Plan Review Details - Permit 12070928
Plan Review Stops For Permit 12070928
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-07-27 Cont ID  
Sent By rmcdouga Date 2012-07-27 Time 07:04 Rev Time 0.00
Received By rmcdouga Date 2012-07-27 Time 07:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-08-09 Cont ID  
Sent By rlecky Date 2012-08-09 Time 12:32 Rev Time 0.00
Received By rlecky Date 2012-08-09 Time 12:13 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-08-07 Cont ID  
Sent By rmcdouga Date 2012-08-07 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2012-08-07 Time 07:25 Sent To  
Notes
2012-08-07 07:32:53REPEAT COMMENTS
  
 2010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) SUBMIT TWO SETS OF ELECTRICAL WIRING DIAGRAMS FOR
 THE POOL EQUIPMENT. CITY AMENDMENTS 107.2.1 & 107.3.5.3
  
 2) SUBMIT TWO SETS OF LOAD CALCULATIONS AND RISER
 DIAGRAM FOR THE EXISTING SERVICE. CITY AMENDMENTS
 107.2.1 & 107.3.5.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-07-27 Cont ID  
Sent By rmcdouga Date 2012-07-27 Time 07:14 Rev Time 0.00
Received By rmcdouga Date 2012-07-27 Time 07:14 Sent To  
Notes
2012-07-27 07:53:442010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) SUBMIT TWO SETS OF ELECTRICAL WIRING DIAGRAMS FOR
 THE POOL EQUIPMENT. CITY AMENDMENTS 107.2.1 & 107.3.5.3
  
 2) SUBMIT TWO SETS OF LOAD CALCULATIONS AND RISER
 DIAGRAM FOR THE EXISTING SERVICE. CITY AMENDMENTS
 107.2.1 & 107.3.5.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2012-07-27 Cont ID  
Sent By rmcdouga Date 2012-07-27 Time 07:54 Rev Time 0.00
Received By rmcdouga Date 2012-07-27 Time 07:54 Sent To  
Notes
2012-07-27 07:55:50A SEPARATE APPLICATION, DRAWINGS AND REVIEW IS REQUIRED
 FOR A GAS PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-08-07 Cont ID  
Sent By rmcdouga Date 2012-08-07 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2012-08-03 Time 16:13 Sent To  
Notes
2012-08-03 16:13:27SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-27 Cont ID  
Sent By rmcdouga Date 2012-07-27 Time 07:56 Rev Time 0.00
Received By rmcdouga Date 2012-07-25 Time 15:24 Sent To  
Notes
2012-07-25 15:24:41GAVE TO MURRIAH

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-08-07 Cont ID  
Sent By rmcdouga Date 2012-08-07 Time 07:25 Rev Time 0.00
Received By rmcdouga Date 2012-08-07 Time 06:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-07-27 Cont ID  
Sent By rmcdouga Date 2012-07-27 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2012-07-27 Time 07:55 Sent To  
Notes
2012-07-27 08:37:152010 FBC
  
 DENIED BY PLUMBING
  
 1) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECTION 403.9.4 (3) AND HOUSE BILL 849 WHICH REQUIRE
 FILTRATION POOL PUMPS 1 HP AND GREATER TO HAVE A
 DEFAULT CIRCULATION SPEED THAT RESULTS IN A FLOW RATE
 THAT WILL NOT TURN THE POOL OVER IN LESS THAN SIX HOURS
 OR 36 GPM WHICHEVER IS GREATER WITH A HIGHER SPEED
 OVERRIDE CAPABILITY FOR A TEMPORARY PERIOD NOT TO
 EXCEED ONE NORMAL CYCLE OR 24 HOURS, WHICHEVER IS LESS.
 THE PLANS SPECIFY A 3.68 HR TURNOVER RATE AT 60 GPM.
  
 2) SUBMIT THE MANUFACTURER'S SPECIFICATIONS WITH PUMP
 CURVES FOR THE SPA AND POOL FILTRATION PUMP. THE
 MAXIMUM FLOW RATES FOR TWO SPEED OR VARIABLE SPEED
 PUMPS ARE REQUIRED TO BE USED TO DETERMINE THE WATER
 VELOCITY IN THE POOL PIPING. BASED ON THE INFORMATION
 ON PENTAIR'S WEBSITE, THE MAXIMUM FLOW RATE FOR THE 3
 HP PENTAIR VS-3050 IS 145 GPM AT 56 FT TDH. AT THIS
 RATE THE WATER VELOCITY IN THE 3" BRANCH PIPING IS 6.58
 FT/SEC WHICH EXCEEDS THE 6 FT/SEC WHEN ONE OF THE PAIR
 IS BLOCKED THAT IS ALLOWED BY ANSI / APSP- 7 2006
 SECTION 4.4. THE MAXIMUM FLOW RATE FOR THE 2 HP PENTAIR
 WHISPERFLO IS 140 GPM AT 39 FT TDH, WHICH RELATES TO A
 WATER VELOCITY OF 6.36 FT/SEC IN THE 3" PIPE. THIS
 EXCEEDS THE 6 FT/SEC ALLOWED IN THE BRANCH PIPING.
 PLEASE CORRECT. NOTE: ONLY THE BRANCH PIPING AT THE
 MAIN DRAINS DOES NOT COMPLY, THE REST OF THE SUCTION
 PIPING WILL COMPLY. IF CHANNEL DRAINS ARE USED IN LIEU
 OF THE TWO MAIN DRAINS, THERE IS NO BRANCH PIPING
 REQUIREMENT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2012-07-25 Time   Rev Time  
Received By   Date 2012-07-25 Time   Sent To B
Notes
2012-07-25 15:46:03GAVE TO R.M. - MD