Plan Review Details - Permit 12070908
Plan Review Stops For Permit 12070908
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-08-14 Cont ID  
Sent By jwitmer Date 2012-08-14 Time 07:50 Rev Time 0.00
Received By jwitmer Date 2012-08-14 Time 07:04 Sent To  
Notes
2012-08-14 07:50:34BUILDING PLAN REVIEW
 PERMIT: 12070908
 ADD: 951 OKEECHOBEE RD.
 CONT: TO BE DETERMINED
 TEL: (561)838-????
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 RULE 9N-3 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-31 Cont ID  
Sent By jwitmer Date 2012-07-31 Time 07:09 Rev Time 0.00
Received By jwitmer Date 2012-07-31 Time 07:00 Sent To  
Notes
2012-07-31 07:15:10BUILDING PLAN REVIEW
 PERMIT: 12070908
 ADD: 951 OKEECHOBEE RD.
 CONT: TO BE DETERMINED
 TEL: (561)838-????
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET S-100 INDICATES UNDER THE HEADINGDESIGN WIND
 LOADS, THE EXPOSURE "B", PLEASE REVIEW SECTION:
 2010 FBC-B 1609.4.1 WIND DIRECTIONS AND SECTORS.
 SURFACE ROUGHNESS C.
 OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS HAVING HEIGHTS
 GENERALLY LESS THAN 30 FEET (9144 MM). THIS CATEGORY
 INCLUDES FLAT OPEN COUNTRY AND GRASSLANDS.THIS SURFACE
 ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING LOCATED
 WITHIN SURFACE ROUGHNESS B-TYPE TERRAIN WHERE THE
 BUILDING IS WITHIN 100 FEET HORIZONTALLY IN ANY
 DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR
 D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FEET IN THE UPWIND
 DIRECTION...
 1609.4.2 SURFACE ROUGHNESS CATEGORIES.
 A GROUND SURFACE ROUGHNESS WITHIN EACH 45-DEGREE (0.79
 RAD) SECTOR SHALL BE DETERMINED FOR A DISTANCE UPWIND
 OF THE SITE AS DEFINED IN SECTION 1609.4.3 FROM THE
 CATEGORIES DEFINED BELOW, FOR THE PURPOSE OF ASSIGNING
 AN EXPOSURE CATEGORY AS DEFINED IN SECTION 1609.4.3.
  
 2) PLEASE REVIEW POSITIVE / NEGATIVE PRESSURES FOR
 COMPONENTS & CLADDING WITH HEIGTH AND EXPOSURE
 ADJUSTMENT FACTORS 2010 FBC-B TABLE 1609.7(2) . PLEASE
 PROVIDE MEAN ROOF HEIGHT.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 6) SHEET S-100 NOTE SERVICE DESIGN LOADS INDICATES A
 NEW FIRST FLOOR OFFICE AND PLANS INDICATE A "NEW 2ND
 FLOOR OFFICE FRAMING PLAN" THE PLANS INDICATE A 100 LBS
 IMPOSED LIVE LOAD SUPERIMPOSED STORAGE LOFT" WHICH IS
 THIS AREA TO BE USED FOR, STORAGE OR OFFICE? 107.2.1.3.
 ADDITIONAL INFORMATION REQUIRED? 2ND FLOOR OCCUPANCY
 TYPE? 2010 FBC-B 302.1.
  
 6A) PLANS DO NOT PROVIDE INFORMATION AS TO IF THE 2ND
 FLOOR MEZZANINE WILL BE CLOSED, AS IF FOR OFFICE OR
 OPEN AS IF USED FOR STORAGE? PLANS ARE DEFICIENT IN
 INDICATING STAIRS TO THE 2ND FLOOR FOR ACCESS? PLEASE
 REVIEW 2010 FBC-B 505.3 EGRESS REQUIREMENTS & 505.4
 OPENESS.
  
 6B) WILL VERTICAL ACCESSIBILITY BE REQUIRED FOR THE
 FIRST FLOOR OFFICE SPACE SINCE THE PLANS INDICATE A NEW
 6" SLAB THAT WILL BE HIGHER THAN THE SURROUNDING FLOOR
 LEVEL, NEW EXTERIOR STAIRS, AND HOW WILL ACCESSIBILITY
 BE ACHIEVED FOR THE 2ND FLOOR IF USED AS OFFICE? 2010
 FBC-B 201.1.1. VERTICAL ACCESSIBILITY.
  
 7) NEITHER SHEET A4.1 NOR S SHEETS PROVIDE A GAURDRAIL
 SYSTEM IN COMPLIANCE WITH 2010 FBC-B 1013.1 OR 1607.7.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-31 Cont ID  
Sent By rlecky Date 2012-07-31 Time 13:15 Rev Time 0.00
Received By rlecky Date 2012-07-31 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-08-10 Cont ID  
Sent By wjolin Date 2012-08-10 Time 11:05 Rev Time 0.00
Received By wjolin Date 2012-08-10 Time 10:47 Sent To  
Notes
2012-08-10 10:57:47951 OLD OKEECHOBEE ROAD
 PERMIT #12070908
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE NFPA 101.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-08-02 Cont ID  
Sent By wjolin Date 2012-08-02 Time 12:14 Rev Time 0.00
Received By wjolin Date 2012-08-02 Time 11:40 Sent To  
Notes
2012-08-02 12:03:43951 OLD OKEECHOBEE ROAD
 PERMIT #12070908
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE ? NFPA 101.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 SHEET A4.1: DOOR #100B IS LOCATED IN FIRE RATED WALL;
 HOWEVER, THE DOOR IS NOT INDICATED AS HAVING A FIRE
 RESISTANCE RATING OR CLOSER.
  
 SHEET S100: PLAN INDICATES "STORAGE LOFT" ABOVE OFFICE
 SPACE. INDICATE HOW THIS LOFT WILL BE UTITLIZED. A 42"
 PERIMETER GUARD AND STAIRS MAY BE NEEDED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-08-14 Cont ID  
Sent By jwitmer Date 2012-08-14 Time 07:51 Rev Time 0.00
Received By jwitmer Date 2012-08-08 Time 09:24 Sent To  
Notes
2012-08-08 09:26:15INCOMING SENT TO C-11. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-08-07 Cont ID  
Sent By hmoser Date 2012-08-07 Time 06:28 Rev Time 0.00
Received By hmoser Date 2012-07-25 Time 15:18 Sent To  
Notes
2012-07-25 15:18:51EXPEDITED
 C--11

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-08-07 Cont ID  
Sent By hmoser Date 2012-08-07 Time 06:28 Rev Time 0.00
Received By hmoser Date 2012-08-07 Time 06:03 Sent To  
Notes
2012-08-07 06:28:07PASS PROVISO
 PROVIDE A LETTER FROM THE ENGINEER ON HOW THE
 AIR CONDITIONING IS MOUNTED TO THE WALL FOR WIND LOADS.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-07-27 Cont ID  
Sent By lwagner Date 2012-07-27 Time 14:38 Rev Time 0.00
Received By lwagner Date 2012-07-27 Time 14:22 Sent To  
Notes
***NONE***