NOT HAVING WALLS THAT GO TO THE DECK ABOVE THE
 INTAKE DUCT WORK AS WELL AS THE MECHANICAL ROOM
 EQUIPMENT ARE STILL LOCATED IN THE STAIRWELL. IF THE
 PLANS DID HAVE A RATED CEILING INTHE MECHANICAL ROOM,
 AS IT APPEARS THE DESIGNER IS TRYING BECAUSE OF THE
 FIRE DAMPER SHOWN PLEASE REVIEW 2010 FBC-B 1022.4
 PENETRATIONS, THE FRESH AIR DUCT CAN NOT BE WITHIN THE
 STAIRWWELL, IT DOES NOT SERVE THE STAIRWELL.
  
 5) 2ND REQUEST MAY OR MAY NOT BE A ISSUE DEPENDING ON
 THE REDESIGN. SHEET 710-A1-303 IS MISSING FIRE DAMPER,
 PLEASE REVIEW 2010 FBC-B 1022.4. 1022.5 EXIT ENCLOSURE
 VENTILATION SYSTEMS SHALL BE INDEPENDENT OF OTHER
 BUILDING VENTILATION SYSTEMS.
  
 6) 2ND REQUEST. EAST STAIR TOWER SHEET 710-A1-203
 PLEASE PROVIDE ADDITIONAL INFORMATION REQUIRED FOR
 SUSPENDED ACCENT CANOPY, 2010 FBC-B TABLE 803.9
 INTERIOR WALL & CEILING FINISHES.
  
 7)COMPLIED.
  
 8) SEMI-COMPLIED 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) PRODUCT APPROVALS WERE SUBMITTED AT THIS TIME.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. CIRCLE TYPE OF GLAZING ,SIZE OF
 DOORS AND ASSOCIATED PRESSUES
 (B) WINDOWS CIRCLE TYPES OF GLAZING, SIZE OF GLASS,
 TYPE OF MULLIONS, TYPES OF CONNECTIONS USED AND
 PRESSURES
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, CIRCLE TYPES OF GLAZING, SIZE OF
 GLASS, TYPE OF MULLIONS, TYPES OF CONNECTIONS USED AND
 PRESSURES
 (D) ROOFING PRODUCTS AND ASSEMBLIES CIRCLE WHICH
 SUBSYSTEM TO BE INSTALLED VARIUOS PRESSURES INDICATED
  
 10) NEW COMMENT) PLEASE SEE DESCREPANCY BETWEEN THE
 ARCHITECTURAL SHEET710-A1-300 AND MECHANICAL SHEET
 710-HC-103, THE MECHANICAL SHEET HAS THE THIRD FLOOR
 STAIR RUNNING DIRECTLY INTO THE MECHANICAL ROOM. PLEASE
 REVISE.
  
 11) NEW COMMENT. IN THE FOLDER WE FIND VARIOUS SPECS,
 PLEASE REMOVE THE SPECS, THE PERMIT WILL NOT BE ISSUED
 SINCE THEY END UP BEING BATCHED STAMPED. WE DO NOT
 REVIEW SPECIFICATIONS!!!!!! PLEASE SEPERATE THE REVIEW
 COMMENTS INTO A SEPERATE FOLDER FROM THE PRODUCT
 APPROVALS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-11 Cont ID  
Sent By jwitmer Date 2012-09-11 Time 14:02 Rev Time 0.00
Received By jwitmer Date 2012-08-27 Time 10:20 Sent To  
Notes
2012-09-11 15:32:51BUILDING PLAN REVIEW
 PERMIT: 112080469
 ADD: 6751 N JOG ROAD
 CONT: CDM CONSTRUCTORS
 TEL: (561)689-3336
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 SEPT. 11/2012
 ACTION: DENIED
  
 1) SHEET710- A1-300 THIRD STORY ROOF TOP GARDEN AREA,
 TO DATE THE PLANS ONLY SHOW ONE MEANS OF EGRASS FROM
 THE 3RD STORY ROOFTOP GARDEN, PLEASE REVIEW SECTION
 2010 FBC-B TABLE 1021.2 FOR ASSEMBLY OCCUPANCIES AND
 SINGLE EXIT.
  
 2) THIS SAME SHEET A1-300 INDICATES A SKYBRIDEGE TO THE
 POWER BLOCK, SHEET 710-SS-103 ALSO MKES REFERENECE TO
 THE SKYBRIDGE AND A NOTE INDICATEING SEE SHEET
 710-S3-301 FOR WIND LOADING ON SKYBRIDGE AND SKYBRIDGE
 STAIR TOWER. THIS SHEET IS NOT INCLUDED IN THIS
 SUBMITION, AT THIS TIME WE CAN ONLY VIEW THIS AREA AS A
 SINGLE EXIT FROM THE THIRD FLOOR.
  
 3) SHEET 710-A1-300 INDICATES THE USE OF A SKYBRIDGE TO
 THE POWER BLOCK, PLESE REVIEW 2010 FBC-B 3104.2
 SEPERATE STRUCTURES, 3104.3 CONSTRUCTION, 3104.4
 CONTENTS & 3104.5 FIRE BARRIERS BETWEEN PEDESTRIAN
 WALKWAYS AND BUILDINGS.
  
 4) SHEET 710-A1-300 THE EAST STAIR TOWER HAS TWO
 ISSUES:
 4A) THE MECHANICAL ROOM IS NOT SEPERATED FROM THE
 VERTICAL EXIT ENCLOSURE BY A ONE HOUR RATED WALL PER
 2010 FBC-B 1022.1.
  
 4B) THE VERTICAL EXIT ALSO HAS A/C DUCTWORK WITHIN THE
 EXIT ENCLOSURE THAT IS COMMON TO THE THIRD FLOOR.
 PLEASE REVIEW 2010 FBC-B 1022.4. 1022.5 EXIT ENCLOSURE
 VENTILATION SYSTEMS SHALL BE INDEPENDENT OF OTHER
 BUILDING VENTILATION SYSTEMS.
  
 5) SHEET 710-A1-303 IS MISSING FIRE DAMPER, PLEASE
 REVIEW 2010 FBC-B 1022.4. 1022.5 EXIT ENCLOSURE
 VENTILATION SYSTEMS SHALL BE INDEPENDENT OF OTHER
 BUILDING VENTILATION SYSTEMS.
  
 6) EAST STAIR TOWER SHEET 710-A1-203 PLEASE PROVIDE
 ADDITIONAL INFORMATION REQUIRED FOR SUSPENDED ACCENT
 CANOPY, 2010 FBC-B TABLE 803.9 INTERIOR WALL & CEILING
 FINISHES.
  
 7) PLEASE REVIEW BUILDING PROJECT SUMMARY OCCUPANT
 LOADS FOR THE SECOND FLOOR INDICATE A OCCUPANT LOAD OF
 25, WHEREAS THE CONFERENCE ROOM IS 533/ 15=37
 AND TRAIN/ WORK ROOM 1134/50= 23 OCCUPANTS OR A TOTAL
 LOAD OF 59.TABLE 1004.1.1.
  
 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) NO PRODUCT APPROVALS WERE SUBMITTED AT THIS TIME.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-03-08 Cont ID  
Sent By rlecky Date 2013-03-08 Time 15:27 Rev Time 0.00
Received By rlecky Date 2013-03-08 Time 15:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-09-05 Cont ID  
Sent By rlecky Date 2012-09-05 Time 13:23 Rev Time 0.00
Received By rlecky Date 2012-08-29 Time 09:20 Sent To  
Notes
2012-09-05 13:24:10THE FOLLOWING NOTES HAVE BEEN APPLIED TO THE ELECTRONIC
 PLAN.
  
 SEPARATE PERMITS ARE REQUIRED FOR THE PHOTOVOLTAIC
 SYSTEM AND SITE LIGHTING. FBC 105.1
 ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GFCI PROTECTION. NEC 422.52
 RECEPTACLES IN ELEVATOR MACHINE ROOMS SHALL HAVE GROUND
 FAULT CIRCUIT INTERRUPTER PROTECTION. NEC 620.85
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2012-10-05 Cont ID  
Sent By mgonzale Date 2012-10-05 Time   Rev Time 0.25
Received By mgonzale Date 2012-10-05 Time   Sent To I
Notes
2012-10-05 12:15:06NO CONFLICTS WITH CITY OF WPB UTILITIES.
  
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-03-06 Cont ID  
Sent By wjolin Date 2013-03-06 Time 12:50 Rev Time 0.00
Received By wjolin Date 2013-03-06 Time 08:30 Sent To  
Notes
2013-03-06 08:36:076751 NORTH JOG ROAD
 PERMIT #12080469
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PREVIOUS FIRE DEPARTMENT COMMENTS HAVE BEEN ADDRESSED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-12-01 Cont ID  
Sent By wjolin Date 2012-12-01 Time 12:39 Rev Time 0.00
Received By wjolin Date 2012-11-30 Time 10:46 Sent To  
Notes
2012-11-30 15:39:516751 NORTH JOG ROAD
 PERMIT #12080469
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PEDESTRIAN BRIDGE - RESPONSE: UPON FURTHER CODE REVIEW,
 THE FLORIDA FIRE PREVENTION CODE REQUIRES (EVEN WHILE
 THE FBC MAY NOT) THE FOLLOWING WITHOUT EXCEPTION:
 NFPA 101 SECTION 7.2.4.3.1 "FIRE BARRIERS SEPARATING
 BUILDINGS OR AREAS BETWEEN WHICH THERE ARE HORIZONTAL
 EXITS SHALL HAVE A MINIMUM 2-HOUR FIRE RESISTANCE
 RATING, UNLESS OTHERWISE PROVIDED IN 7.2.4.4.1, AND
 SHALL
 PROVIDE A SEPARATION THAT IS CONTINUOUS TO THE FINISHED
 GROUND LEVEL." ALSO NFPA 101 SECTION 7.2.4.4 "BRIDGES
 SERVING HORIZONTAL EXITS BETWEEN BUILDINGS. THE
 PROVISIONS OF 7.2.4.4 SHALL APPLY TO BRIDGES SERVING
 HORIZONTAL EXITS BETWEEN BUILDINGS AND TO THE
 ASSOCIATED HORIZONTAL EXIT FIRE BARRIER. THE MINIMUM
 2-HOUR FIRE RESISTANCE-RATED BARRIER REQUIRED BY
 7.2.4.3.1 SHALL EXTEND AS FOLLOWS:
 (1) VERTICALLY FROM THE GROUND TO A POINT 10 FEET ABOVE
 THE BRIDGE OR TO THE ROOFLINE, WHICHEVER IS LOWER
 (2) HORIZONTALLY FOR NOT LESS THAN 10 FEET TO EACH SIDE
 OF THE BRIDGE 7.2.4.4.2 ANY OPENING IN THE FIRE BARRIER
 ADDRESSED IN 7.2.4.4.1 SHALL BE PROTECTED WITH FIRE
 DOOR ASSEMBLIES OR FIXED FIRE WINDOW ASSEMBLIES HAVING
 A 3/4-HOUR FIRE PROTECTION RATING, UNLESS OTHERWISE
 PROVIDED IN 7.2.4.4.3."
  
 SHEET 710-A5-100 - NEW COMMENT: THE SOUTH LOBBY DOOR
 SWING WAS REVISED AND NOW THE SWING IS AGAINST THE FLOW
 OF EGRESS.
  
 SHEET 710-FP-100 - RESPONSE: THE EXCEPTION STATED IN
 FBC 1004.1.1 FOR REDUCING THE OCCUPANT LOAD IS NOT
 APPROVED BY THE FIRE MARSHAL'S OFFICE.
 ORIGINAL COMMENT: PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES AS NEW ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM
 NOTIFICATION BY VISIBLE SIGNALS AND VOICE
 ANNOUNCEMENTS. REFERENCE SECTION 12.3.4.3.3 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101
  
 SHEET 710-FP-100 - REPEAT COMMENT: PROVIDE A
 PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING
 OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE
 BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
  
 SHEET 710-FP-111 - RESPONSE: THE RESPONSE LETTER
 INDICATES HYDRAULIC CALCULATIONS WERE SUBMITTED WITH
 THE ORIGINAL SUBMITTAL AND ALSO WITH THE RE-SUBMITTAL;
 HOWEVER, A FILE CONTAINING THESE CALCULATIONS CANNOT BE
 LOCATED.
 ORIGINAL COMMENT: SUBMIT HYDRAULIC CALCULATIONS FOR
 REVIEW.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-08-28 Cont ID  
Sent By wjolin Date 2012-08-28 Time 15:08 Rev Time 0.00
Received By wjolin Date 2012-08-27 Time 11:14 Sent To  
Notes
2012-08-28 10:49:456751 NORTH JOG ROAD
 PERMIT #12080469
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL CONSTRUCTION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. SMOKING SHALL BE PROHIBITED EXCEPT IN
 DESIGNATED EXTERIOR AREAS. ALL OTHER CONSTRUCTION AREAS
 SHALL HAVE "NO SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SHEET 710-A2-100: COULD NOT LOCATE THE DOOR HARDWARE
 SET INFORMATION. INDICATE THE DOORS TO BE EQUIPPED WITH
 PANIC OR FIRE EXIT HARDWARE.
  
 SHEET 710-A1-203: INDICATE THE INTERIOR FINISH
 CLASSIFICATION OF THE SUSPENDED CANOPIES LOCATED IN THE
 STAIR ENCLOSURE.
  
 SHEET 710-A5-100: THE PLAN DOES NOT INDICATE A SECOND
 EXIT FOR THE THIRD FLOOR; HOWEVER, THE PEDESTRIAN
 BRIDGE WOULD APPEAR TO FUNCTION AS THE SECONDARY MEANS
 OF EGRESS (HORIZONTAL EXIT). PROVIDE EXIT SIGNAGE FOR
 ENTRANCE INTO PEDESTRIAN BRIDGE.
  
 SHEET 710-A5-100: THE EMERGENCY LIGHTING IN THE STAIRS
 IS ONLY SHOWN ON THE THIRD FLOOR.
  
 SHEET 710-A5-100: THE MECHANICAL ROOM LOCATED WITHIN
 THE STAIR ENCLOSURE DOES NOT SHOW A FIRE RATING
 SEPARATING THIS ROOM FROM THE STAIR.
  
 SHEET 710-A5-100: INDICATE THE OCCUPANT LOAD FOR THE
 THIRD FLOOR ROOF/GARDEN AREA.
  
 SHEET 710-A5-100: THE NORTH LOBBY DOOR HAS A SWING THAT
 IS AGAINST THE FLOW OF EGRESS.
  
 PEDESTRIAN BRIDGE MAY NEED TO BE SEPARATED FROM THE
 VISITOR CENTER WITH A 2-HOUR FIRE BARRIER OR
 EQUIVALENT. REFERENCE THE FLORIDA BUILDING CODE SECTION
 3104 FOR CODE REQUIREMENTS.
  
 DRAWINGS FOR THE ATTACHED PEDESTRIAN BRIDGE ARE
 REFERENCED ON THE DRAWINGS BUT DO NOT APPEAR TO HAVE
 BEEN SUBMITTED (710-A1-400, 710-A1-401 & 710-A3-400)
  
 SHEET 710-FP-100: PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES AS NEW ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM
 NOTIFICATION BY VISIBLE SIGNALS AND VOICE
 ANNOUNCEMENTS. REFERENCE SECTION 12.3.4.3.3 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101
  
 SHEET 710-FP-100: PROVIDE A PRE-RECORDED FIRE ALARM
 EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS
 BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT,
 AND EXIT THE BUILDING IMMEDIATELY. DO NOT USE THE
 ELEVATOR.
  
 SHEET 710-FP-100: PLANS DO NOT INDICATE THE METHOD
 (HEAT DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO
 SHUNT TRIP POWER TO THE ELEVATOR IN THE EVENT AN
 AUTOMATIC SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE
 ROOM.
  
 SHEET 710-FP-100: A CERTIFICATE OF COMPLETION AND A
 THIRD PARTY MONITORING/VERIFICATION (UL OR ETL)
 CERTIFICATE SHALL BE PROVIDED AT TIME OF FINAL FIRE
 ALARM INSPECTION.
  
 SHEET 710-FP-102: PROVIDE A MANUAL PULL STATION IN
 LOBBY #300.
  
 SHEET 710-FP-111: THE PEDESTRIAN BRIDGE IS LESS THAN
 50% OPEN AND IS ATTACHED TO A THREE STORY BUILDING.
 PROVIDE SPRINKLER PROTECTION FOR BRIDGE PER FBC
 903.6.1.
  
 SHEET 710-FP-111: SUBMIT HYDRAULIC CALCULATIONS FOR
 REVIEW.
  
 SHEET 710-FP-114: DESIGN SHALL CONFORM TO THE 2007
 EDITION OF NFPA 13 NOT THE 2002 EDITION.
  
 SHEET 710-FP-114: PROVIDE LOCKING KNOX CAPS FOR THE
 FIRE DEPARTMENT CONNECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-03-15 Cont ID  
Sent By rregueir Date 2013-03-13 Time 15:35 Rev Time 0.00
Received By rregueir Date 2013-02-28 Time 15:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2013-01-10 Time   Rev Time 0.00
Received By rregueir Date 2012-11-22 Time 08:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2012-10-09 Time   Rev Time 0.00
Received By rregueir Date 2012-08-22 Time 10:01 Sent To  
Notes
2012-08-22 10:01:21DIGITAL

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-03-13 Cont ID  
Sent By rregueir Date 2013-03-13 Time 09:09 Rev Time 0.00
Received By rregueir Date 2013-03-13 Time 09:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-01-11 Cont ID  
Sent By rregueir Date 2013-01-10 Time 09:01 Rev Time 0.00
Received By rregueir Date 2013-01-10 Time 09:01 Sent To  
Notes
2013-01-11 09:03:19PROVISO:
  
 PAGE HC103: CONDENSATE SHALL NOT PENETRATE RATED EXIT
 ENCLOSURE PER FBC-B 1022.4. SEE PROVISO ON PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-10-09 Cont ID  
Sent By rregueir Date 2012-10-09 Time 16:49 Rev Time 0.00
Received By rregueir Date 2012-09-26 Time 08:48 Sent To  
Notes
2012-10-04 17:02:46REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE HC-101: PLAN SHOWS DUCT PENETRATIONS OF THE
 STAIR EXIT ENCLOSURE. SUCH PENETRATIONS AND VENTILATION
 SYSTEMS ARE PROHIBITED FOR EXIT ENCLOSURES PER FBC-B
 1022.4 AND 1022.5.
  
 2. PAGE HC-101: PLAN SHOWS SEVERAL DUCT PENETRATIONS
 FROM THE FIRST FLOOR UP THROUGH TO THE 2ND FLOOR. SHOW
 HOW THESE PENETRATIONS ARE TO BE PROTECTED PER FBC-M
 607.5.
  
 3. PAGE HC-102: PLAN SHOWS DUCT PENETRATIONS OF THE
 STAIR EXIT ENCLOSURE. SUCH PENETRATIONS AND VENTILATION
 SYSTEMS ARE PROHIBITED FOR EXIT ENCLOSURES PER FBC-B
 1022.4 AND 1022.5.
  
 4. PAGE HC-103: PLAN SHOWS AHU/VENTILATION SYSTEM FOR
 THE STAIR EXIT ENCLOSURE AND THE REST OF THE 3RD FLOOR
 LOCATED IN THE EXIT ENCLOSURE. THE VENTILATION SYSTEM
 FOR THE EXIT ENCLOSURE MUST BE DEDICATED TO THE
 ENCLOSURE PER FBC-B 1022.5.
  
 5. PAGE HC-103: DUCT PENETRATIONS OF EXIT ENCLOSURE ARE
 PROHIBITED PER FBC--B 1022.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-12-07 Cont ID  
Sent By lwagner Date 2012-12-07 Time 09:40 Rev Time 0.00
Received By lwagner Date 2012-12-06 Time 10:33 Sent To  
Notes
2012-12-06 10:41:18PER LETTER 11202012 UNISEX RESTROOM NOT REQUIRED DUE TO
 REDUCED OCCUPANT LOAD.
  
 *PROVISO*
 1. THE SANITARY DRAINAGE FROM THE SECOND FLOOR
 RESTROOMS IS DROPPING INTO THE VENT FOR THE FIRST FLOOR
 RESTROOMS.
 THE 2ND FLOOR SOIL STACK SHALL BE CONNECTED TO THE
 SANITARY MAIN.
  
 2. A SHUTOFF VALVE IS REQUIRED WHERE THE DOMESTIC WATER
 ENTERS THE BUILDING. 606.1 (2)
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-08-24 Cont ID  
Sent By lwagner Date 2012-08-24 Time 15:57 Rev Time 0.00
Received By lwagner Date 2012-08-22 Time 11:18 Sent To  
Notes
2012-08-22 11:54:46FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET A1-102, A1-201
 THE DETAIL FOR THE STANDARD TOILET STALLS DOES NOT HAVE
 A MEASUREMENT FOR STALL DEPTH ON THE DRAWING. THE
 INSIDE DIMENSION APPEARS TO BE 4'-6". THE MINIMUM FOR
 STALLS IS 60" DEEP. FBC PLUMBING 405.3.1
  
 2. AS THREE FLOORS ARE OCCUPIED AND AN AGGREGATE OF
 MORE THAN SIX WATER CLOSETS ARE REQUIRED, A UNISEX
 RESTROOM WILL BE REQUIRED. THE RESTROOM SHOULD BE
 PLACED ON THE SECOND FLOOR TO BE WITHIN ONE FLOOR LEVEL
 PER 403.3.2. THE UNISEX FIXTURES COUNT AS REQUIRED
 FIXTURES.
 403.5 UNISEX TOILET AND BATHING ROOMS.
 IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE
 UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE
 OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS
 REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE
 WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE
 OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET
 ROOM REQUIREMENT.
  
 3. SHEET PB-106
 THE SANITARY DRAINAGE FROM THE SECOND FLOOR RESTROOMS
 IS DROPPING INTO THE VENT FOR THE FIRST FLOOR
 RESTROOMS.
 908.1 INDIVIDUAL VENT AS COMMON VENT.
 AN INDIVIDUAL VENT IS PERMITTED TO VENT TWO TRAPS OR
 TRAPPED FIXTURES AS A COMMON VENT. THE TRAPS OR TRAPPED
 FIXTURES BEING COMMON VENTED SHALL BE LOCATED ON THE
 SAME FLOOR LEVEL.
  
 4. A CLEANOUT WILL BE REQUIRED NEAR THE BASE OF THE
 SOIL STACK FOR THE SECOND FLOOR RESTROOMS.
 708.3.4 BASE OF STACK.
 A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH WASTE
 OR SOIL STACK.
  
 5, ALL HOSE BIBBS AND WALL HYDRANTS REQUIRE A SEPARATE
 SHUTOFF VALVE.
 606.2 LOCATION OF SHUTOFF VALVES.
 SHUTOFF VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER THAN
 ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 6. SHEET PB-106
 THE DOWNFEED WATER RISERS FOR THE FIRST FLOOR REQUIRE
 SHUTOFF VALVES.
 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 5. ON THE TOP OF EVERY WATER DOWN-FEED PIPE IN
 OCCUPANCIES OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL
 OCCUPANCIES.
  
 7. A SERVICE SINK WAS NOT FOUND ON THE PLAN.
 403.1 ASSEMBLY OCCUPANCIES REQUIRE A SERVICE SINK.
  
 8. SHEET PB-102
 A. A SHUTOFF VALVE IS REQUIRED WHERE THE DOMESTIC WATER
 ENTERS THE BUILDING. 606.1 (2)
 B. A BACKFLOW PREVENTOR IS SHOWN INSIDE THE BUILDING.
 IF THIS IS THE MAIN RPZ BACKFLOW FOR THE BUILDING, IT
 SHOULD BE AS CLOSE TO THE DOMESTIC WATER METER AS
 POSSIBLE PER UTILITIES ORD.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  
  
  
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-03-15 Cont ID  
Sent By rregueir Date 2013-03-15 Time 15:29 Rev Time 0.00
Received By rregueir Date 2013-03-15 Time 15:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2013-03-14 Cont ID  
Sent By eschneid Date 2013-03-14 Time 09:25 Rev Time 0.75
Received By eschneid Date 2013-03-14 Time 09:25 Sent To  
Notes
2013-03-14 10:12:26PASSED
  
 1) THE FINAL AS-BUILT PLANS NEED TO BE SUBMITTED AS A
 MINOR SITE PLAN AMENDMENT TO THE PLANNING DIVISION
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 2) LANDSCAPE PLANS SHALL BE APPROVED AND THE LANDSCAPE
 INSTALLED TO SCREEN THE AIR CONDITION UNITS PRIOR TO
 THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 3) LANDSCAPE, SITE LIGHTING, SIGNAGE AND PARKING LOT
 STRIPING REQUIRE SEPARATE PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2012-12-04 Cont ID  
Sent By eschneid Date 2012-12-04 Time 15:38 Rev Time 1.50
Received By eschneid Date 2012-12-04 Time 15:38 Sent To  
Notes
2012-12-04 15:49:35PASSED
  
 1) THE FINAL AS-BUILT PLANS NEED TO BE SUBMITTED AS A
 MINOR SITE PLAN AMENDMENT TO THE PLANNING DIVISION
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 2) LANDSCAPE PLANS SHALL BE APPROVED AND THE LANDSCAPE
 INSTALLED TO SCREEN THE AIR CONDITION UNITS PRIOR TO
 THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 3) LANDSCAPE, SITE LIGHTING, SIGNAGE AND PARKING LOT
 STRIPING REQUIRE SEPARATE PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-09-20 Cont ID  
Sent By eschneid Date 2012-09-20 Time 15:28 Rev Time 4.00
Received By eschneid Date 2012-09-20 Time 15:28 Sent To  
Notes
2012-09-20 15:31:11FAILED
  
 PLEASE RESPOND IN WRITING. PLEASE NOTE THAT THE PLANS
 HAVE BEEN MARKED WITH THE COMMENTS. ALL CORRECTIONS
 SHALL BE REFLECTED ON ALL PLANS, REGARDLESS IF THEY
 INCLUDE NOTES.
  
 1) SITE LAYOUT AND ELEVATIONS HAVE CHANGED. THE FINAL
 AS-BUILT PLANS NEED TO BE SUBMITTED AS A MINOR SITE
 PLAN AMENDMENT TO THE PLANNING DIVISION.
  
 2) THE RELOCATED SIDEWALK, SOUTH OF THE VISITOR
 BUILDING LEADING TO THE MAIN POWER BLOCK, HAS BEEN
 SHIFTED TO THE WEST FROM THE ORIGINALLY APPROVED PLANS.
 THIS RESULTS IN THE INTERIOR LANDSCAPE ISLANDS NOT
 HAVING SUFFICIENT WIDTH TO SUPPORT THE REQUIRED TREES.
  
 3) HOW WILL THE FOOTER AND SUPPORT POST ALLOW FOR THE
 INSTALLATION OF THE REQUIRED TREES IN THE TERMINAL
 PARKING ISLANDS? THE ACCURATE DIMENSIONS NEED TO BE
 SHOWN ON THE SITE AND LANDSCAPE PLANS. THE SUPPORT
 POSTS SHOWN ON SHEET 710-A5-101 DO NOT MATCH THE
 FOOTPRINT ON THE SITE PLAN.
  
 4) HOW WILL THE AIR CONDITION UNITS BE SCREENED?
  
 5) CHECK THE DIMENSIONS IN THE NORTHEAST CORNER OF THE
 PARKING LOT. THEY DO NOT SEEM TO SCALE WITH WHAT IS
 SHOWN.
  
 6) WHAT IS THE 16 FOOT MEASUREMENT SHOWING AT THE
 PHOTOVOLTAIC CARPORTS?
  
 7) LIGHT POLE LOCATIONS SHALL NOT INTERFERE WITH
 PARKING LOT TREES. STAFF WILL NOT APPROVE THE SITE
 LIGHTING UNTIL THE LANDSCAPE PLAN IS SUBMITTED FOR
 REVIEW TO ENSURE NO CONFLICTS. PLEASE NOTE THAT SITE
 LIGHTING REQUIRES A SEPARATE PERMIT.
  
 8) SIGNAGE AND PARKING LOT STRIPING REQUIRE SEPARATE
 PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
  
  