Plan Review Details - Permit 12080080
Plan Review Stops For Permit 12080080
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-11-06 Cont ID  
Sent By jgomez Date 2012-11-06 Time 10:20 Rev Time 0.00
Received By jgomez Date 2012-11-06 Time 10:20 Sent To  
Notes
2012-11-06 10:24:39BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE ENERGY CALCULATIONS.
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FRENCH
 DOORS. NOA 08-0821.09 SUBMITTED WAS SUPERSEDED.
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE DOORS
 PRODUCT APPROVAL.
 4- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF THE ALUMINUM BAHAMA SHUTTERS.
 5- NEW SECTION B-B ON SHEET A-2:
 A) SPECIFY INSULATION ON THE DEMISING WALL BETWEEN THE
 GARAGE AND THE OFFICE. SEE ENERGY CALCULATIONS.
 B) PROVIDE COMPLETE SPECIFICATIONS FOR THE 1 HR
 DEMISING WALL BETWEEN THE GARAGE AND THE OFFICE. WHERE
 IS THE GA FILE NO WP1072?.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-11-05 Cont ID  
Sent By jgomez Date 2012-11-05 Time 08:38 Rev Time 0.00
Received By jgomez Date 2012-11-05 Time 08:27 Sent To  
Notes
2012-11-05 08:39:24BUILDING REVIEW SECOND CHECKLIST:
 CODE:2010 FBC.
  
  
 1- PROVIDE ENERGY CALCULATIONS. SEC.103.2 OF 2010
 FBC-ENERGY CONSERVATION.
 ***NOTE: THIS IS NOT A CONTRIBUTING HISTORIC BUILDING,
 THEREFORE, HISTORIC EXEMPTION DOESN'T APPLY.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FRENCH
 DOORS. NOA 08-0821.09 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. REQ'D DCA RULE 9N-3. (REPEAT COMMENT).
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE DOORS
 PRODUCT APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS TO
 FBC.
  
 4- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF THE ALUMINUM BAHAMA SHUTTERS. SEC.
 107.2.1 CITY AMENDMENTS TO FBC. (REPEAT COMMENT).
  
 5- NEW SECTION B-B ON SHEET A-2:
 A) SPECIFY INSULATION ON THE DEMISING WALL BETWEEN THE
 GARAGE AND THE OFFICE. COORDINATE WITH THE ENERGY
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) PROVIDE COMPLETE SPECIFICATIONS FOR THE 1 HR
 DEMISING WALL BETWEEN THE GARAGE AND THE OFFICE. WHERE
 IS THE GA FILE NO WP1072?. SEC. 107.2.1 CITY AMENDMENTS
 TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-09-18 Cont ID  
Sent By jgomez Date 2012-09-17 Time 16:20 Rev Time 0.00
Received By jgomez Date 2012-09-17 Time 10:51 Sent To  
Notes
2012-09-18 16:19:10RESIDENTIAL (R3) GARAGE CHANGE OF USE BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 103.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 3- SHEET A-1: DESIGN CRITERIA, ENGINEER SPECIFIES THAT
 THIS BUILDING IS LOCATED ON EXPOSURE "B". ACCORDING TO
 SEC. R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL CODE THIS
 BUILDING IS LOCATED ON EXPOSURE "C". REVISE DESIGN
 CRITERIA INFORMATION AND DOORS/ WINDOWS DESIGN
 PRESSURES AS REQUIRED.
  
 4- ENGINEER OF RECORD TO PROVIDE COMPLETE
 SPECIFICATIONS DETAILS ON PLANS SHOWING COMPLIANCE WITH
 THE OFFICE/GARAGE FIRE SEPARATION AS REQUIRED BY SEC.
 R302.6 OF 2010 FLORIDA RESIDENTIAL CODE.
  
 5- SHEET A-2:
 A) PROPOSED FLOOR PLAN SPECIFIES OFFICE TRAY CEILING BY
 OWNER. ENGINEER OF RECORD TO PROVIDE COMPLETE FRAMING
 DETAILS. CLARIFY IF EXISTING TRUSSES OR ROOF RAFTERS
 ARE GOING TO BE CUT TO ALLOW FOR THE NEW TRAY CEILING.
 PROVIDE DETAILS SHOWING HOW THE EXISTING TRUSSES/ROOF
 RAFTERS ARE GOING TO BE REINFORCED TO KEEP THE
 STRUCTURAL STABILITY. SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 B) BATHROOM CLOSET SHOWN ON THE PROPOSED FLOOR PLAN
 SHOWS THAT THE LAVATORY IS IN FRONT OF THE DOOR.
 THEREFORE, THE CLOSET IS NOT ACCESSIBLE. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) DOUBLE CASEMENT WINDOW SIZE AS SHOWN ON PLANS. NOA
 07-0820.02 SUBMITTED DOESN'T COVER THE SIZE OF WINDOW
 SPECIFIED.
  
 B) FRENCH DOORS AS SHOWN ON PLANS. NOA 08-0821.09
 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. VISIT THE
 MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA AND
 RESUBMIT.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THE BAHAMA SHUTTERS) AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS TO FBC TO VERIFY THAT PRODUCT
 APPROVALS MEET THE CALCULATED DESIGN PRESSURES.
  
 8- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF THE ALUMINUM BAHAMA SHUTTERS. CLEARLY
 IDENTIFY WHICH SPECIFIC SHUTTERS FROM NOA 09-0122.07
 SUBMITTED ARE GOING TO BE INSTALLED. AND SPECIFY
 SPECIFIC ANCHOR TYPE AND SPACING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER. SEC. R301.2.1.4.3.
  
 9- ACCORDING TO THE FLORIDA DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION (DBPR) THE CONTRACTOR NEEDS TO
 UPDATE HIS LICENSE. CONTRACTOR TO CONTACT DBPR TO
 UPDATE LICENSE STATUS. SEC. 105.1 CITY AMENDMENTS TO
 FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-11-05 Cont ID  
Sent By rlecky Date 2012-11-05 Time 11:52 Rev Time 0.00
Received By rlecky Date 2012-11-05 Time 11:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-08-20 Cont ID  
Sent By rlecky Date 2012-08-20 Time 08:41 Rev Time 0.00
Received By rlecky Date 2012-08-20 Time 08:26 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2012-11-06 Cont ID  
Sent By fmittner Date 2012-11-06 Time 10:09 Rev Time 0.00
Received By fmittner Date 2012-11-06 Time 10:09 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-08-16 Cont ID  
Sent By fmittner Date 2012-08-16 Time 09:38 Rev Time 0.00
Received By fmittner Date 2012-08-16 Time 09:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-11-15 Cont ID  
Sent By rbrown Date 2012-11-15 Time 14:09 Rev Time 0.00
Received By rbrown Date 2012-11-09 Time 15:45 Sent To  
Notes
2012-11-09 15:51:57INCOMING SENT TO JULIO DESK . JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-11-06 Cont ID  
Sent By jgomez Date 2012-11-06 Time 08:58 Rev Time 0.00
Received By jgomez Date 2012-10-29 Time 16:30 Sent To  
Notes
2012-10-29 16:41:01GAVE TO JULIO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-18 Cont ID  
Sent By jgomez Date 2012-09-18 Time 16:19 Rev Time 0.00
Received By jgomez Date 2012-08-16 Time 16:39 Sent To  
Notes
2012-08-16 16:49:16R--5

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2012-11-15 Cont ID  
Sent By rbrown Date 2012-11-15 Time 14:07 Rev Time 0.00
Received By rbrown Date 2012-11-15 Time 14:07 Sent To  
Notes
2012-11-15 14:09:05PBC IMPACT FEE RECEIPT NO.: 2012-1108-225

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-11-05 Cont ID  
Sent By jgomez Date 2012-11-05 Time 08:49 Rev Time 0.00
Received By jgomez Date 2012-11-05 Time 08:49 Sent To  
Notes
2012-11-05 08:50:01BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-09-17 Cont ID  
Sent By jgomez Date 2012-09-17 Time 10:53 Rev Time 0.00
Received By jgomez Date 2012-09-17 Time 10:53 Sent To  
Notes
2012-09-17 10:54:56BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-11-05 Cont ID  
Sent By jgomez Date 2012-11-05 Time 10:33 Rev Time 0.00
Received By jgomez Date 2012-11-05 Time 10:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-09-18 Cont ID  
Sent By jgomez Date 2012-09-18 Time 11:46 Rev Time 0.00
Received By jgomez Date 2012-09-18 Time 11:36 Sent To  
Notes
2012-09-18 11:57:04RESIDENTIAL (R3) GARAGE CHANGE OF USE PLUMBING REVIEW
 COMMENTS.
 2010 FBC.
  
 1- PROVIDE PLUMBING RISER DIAGRAM AS REQUIRED BY SEC.
 107.3.5.3(11) OF CITY AMENDMENTS TO FBC.
  
 2- SHOW WHERE IS THE WATER HEATER LOCATED. SEC. P2801.1
 OF 2010 FLORIDA RESIDENTIAL CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 1 Status P Date 2012-08-16 Cont ID  
Sent By fmittner Date 2012-08-16 Time 09:38 Rev Time 0.00
Received By fmittner Date 2012-08-16 Time 09:38 Sent To  
Notes
***NONE***