Plan Review Details - Permit 12070514
Plan Review Stops For Permit 12070514
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-08-08 Cont ID  
Sent By jwitmer Date 2012-08-08 Time 13:11 Rev Time 0.00
Received By jwitmer Date 2012-08-08 Time 13:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-23 Cont ID  
Sent By jwitmer Date 2012-07-23 Time 15:01 Rev Time 0.00
Received By jwitmer Date 2012-07-23 Time 14:37 Sent To  
Notes
2012-07-23 15:57:30BUILDING PLAN REVIEW
 PERMIT: 12070514
 ADD: 300 OKEECHOBEE BLVD VS 901 S OLIVE?
 CONT: ROBLING ARCHITECTURE CONSTRUCTION, INC
 TEL: (561)662-0000
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES THE WORK TO BE
 COMPLETED UNDER THIS PERMIT IS TO BE LOCATED AT 300
 OKEECHOBEE BLVD OR PALM BEACH ATLANTIC CHAPEL WHERE AS
 THE TITLE BLOCK OF THE PLANS INDICATES THE PROJECT TO
 BE LOCATED AT 901 S OLIVE PEMBROKE HALL, PLEASE MAKE
 CORRECTION TO THE LOCATION? ADDITIONAL INFORMATION
 REQUIRED 107.2.1.3.
  
 2) PLEASE PROVIDE THE MINIMUM BUILDING TPYE, 2010 FBC-
 B 107.3.5.1.1(3)*.
  
 3)SHEET A-1PLEASE REVIEW PLATFORM CONSTRUCTION
 REQUIREMENTS: 410.4 PLATFORM CONSTRUCTION. PERMANENT
 PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS AS REQUIRED
 FOR THE TYPE OF CONSTRUCTION OF THE BUILDING IN WHICH
 THE PERMANENT PLATFORM IS LOCATED. PERMANENT PLATFORMS
 ARE PERMITTED TO BE CONSTRUCTED OF
 FIRE-RETARDANT-TREATED WOOD FOR TYPE I, II, AND IV
 CONSTRUCTION WHERE THE PLATFORMS ARE NOT MORE THAN 30
 INCHES (762 MM) ABOVE THE MAIN FLOOR, AND NOT MORE THAN
 ONE-THIRD OF THE ROOM FLOOR AREA AND NOT MORE THAN
 3,000 SQUARE FEET (279 M2) IN AREA. WHERE THE SPACE
 BENEATH THE PERMANENT PLATFORM IS USED FOR STORAGE OR
 ANY OTHER PURPOSE OTHER THAN EQUIPMENT, WIRING OR
 PLUMBING, THE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE
 SPACE BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR
 EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE
 PERMANENT PLATFORM NEED NOT BE PROTECTED.
  
 4) SHEET A-12010 FBC-B 1009.6 STAIRWAY CONSTRUCTION.
 ALL STAIRWAYS SHALL BE BUILT OF MATERIALS CONSISTENT
 WITH THE TYPES PERMITTED FOR THE TYPE OF CONSTRUCTION
 OF THE BUILDING, EXCEPT THAT WOOD HANDRAILS SHALL BE
 PERMITTED FOR ALL TYPES OF CONSTRUCTION.
  
 5) SHEET A-1 PLANS ARE MISSING DETAILS FOR HANDRAILS.
 2010 FBC-B 1009.12 STAIRWAYS SHALL HAVE HANDRAILS ON
 EACH SIDE AND SHALL COMPLY WITH SECTION 1012.
  
 6) SHEET A-2 IT APPEARS THE WORK BEING COMPLETED ON
 THIS SHEET INDICATED BY THE KEY PLAN APPEARS TO BE
 WITHIN A DIFFERENT BUILDING, POSSIBLY A DIFFERENT
 ADDRESS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-07-24 Cont ID  
Sent By rlecky Date 2012-07-24 Time 10:06 Rev Time 0.00
Received By rlecky Date 2012-07-24 Time 10:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-08-09 Cont ID  
Sent By rferguso Date 2012-08-09 Time 07:25 Rev Time 0.00
Received By rferguso Date 2012-08-09 Time 07:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-07-19 Cont ID  
Sent By wjolin Date 2012-07-19 Time 14:05 Rev Time 0.00
Received By wjolin Date 2012-07-19 Time 13:41 Sent To  
Notes
2012-07-19 14:05:19901 SOUTH OLIVE AVENUE
 PERMIT #12070514
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIRS AND
 PLATFORM ELEVATION CHANGE. HANDRAILS SHALL BE LOCATED
 NOT LESS THAN 34 INCHES AND NOT MORE THAN 38 INCHES
 ABOVE THE SURFACE OF THE TREAD, MEASURED VERTICALLY TO
 THE TOP OF THE RAIL FROM THE LEADING EDGE OF THE TREAD.
 HANDRAIL ENDS SHALL BE RETURNED TO THE WALL OR FLOOR OR
 SHALL TERMINATE AT NEWEL POSTS. HANDRAIL CROSS SECTION
 SHALL HAVE A DIAMETER OF NOT LESS THAN 1.25 INCHES AND
 NOT MORE THAN 2 INCHES.
  
 STEPS SHALL HAVE A TREAD DEPTH OF AT LEAST 13-INCHES.
 PROVIDE A CONTRASTING STRIPE ON EACH STEPPING SURFACE
 OF THE LEADING EDGE OR TREAD NOSING TO MAKE THE
 PRESENCE OF AN ELEVATION CHANGE READILY APPARENT TO
 OCCUPANTS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-08-09 Cont ID  
Sent By lmartine Date 2012-08-08 Time 17:13 Rev Time 0.00
Received By lmartine Date 2012-08-01 Time 13:52 Sent To  
Notes
2012-08-01 13:52:35B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2012-08-01 Cont ID  
Sent By hmoser Date 2012-08-01 Time 09:41 Rev Time 0.00
Received By hmoser Date 2012-07-17 Time 13:11 Sent To  
Notes
2012-07-18 13:11:56INCOMING SENT TO B03 . JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-08-01 Cont ID  
Sent By hmoser Date 2012-08-01 Time 14:11 Rev Time 0.00
Received By hmoser Date 2012-08-01 Time 14:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-08-01 Cont ID  
Sent By hmoser Date 2012-08-01 Time 09:12 Rev Time 0.00
Received By hmoser Date 2012-07-31 Time 14:24 Sent To  
Notes
2012-08-01 09:12:30PASS PROVISO
 REFER TO NOTE # 2 ON PAGE M-1 OF THE PLANS TO PAINT
 DUCT.
 IF THE DUCT IS PAINTED YOU LOSE THE UL LISTING.
 REFER TO SECTION 605.3 NONMETALLIC DUCT 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER.
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2012-07-23 Cont ID  
Sent By lwagner Date 2012-07-23 Time 09:09 Rev Time 0.00
Received By lwagner Date 2012-07-23 Time 09:09 Sent To  
Notes
2012-07-23 09:10:22NO PLUMBING AT THIS TIME

Review Stop Z ZONING
Rev No 2 Status P Date 2012-08-07 Cont ID  
Sent By jroach Date 2012-08-07 Time 10:45 Rev Time 0.00
Received By jroach Date 2012-08-07 Time 10:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-07-25 Cont ID  
Sent By jroach Date 2012-07-25 Time 15:38 Rev Time 0.00
Received By jroach Date 2012-07-25 Time 14:13 Sent To  
Notes
***NONE***