Plan Review Details - Permit 12070677
Plan Review Stops For Permit 12070677 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2012-07-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2012-07-25 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2012-07-25 |
Time |
08:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2012-07-19 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2012-07-19 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2012-07-19 |
Time |
14:16 |
Sent To |
|
|
Notes |
2012-07-19 14:40:53 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- ENGINEER TO PROVIDE ACTUAL RAS 117 CALCULATIONS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. | | | | 2- ENGINEER TO REVISE NAILING SPACING: | | A) THE MINIMUM FASTENER SPACING SHALL NOT BE LESS THAN | | 4" O.C. SEE RAS 117 SEC. 8.1 AND REVISE AS REQUIRED. | | | | B) ALL FRACTIONS SHALL BE ROUNDED DOWN TO THE NEXT | | WHOLE NUMBER. SEE RAS 117 SEC. 10.4.5 AND REVISE AS | | REQUIRED. | | | | C) ENGINEER TO SPECIFY THE NAIL SPACING AT THE BASE | | SHEET LAP. MISSING THE INFORMATION. SEC. 107.2.1 CITY | | AMENDMENTS TO FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2012-07-25 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2012-07-25 |
Time |
08:21 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2012-07-25 |
Time |
08:21 |
Sent To |
|
|
Notes |
2012-07-25 08:22:06 | ENGINEERING SUBMITTED. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-07-19 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2012-07-19 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2012-07-19 |
Time |
14:16 |
Sent To |
|
|
Notes |
|
|
|