Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-07-23 Cont ID  
Sent By rlecky Date 2012-07-23 Time 11:13 Rev Time 0.00
Received By rlecky Date 2012-07-23 Time 10:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-07-20 Cont ID  
Sent By rlecky Date 2012-07-20 Time 09:17 Rev Time 0.00
Received By rlecky Date 2012-07-20 Time 08:33 Sent To  
Notes
2012-07-20 09:17:4512070429
 240 PALMETTO LANE
 20 KW GENERATOR
  
 PLEASE CLARIFY THE SCOPE OF THE ELECTRIC WORK PROPOSED.
 NEC 215.5
  
 PROVIDE A SINGLE LINE ELECTRICAL DIAGRAM SHOWING ALL
 CONDUIT AND WIRE SIZES INCLUDING THE EXISTING SERVICE
 AND METER.
 PROVIDE THE SPECIFICATIONS ON THE GENERATOR. VERIFY THE
 GENERATOR HAS A MAIN BREAKER. INDICATE THE PROXIMITY OF
 THE GENERATOR TO THE BUILDING.
 PROVIDE THE SPECIFICATIONS ON THE GENERATOR SLAB.
 PROVIDE THE SPECIFICATIONS ON THE AUTOMATIC TRANSFER
 SWITCH.
  
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-23 Cont ID  
Sent By rlecky Date 2012-07-23 Time 11:13 Rev Time 0.00
Received By rlecky Date 2012-07-20 Time 17:38 Sent To  
Notes
2012-07-20 17:39:46GAVE TO LECKY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-20 Cont ID  
Sent By rlecky Date 2012-07-20 Time 09:18 Rev Time 0.00
Received By rlecky Date 2012-07-14 Time 08:14 Sent To  
Notes
2012-07-14 08:14:34TO ZONING
  

Review Stop Z ZONING
Rev No 1 Status P Date 2012-07-19 Cont ID  
Sent By mdekle Date 2012-07-19 Time   Rev Time 0.00
Received By mdekle Date 2012-07-16 Time 08:04 Sent To E
Notes
***NONE***