Plan Review Stops For Permit 12080092 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2012-08-08 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-08-08 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-08-08 |
Time |
15:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2012-08-06 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-08-06 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-08-06 |
Time |
11:28 |
Sent To |
|
|
Notes |
2012-08-06 13:29:50 | 12080092 | | 6615 PAMELA LANE | | ELECTRIC REVISION | | | | ELECTRICAL PANEL BOARDS MAY NOT BE LOCATED IN CLOSETS. | | NEC 240.24 (D), 408.17 | | PANEL BOARD ?A? REQUIRES A MAIN BREAKER. NEC 408.36 | | MAIN DISCONNECTS ARE REQUIRED TO BE GROUPED AND LOCATED | | NEAR THE POINT OF ENTRANCE OF THE SERVICE CONDUCTORS. | | NEC 230.70, 230. 72 | | | | ROBERT LECKY | | ELECTRIC PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2012-08-08 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-08-08 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-08-08 |
Time |
15:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-08-06 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-08-06 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-08-06 |
Time |
11:28 |
Sent To |
|
|
Notes |
2012-08-03 16:12:16 | SENT TO RMCDOUGAL |
|
|
|