2012-09-18 16:19:10 | RESIDENTIAL (R3) GARAGE CHANGE OF USE BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| BY SEC. 103.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE |
| DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT |
| IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE |
| UNIFIED LAND DEVELOPMENT CODE. |
| |
| 3- SHEET A-1: DESIGN CRITERIA, ENGINEER SPECIFIES THAT |
| THIS BUILDING IS LOCATED ON EXPOSURE "B". ACCORDING TO |
| SEC. R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL CODE THIS |
| BUILDING IS LOCATED ON EXPOSURE "C". REVISE DESIGN |
| CRITERIA INFORMATION AND DOORS/ WINDOWS DESIGN |
| PRESSURES AS REQUIRED. |
| |
| 4- ENGINEER OF RECORD TO PROVIDE COMPLETE |
| SPECIFICATIONS DETAILS ON PLANS SHOWING COMPLIANCE WITH |
| THE OFFICE/GARAGE FIRE SEPARATION AS REQUIRED BY SEC. |
| R302.6 OF 2010 FLORIDA RESIDENTIAL CODE. |
| |
| 5- SHEET A-2: |
| A) PROPOSED FLOOR PLAN SPECIFIES OFFICE TRAY CEILING BY |
| OWNER. ENGINEER OF RECORD TO PROVIDE COMPLETE FRAMING |
| DETAILS. CLARIFY IF EXISTING TRUSSES OR ROOF RAFTERS |
| ARE GOING TO BE CUT TO ALLOW FOR THE NEW TRAY CEILING. |
| PROVIDE DETAILS SHOWING HOW THE EXISTING TRUSSES/ROOF |
| RAFTERS ARE GOING TO BE REINFORCED TO KEEP THE |
| STRUCTURAL STABILITY. SEC. 107.2.1 CITY AMENDMENTS TO |
| FBC. |
| |
| B) BATHROOM CLOSET SHOWN ON THE PROPOSED FLOOR PLAN |
| SHOWS THAT THE LAVATORY IS IN FRONT OF THE DOOR. |
| THEREFORE, THE CLOSET IS NOT ACCESSIBLE. REVISE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) DOUBLE CASEMENT WINDOW SIZE AS SHOWN ON PLANS. NOA |
| 07-0820.02 SUBMITTED DOESN'T COVER THE SIZE OF WINDOW |
| SPECIFIED. |
| |
| B) FRENCH DOORS AS SHOWN ON PLANS. NOA 08-0821.09 |
| SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. VISIT THE |
| MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA AND |
| RESUBMIT. |
| |
| 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| (INCLUDING THE BAHAMA SHUTTERS) AS REQUIRED BY SEC. |
| 107.3.4.1 CITY AMENDMENTS TO FBC TO VERIFY THAT PRODUCT |
| APPROVALS MEET THE CALCULATED DESIGN PRESSURES. |
| |
| 8- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE |
| INSTALLATION OF THE ALUMINUM BAHAMA SHUTTERS. CLEARLY |
| IDENTIFY WHICH SPECIFIC SHUTTERS FROM NOA 09-0122.07 |
| SUBMITTED ARE GOING TO BE INSTALLED. AND SPECIFY |
| SPECIFIC ANCHOR TYPE AND SPACING TO BE USED TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES CALCULATED BY THE |
| ENGINEER. SEC. R301.2.1.4.3. |
| |
| 9- ACCORDING TO THE FLORIDA DEPARTMENT OF BUSINESS AND |
| PROFESSIONAL REGULATION (DBPR) THE CONTRACTOR NEEDS TO |
| UPDATE HIS LICENSE. CONTRACTOR TO CONTACT DBPR TO |
| UPDATE LICENSE STATUS. SEC. 105.1 CITY AMENDMENTS TO |
| FBC. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |