Plan Review Details - Permit 12070329
Plan Review Stops For Permit 12070329
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2012-07-19 Cont ID  
Sent By lwagner Date 2012-07-19 Time 08:37 Rev Time 0.00
Received By lwagner Date 2012-07-19 Time 08:37 Sent To  
Notes
2012-07-19 08:37:46PER CONTRACTOR GAS PRESSURE 2LB

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2012-07-17 Cont ID  
Sent By lwagner Date 2012-07-17 Time 10:37 Rev Time 0.00
Received By lwagner Date 2012-07-16 Time 10:40 Sent To  
Notes
2012-07-17 10:37:31FBC FUEL GAS 2010 REVIEW #1
 DENIED:
  
 1. THE ORIGINAL PLAN FOR THE POOL HEATER #12020448
 SHOWS 1 1/4" CSST AT 78' TOTAL LENGTH. THE NEW PLAN
 ADDING A GENERATOR WOULD BE UNDERSIZED. TOTAL LENGTH
 WOULD BE 127' AT 693 TOTAL BTU (400 HEATER + 293
 GENERATOR). AT LESS THAN 2LB THE REQUIRED SIZE FOR THE
 MAIN FROM THE METER WOULD BE 2" ON TABLE 402.4(2) &
 402.4(13). THE RUN FROM THE POOL HEATER TO THE
 GENERATOR WOULD BE OK. AS AN ALTERNATE THE SYSTEM COULD
 BE CHANGED TO 2LB WITH REGULATORS.
  
 2. ***NOTE***
 THE GAS PERMIT WILL NOT BE PRINTED BEFORE THE GEN-ELECT
 PERMIT IS APPROVED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-17 Cont ID  
Sent By lwagner Date 2012-07-17 Time 10:41 Rev Time 0.00
Received By lwagner Date 2012-07-14 Time 09:10 Sent To  
Notes
2012-07-14 09:10:17TO PLUMBING < $5K