Plan Review Details - Permit 12070923
Plan Review Stops For Permit 12070923
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-09-12 Cont ID  
Sent By jwitmer Date 2012-09-12 Time 10:52 Rev Time 0.00
Received By jwitmer Date 2012-09-12 Time 10:04 Sent To  
Notes
2012-09-12 10:56:42BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 SHEET SHEET 2.0E DOOR # 2 HAS AN EXIT SIGN ABOVE IT,
 PLEASE REVIEW SHEET 1.0A NOTE 9.1 THIS AREA COULD BE
 BLOCKED BY A 15 FOOT WIDE SECURITY GRILL.REVISION
 REQUIRED. ALSO SEE FIRE PROVISO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-08-28 Cont ID  
Sent By jwitmer Date 2012-08-28 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2012-08-28 Time 09:10 Sent To  
Notes
2012-08-28 15:46:17BUILDING PLAN REVIEW
 PERMIT: 12070923
 ADD: 700 S ROSEMARY # 208
 CONT: L & L INTERIOR & REMODELING
 TEL: (561)686-5853
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET 1.7A THE LIFE SAFETY PLAN INDICATES THAT PART
 OF THE NEW A-2 OCCUPANCY IS EXITING THROUGH A PORTION
 OF THE KITCHEN AREA/ STORAGE AREA, PLEASE REVIEW
 2010 FBC-B 1014.2(4).
  
 2) SHEET 1.7A , LIFE SAFETY PLAN THE SAME PATH OF
 TTRAVEL HAS A SECOND ISSUE, WHERE TWO MEANS OF EGRESS
 ARE REQUIRED AND AT LEAST 1/3 RD THE DIAGONAL APART,
 THEY ALSO NEED TO HAVE 2 ACCESSIBLE MEANS OF EGRESS,
 CURRENTLY THE PLANS ONLY INDICATE ONE, PLEASE SEE 2010
 ACCESSIBILITY CODE ADVISORY 105.2.4 ICC/IBC .
  
 3) SHEET 1.6A:
 3A) THE PLANS INDICATE A NEW RAISED PLATFORMED FLOOR
 AREA, THE PLANS DO NOT INDICATE THE DESIGN LIVE LOADS
 IT WAS DESIGNED TOO, 2010 FBC-B TABLE 1607.1(11).
  
 3B) THE PLANS DO NOT PROVIDE THE TOTAL SQUARE FOOT AREA
 OF WHICH THE RAISED PLATFORM FLOOR ENCOMPASSES, APPROX
 2690 SQ FT. THE ISSUE WITH THE NEW PLATFORM AREA IS THE
 NEW WALLS BEING INSTALLED WILL NOW CREATE NEW ROOMS,
 WHEREAS SECTION 410.4 ONLY ALLOWS ONE-THIRD THE THE
 ROOM AREA TO BE RAISED FLOOR.
  
 3C) THE OTHER CONCERNS, THE PLANS DO NOT PROVIDE WHAT
 TYPE OF FLOOR DECKING/ SHEATHING IS TO BE APPLIED TO
 THE STEEL FRAMING, 2010 FBC-B 603.1.1 ALLOWABLE
 COMBUSTIBLES IN TYPE I OR II BUILDINGS.
  
 4) PLEASE PROVIDE SPECIFICATIONS FOR THE HIBACHI
 TABLES, ADDITIONAL FRAMING MAYBE REQUIRED IN THE NEW
 FLOOR FRAMING? ADDITIONAL INFORMATION REQUIRED
 107.2.1.3.
  
 5) SHEET 1.0A NOTE # 6 INDICATES INFILE OF FLOORING BUT
 NO FRAMING DETAILS ARE PROVIDED TO COMPLY WITH 2010
 FBC_B TABLE 1607.1(11).
  
 6) THE COVER SHEET INDICATES THE MINIMUM BUILDING TYPE
 AS A TYPE II SPRINKLERED, THE ORIGINAL BUILDING WAS
 BUILT BEORE THE 2004 FBC, THE BUILDING CLASSIFICATIONS
 CHANGED IN THE 2004 FBC, THE CURRENT BUILDING
 CLASSIFICATION IS NOW A IB PLEASE UPDATE PLANS.
  
 7) THE NEWLY FORMED PORTION OF RESTARAUNT MAY BE A
 CHANGE OF OCCUPANCY AND WOULD REQUIRE PALM BEACH COUNTY
 IMPACT FEE ASSESSMENT. BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-09-17 Cont ID  
Sent By rlecky Date 2012-09-17 Time 17:01 Rev Time 0.00
Received By rlecky Date 2012-09-17 Time 16:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-08-28 Cont ID  
Sent By rlecky Date 2012-08-28 Time 16:18 Rev Time 0.00
Received By rlecky Date 2012-08-28 Time 15:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-09-08 Cont ID  
Sent By wjolin Date 2012-09-08 Time 16:48 Rev Time 0.00
Received By wjolin Date 2012-09-08 Time 14:43 Sent To  
Notes
2012-09-08 16:45:59700 SOUTH ROSEMARY AVENUE - SUITE #208
 PERMIT #12070923
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 REMOVE THE EXIT SIGN ABOVE THE DOOR LEADING TO THE
 OUTSIDE DINING AREA OR REMOVE THE VERTICAL SECURITY
 GRILL.
  
 THE FIRE ALARM SYSTEM WILL NEED TO BE PROVIDED WITH
 VOICE EVACUATION WHEN THE OCCUPANT LOAD EXCEEDS 300
 PERSONS IN AN EXISTING ASSEMBLY OCCUPANCY (REFERENCE
 SECTION 13.3.4.3.3 OF FLORIDA FIRE PREVENTION CODE -
 NFPA 101). PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES. PROVIDE A PRE-RECORDED FIRE ALARM
 EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS
 BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT,
 AND EXIT THE BUILDING IMMEDIATELY. DO NOT USE THE
 ELEVATOR.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE WET CHEMICAL
 SUPPRESSION SYSTEMS, FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 PLEASE INDICATE THE CODE REFERENCE EXCEPTION THAT
 PERMITS THE OMISSION OF A TYPE 1 EXHAUST HOOD OVER
 APPLIANCES PRODUCING GREASE-LADEN VAPORS OR SMOKE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-08-29 Cont ID  
Sent By ddaniels Date 2012-08-29 Time 13:46 Rev Time 0.00
Received By ddaniels Date 2012-08-29 Time 13:46 Sent To  
Notes
2012-08-29 13:53:4708/29/2012 PLANS REVIEW BY FIRE ***DENIED***
  
 1. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
  
 2. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
  
 3. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 4. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 5. PLANS INDEX SHOW D1 DEMOLITION PLAN, DO NOT SEE THIS
 SHEET.
  
  
  
 DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-25 Cont ID  
Sent By lmartine Date 2012-09-21 Time 10:01 Rev Time 0.00
Received By lmartine Date 2012-09-07 Time 10:47 Sent To  
Notes
2012-09-07 10:47:33C26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-09-04 Cont ID  
Sent By lmartine Date 2012-08-30 Time 08:25 Rev Time 0.00
Received By lmartine Date 2012-07-25 Time 09:29 Sent To  
Notes
2012-07-26 09:33:35C--12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2012-09-12 Cont ID  
Sent By jwitmer Date 2012-09-12 Time 10:50 Rev Time 0.00
Received By jwitmer Date 2012-09-12 Time 10:50 Sent To  
Notes
2012-09-12 10:52:05SEPT. 04/2012 FILE SET OF PLANS STAMPED NO FEES DUE FOR
 CHANGE OF OCCUPANCY FROM RETAIL TO A2 FOR NEW A2 BAY.
 JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-09-14 Cont ID  
Sent By hmoser Date 2012-09-14 Time 14:48 Rev Time 0.00
Received By hmoser Date 2012-09-14 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-08-28 Cont ID  
Sent By hmoser Date 2012-08-28 Time 13:41 Rev Time 0.00
Received By hmoser Date 2012-08-28 Time 10:46 Sent To  
Notes
2012-08-28 13:41:16PLANS DENIED
 1) PROVIDE HANGING DETAIL FROM THE ENGINEER FOR AIR
 HANDLERS
 SECTION 107 FBC 2010
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 FLORIDA ENERGY CODE.
 3) SEPARATE APPLICATION ,PLANS AND PERMITS REQUIRED FOR
 HOOD, COOLERS, FIRE SUPPRESSION AND HABACHI TABLES AND
 DUCT
 PER SECTION 107 FBC 2010
 4) PROVIDE EQUIPMENT SCHEDULE FOR NEW EXHAUST FANS AND
 NEW AIR HANDLERS PER SECTION 127 FBC 2010
 5) PROVIDE A DETAIL FROM THE ENGINEER ON THE CURB TO
 ROOF TIEDOWN
 AND THE EXHAUST FAN TO CURB TIEDOWN PER SECTION 301.12
 WIND RESISTANCE FBC (M) 2010
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-09-12 Cont ID  
Sent By lwagner Date 2012-09-12 Time 13:15 Rev Time 0.00
Received By lwagner Date 2012-09-12 Time 12:59 Sent To  
Notes
2012-09-12 13:16:52FUEL GAS IS NOT PART OF THIS REVIEW. SEPARATE
 APPLICATION, DRAWING, REVIEW, FEE, AND PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-08-28 Cont ID  
Sent By lwagner Date 2012-08-28 Time 16:03 Rev Time 0.00
Received By lwagner Date 2012-08-28 Time 14:06 Sent To  
Notes
2012-08-28 16:09:36FUEL GAS IS NOT PART OF THIS REVIEW.
 SEPARATE APPLICATION, PERMIT, PLANS, FEE REQUIRED

Review Stop Z ZONING
Rev No 2 Status P Date 2012-09-21 Cont ID  
Sent By eschneid Date 2012-09-21 Time 13:01 Rev Time 1.00
Received By eschneid Date 2012-09-20 Time 08:56 Sent To PC
Notes
2012-09-21 13:02:55ARCHITECT PROVIDED EVIDENCE THAT THE NEW AND RELOCATED
 ROOFTOP EQUIPMENT IS LOCATED SUCH THAT IT COMPLIES WITH
 THE SCREENING REQ.
2012-09-20 08:58:07AWAITING A CLARIFICATION DRAWING FROM PETE RUSSO OF
 METRO. HAVE SPOKEN WITH KEN THE OWNER'S REP AS WELL.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-08-30 Cont ID  
Sent By Eschneid Date 2012-08-30 Time 10:40 Rev Time 1.00
Received By eschneid Date 2012-08-30 Time 10:40 Sent To  
Notes
2012-08-30 11:49:53FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE PLANS SHOW NEW FANS AND OTHER NEW AND RELOCATED
 ROOFTOP EQUIPMENT WHICH SHALL BE SCREENED IN ACCORDANCE
 WITH THE CITYPLACE DRI REGULATIONS: ALL ROOFTOP AND
 GROUND LEVEL MECHANICAL EQUIPMENT, INCLUDING BUT NOT
 LIMITED TO SUCH ITEMS AS PUBLIC AND PRIVATE UTILITY
 SERVICE CONNECTIONS; HEATING, VENTILATING, AND AIR
 CONDITIONING SYSTEMS; COMMUNICATIONS DEVICES; AND
 RELATED EQUIPMENT, SHALL BE SCREENED FROM PUBLIC VIEW
 THROUGH ANY COMBINATION OF LANDSCAPING, WALLS AND
 EQUIPMENT LOCATION. PROVIDE VERIFICATION THAT THE
 SCREENING REQUIREMENT IS MET.
  
 PLEASE NOTE THAT ANY NEW EXTERIOR SIGNAGE SHALL COMPLY
 WITH THE CITYPLACE MASTER SIGN PLAN AND REQUIRES A
 SEPARATE PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.