2012-07-11 09:46:30 | ****PROVISO**** |
| ****ISSUED AT CONTRACTOR'S RISK**** |
| ****PROVIDE REVISED INSTALLATION SCHEDULE AND FLOOR |
| PLAN AT INSPECTION**** |
| ****SUBJECT TO FIELD INSPECTOR'S DISCRETION, A REVISION |
| MAY BE REQUIRED**** |
| |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| 1. FBC 301.1, FAC9N-3, PLEASE REVISE THE INSTALLATION |
| SCHEDULE (FOR THE ACCORDION SHUTTERS) TO ADDRESS THE |
| FOLLOWING ISSUES: |
| |
| SUBSTRATE IS NOTED AS "CONCRETE BLOCK" BUT ANCHORING |
| FROM "CONCRETE" SUBSTRATE WAS USED, SEE SHEET 11. FOR |
| FILLED CELLS (GROUT FILLED BLOCK) OR HOLLOW BLOCK, USE |
| THE "HOLLOW BLOCK" CHART ON THE SAME PAGE. |
| |
| 2.5" EDGE DISTANCE REQUIRED, 2" PROPOSED. SEE SHEET 11, |
| ANCHOR CHART. |
| |
| 1 3/4" EMBEDMENT FOR TAPCON REQUIRED, 1 3/4" PROPOSED. |
| DUE TO STUCCO, PRODUCT THICKNESS, A LONGER FASTENER IS |
| REQUIRED. |
| |
| 2. PROVIDE A FLOOR PLAN SHOWING LOCATION OF WINDOW, |
| SHUTTER, DOOR INSTALLATION. |
| |
| INSTRUCTIONS TO CONTRACTOR - REVISE INSTALLATION |
| SCHEDULE AS INDICATED |
| PROVIDE INSTALLATION SCHEDULE AND FLOOR PLAN TO FIELD |
| INSPECTOR - SUBJECT TO INSPECTOR'S DISCRETION, REVISED |
| INSTALLATION SCHEDULE MAY BE ACCEPTED IN THE FIELD OR A |
| REVISION MAY BE REQUIRED |
| |
| DISCUSSED WITH AND AGREED TO BY CONTRACTOR |
| |
| |
| |
| |