Plan Review Details - Permit 12060539
Plan Review Stops For Permit 12060539
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-08-01 Cont ID  
Sent By rlecky Date 2012-08-01 Time 16:24 Rev Time 0.00
Received By rlecky Date 2012-08-01 Time 16:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-07-30 Cont ID  
Sent By jwitmer Date 2012-07-30 Time 09:41 Rev Time 0.00
Received By jwitmer Date 2012-07-30 Time 09:41 Sent To  
Notes
2012-07-30 09:44:54BUILDING PLAN REVIEW
 PERMIT: 12060539
 ADD: 1801 S FLAGLER # 1602
 CONT: MARYJULE CONSTRUCTION, INC
 TEL: (561)386-6032
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1-3) NOT PART OF THIS PERMIT. PERMITTED UNDER 12070057.
  
  
 4) 2ND REQUEST, SUBMITTED WERE MSDS SHEETS THE FOLOWING
 CODE SECTIONS NEED TO BE COMPLIED WITH THROUGH TESTING
 OF AN NATIONALLY RECOGNIZED TESTING FACILITY. THE
 PERMIT APPLICATION INDICATES NEW FLOORS AND THE PLANS
 INDICATE THE USE OF "EASY MAT" SOUND PROOFING, PLAESE
 PROVIDE CODE COMPLIANCE FOR;
 3A) 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 3B)2010 FBC-B 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE
 MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR
 TYPE II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND
 IN ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3:
 603.1.3.2 EXCEPTIONS:
 1 INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 5-6) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-09 Cont ID  
Sent By jwitmer Date 2012-07-09 Time 15:16 Rev Time 0.00
Received By jwitmer Date 2012-07-09 Time 15:15 Sent To  
Notes
2012-07-09 15:46:54BUILDING PLAN REVIEW
 PERMIT: 12060539
 ADD: 1801 S FLAGLER # 1602
 CONT: MARYJULE CONSTRUCTION, INC
 TEL: (561)386-6032
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET # 1 INDICATES NEW EXTERIOR WINDOWS AND SLIDING
 GLASS DOORS. NO PRODUCT TESTING REPORTS WERE SUBMITTED,
 NOTED THIS UNIT IS LOCATED ON THE 16TH FLOOR AND WILL
 ONLY NEED TO COMPLY FOR WIND.
 COMPONENTS & CLADDING 2010 FBC-B 1609.6.4.4.1.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 4) THE PERMIT APPLICATION INDICATES NEW FLOORS AND THE
 PLANS INDICATE THE USE OF "EASY MAT" SOUND PROOFING,
 PLAESE PROVIDE CODE COMPLIANCE FOR;
 3A) 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 3B)2010 FBC-B 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE
 MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR
 TYPE II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND
 IN ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3:
 603.1.3.2 EXCEPTIONS:
 1 INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 5) SHEET 1 INDICATES THE CEILINGS ARE TO BE FURRED DOWN
 3/4" WITH 3/4" FURRING CHANNELS, IS THIS HI-HAT
 MATERIAL AND IF SO HOW OFTEN IS THE HI-HAT TO BE
 FASTENED AND WITH WHAT TYPE OF FASTENER? ADDITIONAL
 INFORMATION REQUIRED 107.2.1.3.
  
 6) SHEET 1 INDICATES THE REMOVAL OF TUB AND THE
 INSTALATION OF A NEW SHOWER, PLEASE PROVIDE
 DOCUMENTATION FOR CODE COMPLIANCE FOR:
 2010 FBC-B 2509.2 BASE FOR TILE. CEMENT, FIBER-CEMENT
 OR GLASS MAT GYPSUM BACKERS IN COMPLIANCE WITH ASTM C
 1178, C 1288 OR C 1325 AND INSTALLED IN ACCORDANCE WITH
 MANUFACTURER RECOMMENDATIONS SHALL BE USED AS A BASE
 FOR WALL TILE IN TUB AND SHOWER AREAS AND WALL AND
 CEILING PANELS IN SHOWER AREAS. WATER-RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C 840 AND MANUFACTURER
 RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED
 UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING
 AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C 840.
  
 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING
 BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS:
 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2 . WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES
 (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16
 INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM)
 WATER-RESISTANT GYPSUM BACKING BOARD.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-07-31 Cont ID  
Sent By rlecky Date 2012-07-31 Time 07:44 Rev Time 0.00
Received By rlecky Date 2012-07-31 Time 07:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-06-27 Cont ID  
Sent By jleahy Date 2012-06-27 Time 08:39 Rev Time 0.00
Received By jleahy Date 2012-06-27 Time 08:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-08-02 Cont ID  
Sent By wjolin Date 2012-08-02 Time 11:26 Rev Time 0.00
Received By wjolin Date 2012-08-02 Time 11:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-06-22 Cont ID  
Sent By wjolin Date 2012-06-22 Time 11:17 Rev Time 0.00
Received By wjolin Date 2012-06-22 Time 11:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-09-10 Cont ID  
Sent By rlecky Date 2012-08-02 Time 16:53 Rev Time 0.00
Received By rlecky Date 2012-08-01 Time 16:24 Sent To  
Notes
2012-08-01 16:33:54TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-31 Cont ID  
Sent By rlecky Date 2012-07-31 Time 07:44 Rev Time 0.00
Received By rlecky Date 2012-07-18 Time 12:44 Sent To  
Notes
2012-07-19 12:45:27TO JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-12 Cont ID  
Sent By lwagner Date 2012-07-12 Time 09:03 Rev Time 0.00
Received By lwagner Date 2012-06-19 Time 16:00 Sent To  
Notes
2012-06-20 16:02:28B--8

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-07-24 Cont ID  
Sent By lwagner Date 2012-07-24 Time 14:58 Rev Time 0.00
Received By lwagner Date 2012-07-24 Time 14:51 Sent To  
Notes
2012-07-24 14:58:21B-10
 RE-STAMP

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-07-12 Cont ID  
Sent By lwagner Date 2012-07-12 Time 09:03 Rev Time 0.00
Received By lwagner Date 2012-07-12 Time 08:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-06-25 Cont ID  
Sent By eschneid Date 2012-06-25 Time 13:01 Rev Time 0.25
Received By eschneid Date 2012-06-25 Time 13:01 Sent To  
Notes
2012-06-25 13:01:30INTERIOR RENOVATION, LESS THAN 50% STRUCTURE VALUE